Page 8 of 32
<br />Hilti PROFIS Engineering 3.0.85
<br />www.hilti.com
<br />Company: Page: 5
<br />Address: Specifier:
<br />Phone I Fax: E-Mail:
<br />Design: 39451-2-H I LTI Date: 4/21 /2023
<br />Fastening point:
<br />4 Shear load (Most utilized anchor 1)
<br />Load Vs [lb] Capacity Vt [lb] Utilization (iv = Vs/Vt [%] Status
<br />Steel strength 34 605 6 OK
<br />Bond strength para and perp, (Dir. x+)' - - 13 OK
<br />'Shear utilization may result from parallel and perpendicular shear (see details)
<br />4.1 Steel strength
<br />Vts = ESR Value refer to ICC-ES ESR-4143
<br />Vt,s > Vs
<br />Results
<br />Vt,s [lb] Vs [lb]
<br />605 34
<br />4.2 Bond strength parallel
<br />Vt,b,Base,ll = ESR Value refer to ICC-ES ESR-4143
<br />Vt,b,ll = Vt,b,Base,l fred,E,ll - fred,s,ll ' fred,Temp
<br />Vt,b,ll ? Vs.11
<br />Variables
<br />omin [in.] c°r [in.] Smin [in.] Sir [in.] Temperature [°F]
<br />4.000 4.000 4.000 - 68
<br />Results
<br />Vt,b,ll [lb] Vt,b,Base,ll [lb] Val, [lb] fred,E,ll fred,S,ll fred,Temp Utilization avai [%]
<br />385 385 -23 1.000 1.000 1.000 6
<br />4.3 Bond strength perpendicular
<br />Vt,b,Base,l = ESR Value refer to ICC-ES ESR-4143
<br />Vt,b,l = Vt,b,Base,l - fred,E,l - fred,s,l ' fred,Temp
<br />Vtbl >— Vsl
<br />Variables
<br />Amin [in.]
<br />c°r [in.]
<br />smin [in.]
<br />S°r [in.] Temperature [°F]
<br />4.000
<br />4.000
<br />4.000
<br />- 68
<br />Results
<br />Vt,b,l [lb]
<br />Vt,b,Base,l [lb]
<br />Vsl [Ib]
<br />fred,E,l fred,S,l fred,Temp Utilization Rv,l [%]
<br />385
<br />385
<br />26
<br />1.000 1.000 1.000 7
<br />Input data and results must be checked for conformity with the existing conditions and for plausibility!
<br />PROMS Engineering ( c) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
<br />5