-COFFMAN
<br /> ENGINEERS
<br /> COPPER FEEDER SCHEDULE PANEL DESIGNATION 1101 2nd Avenue,Suite 400
<br /> Seattle,WA 98101
<br /> AMPACITY SYMBOL FEEDER RACEWAY SYMBOL FEEDER RACEWAY
<br /> AMPS ID. 3 PHASE,4 WIRE ID. 3 PHASE,3 WIRE EXAMPLE DESIGNATION: Pi 121
<br /> 20 20 4.#12, 1.#12 G 3/4" 20N 3.#12, 1.#12 G 3/4" L ph 206.623.0717
<br /> 30 30 4/10, 1.#10 G 3/4' 30N 3.#10, 1.#10 G 3/4" BUILDING FLOOR SUFFIX
<br /> 40 40 4.#8, 1/10 G 1" 4ON 3.#8, 1.#10 G 1• XX = FLOOR NUMBER 1 = FIRST IN SEQUENCE
<br /> 50 50 6, 1.#10 G I. SON 3.#6, 1.#10 G 1• PH = PENTHOUSE 2=SECOND IN SEQUENCE
<br /> www.coffman.com
<br /> 60 60 4.#4, 1.#10 G 1.5" 6ON 3.#4, 1.#10 G 1.5" BRANCH VOLTAGE
<br /> 70 70 4, 1#8 G 1.5" 70N 3.#4, 1.#8 G 1.5" L=LEGALLY REQUIRED H = 480Y/277V
<br /> 100 100 4.#2, 1.#8 G 1.5" 100N 3.#2, 1.#8 G 1.5" N =NORMAL L= 2081
<br /> 125 125 4.#1, 1.#6 G 2" 125N 3.#1, 1.#6 G 1.5" S =STANDBY
<br /> 150 150 4/1/0, 1.#6 G 2' 15ON 31)1/0, 1.#6 G 1.5' X = EMERGENCY
<br /> 175 175 4.#2/0, 1.#6 G 2N 3.#2/0, 1.#6 G 2" o
<br /> 200 200 4/3/0, 1.#6 G 2.. 20O5' 200N 3.#3/0, 1.#6 G 2' T
<br /> 225 225 41 1.#4 G 2.5" 225N 3.#4/0, 1.#4 G 2" i
<br /> 250 250 4/250 kcmil, 1.#4 G 3' 25ON 3$250 kcmil, 1.#4 G 2.5'
<br /> 300 300 4/350 kCmil, 1.#4 G 3' 30ON 3.#350 kcmil, 1.#4 G 3' GENERAL NOTES
<br /> 400 1 400 14#600 kCmil, 1#2 G 4' 40ON 13#600 kcmil, 1#2 G 3.5'
<br /> 500 500 2 SETS 4.#250 kcmil,1.#1/0 G (2)3• 50ON2 SETS 3/250 kcmil, 1.#1/0 G (2)2.5' 1. REFER TO SHEET E-0.2.
<br /> 600 600 2 SETS 4.#350 11.#1/0 G (2)3' 60ON 2 SETS 3.#350 kcmll, 1.#1/0 G (2)3"
<br /> 800 800 2 SETS 4.#600 kcmil. 1/1/0 G 2 4' 80ON 2 SETS 3/600 kcmil, 1/1/0 G 2 3.5"
<br /> 1000 1000 3 SETS 4.#500 kcmil, 1#2/0 G (3)3.5' 1000N 3 SETS 3.#500 1kcmil, 1.#2/0 G (3)3" ALLIED
<br /> 1200 1200 4 SETS 4.#350 1.#3/0 G (4)3" 12DON 4 SETS 3.#350 kcmil, 1.#3/0 G (4)3'
<br /> 1600 1600 4 SETS 4.#600 kcmil, 1.#4/0 G q 4" 160ON 4 SETS 3/600 kCmil, 1/4/0 G 4 3.5' FLAG NOTES
<br /> 2000 2000 5 SETS 4.#600 kcmil, 1.#250 kcmil G (5)q• 2000N 5 SETS 3.#600 kcmil, 1#2501 G (5)3.5" TELESIS
<br /> 2500 2500 6 SETS 4.#600 kcmil, 1.#350 kcmil G (6)q" 250ON 6 SETS 3.#600 kcmil, 1.#350 kcmil G (6)3.5" D INTERCEPT EXISTING 400 AMP SERVICE TO BE
<br /> 3000 3000 8 SETS 4.#500 kcmil, 1.#500 kcmil G (8)3.5" 3000N 8 SEFS 3.#500 1 1.#500 kcmil G (8)3.5" EXTENDED TO NEW PANELS INDICATED.
<br /> 4000 4000 10 SETS 4#600 kcmil, 1#600 kcmil G 1 4" 4000N 10 SETS 3#600 kCmil, 1#600 kcmil G 10 3.5" D REMOVE EXISTING SERVICE RUN BACK TO SOURCE.
<br /> Silver Plaza
<br /> NOTES:
<br /> 1. ALL FEEDERS ARE COPPER WITH THHN/THWN INSULATION. Floor 2
<br /> 2. FOR FEEDERS WITH AN"Si SUFFIX,DELETE THE GROUND CONDUCTOR.
<br /> 10521 19th Ave SE
<br /> Everett, WA 98202
<br /> Construction Set
<br /> Revisions
<br /> Registration
<br /> BST
<br /> PNL PNL �c
<br /> M1 P1 _
<br /> 16,179A 400A 72 -GA
<br /> 45932
<br /> 40000
<br /> S10NAL
<br /> 3012023
<br /> 400A METER
<br /> OKey Plan
<br /> M
<br /> 00 Go-
<br /> 400A
<br /> 0
<br /> 51, © 4on 0n
<br /> sc
<br /> DISC
<br /> UTILITY as
<br /> TRANSFORMER
<br /> 1 00 00
<br /> IN G na
<br /> L
<br /> ONE-LINE
<br /> DIAGRAM &
<br /> FEEDER
<br /> SCHEDULES
<br /> Scale: NONE
<br /> CEI Project No: 230312
<br /> Date: 3.7.2023
<br /> Designed: J. MAXWELL
<br /> Drawn: R. FROGGE
<br /> 1
<br /> ONE-LINE DIAGRAM Checked: B. MAXWELL
<br /> E-5.1 SCALE:NONE
<br /> Sheet Number
<br /> E-5. 1
<br />
|