Laserfiche WebLink
NEUDORFER r - <br /> NE�B:B <br /> ENGINEERS <br /> WWW.NEUDDRFERENGINEERS,COM <br /> AN Integra COMPANY <br /> Fan Coil <br /> PROJECT: Mountain Pacific Bank Office TI DATE: 8/3/2023 <br /> LOCATION: Everett,WA CONTACT: Tony Amort <br /> PROJECT#: 2023-0783 AUTHOR: <br /> SYSTEM/UNIT: FCU-01 Tested By: Tony Amort <br /> Date: 7/21/2023 <br /> Unit Data Motor Data <br /> Unit Manufacturer Trane Motor HP 1/5 HP <br /> Unit Model Number TEM4AOB18S21SCA Motor Rated Volts 208-230 Volts <br /> Unit Serial Number 22305R823V Motor Phase 1 PH <br /> Fan Rotation Counterclockwise Motor Hertz 60 Hz <br /> Drive Type Direct Drive Motor FL Amps 1.2 Amps <br /> Fan Speed High <br /> Test Pressures <br /> Test Data Actual External SP 0.19 in.we <br /> Total Design Flow 600 CFM Filter DP 0.15 in.we <br /> Total Actual Flow 630 CFM Coil DP Not Accessible in.we <br /> RA Design Flow 600 CFM <br /> RA Actual Flow 595 CFM Filter Data <br /> Motor Volts T1-T2 209 Volts Filter Manufacturer Columbia <br /> Motor Amps T1 1.0 Amps Filter Type Pleated-MERV 8 <br /> Filter Qty-S1 1 <br /> Filter Size-S1 18x2Ox2 <br /> Log: FCU-01 7/21/2023 Tony Amort (1)The volume damper is full open. <br /> FCU-01 Supply Outlet Summary <br /> System/Unit Area Served Type of Outlet Size LxW/D AK Design Prelim Final Final% Remarks <br /> Reading Type Airflow Airflow Airflow <br /> Outlet-01 Reception Flowhood CD-5 10" 1.00 300 355 320 107 <br /> Outlet-02 Reception Flowhood CD-5 10" 1.00 300 295 310 103 (1) <br /> Totals: - - - - 600 650 630 105 - <br /> FCU-01 Return Inlet Summary <br /> System/Unit Area Served Type of Inlet Size LxW/D AK Design Prelim Final Final% Remarks <br /> Readinci Type Airflow Airflow Airflow <br /> Inlet-01 Reception Flowhood RG-1 14" 1.00 600 595 595 99 <br /> Totals: - - 600 595 595 99 <br /> Neudorfer Engineers <br />