Laserfiche WebLink
MODULE SPECIFICATIONS QCelis Q.PEAK DUO BLK ML-G10+395 DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS <br /> RATED POWER(STC) 395 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MICROINVERTER TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 9.7 A AC <br /> MODULE VOC 45.3 V DC STATE Washington JUNCTION BOX(1) MAX.CURRENT(ISC X1.25)= 12.1 A AC <br /> MODULE VMP 36.9 V DC CITY Everett CONDUCTOR(TC-ER,COPPER(90-C))= 12 AWG BLUE RAVEN <br /> MODULE IMP 10.7 A DC WEATHER STATION SNOHOMISH CO CONDUCTOR RATING= 30 A <br /> MODULE ISC 11.1 A DC ASHRAE EXTREME LOW TEMP('C) •5 AMB.TEMP,AMP-CORRECTION= 1 <br /> VOC CORRECTION -0.27%/"C ASHRAE 2%AVG-HIGH TEMP('C) 30 ADJUSTED AMP.= 30 > 12 1 1403 N. Research Way <br /> VMP CORRECTION 434 %/'C JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 9.7 A AC Orem, UT 84097 <br /> 800.377.4480 <br /> SERIES FUSE RATING 20 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR 5 CIR 6 JUNCTION BOX(2) MAX.CURRENT(ISC X1.25)= 12.1 A AC WWW.BLUERAVENSOLAR.COM <br /> ADJ. MODULE VOC @ ASHRAE LOW TEMP 48.9 V DC NUMBER OF MODULES PER MPPT 4 8 8 CONDUCTOR(UF-B,COPPER(60-C))= 10 AWG CONFIDENTIAL-THE INFORMATION <br /> ADJ. MODULE VMP @ ASHRAE 2%AVG. HIGH TEMP 32.2 V DC DC POWER RATING PER CIRCUIT(STC) 1580 31601 13160 CONDUCTOR RATING= 30 A HEREIN CONTAINED SHALL NOT BE <br /> USED FOR THE BENEFIT OF ANYONE <br /> TOTAL MODULE NUMBER 20 CONDUIT FILL DERATE= 1 EXCEPT BLUE RAVEN SOLAR NOR <br /> SHALL IT BE DISCLOSED IN WHOLE OR <br /> MICROINVERTER SPECIFICATIONS Enphase IQ8+Microinverters STC RATING OF ARRAY 7900 AMB.TEMP.AMP.CORRECTION= 1 IN PART TO OTHERS OUTSIDE <br /> POWER POINT TRACKING(MPPT)MIN/MAX 30 - 58 V DC AC CURRENT @ MAX POWER POINT(IMP 4.8 9.7 9.7 ADJUSTED AMP = 30 > 12 1 NECIPIENTS CONNECTION WITH THIE ONSA ELEPT AND <br /> MAXIMUM INPUT VOLTAGE 60 V DC MAX.CURRENT(IMP X 1.25) 6.05 12.1 12.1 JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 9.7 A AC USE OF THE RESPECTIVE EQUIPMENT, <br /> WITHOUT THE WRITTEN PERMISSION <br /> MAXIMUM DC SHORT CIRCUIT CURRENT 15 A DC OCPD CURRENT RATING PER CIRCUIT 20 20 20 COMBINER BOX(3) MAX.CURRENT(ISC X1.25)= 12.1 A AC OF BLUE RAVEN SOLAR LLC. <br /> MAXIMUM USABLE DC INPUT POWER 440 W MAX.COMB.ARRAY AC CURRENT(IMP) 24.2 CONDUCTOR(UF-B,COPPER(60"C))= 10 AWG <br /> MAXIMUM OUTPUT CURRENT 1.21 A AC MAX.ARRAY AC POWER 580OW AC CONDUCTOR RATING= 30 A NABCEP <br /> AC OVERCURRENT PROTECTION 20 A CONDUIT FILL DERATE= 0.8 <br /> MAXIMUM OUTPUT POWER 290 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. fRISE(V) VEND(V) %VRISE AMB.TEMP.AMP-CORRECTION= 1 CERTIFIED <br /> CEC WEIGHTED EFFICIENCY 97 % VRISE SEC. 1(MICRO TO JBOX) 28.8 12 Cu. 0.93 240.93 0.39% ADJUSTED AMP.= 24 > 12.1 PV INSTALLATION <br /> VRISE SEC.2(1BOX TO COMBINER BOX) 30 10 Cu. 0.74 240.74 0.31% COMBINER BOX TO INVERTER RATED AMPS= 24.2 A AC PROFESSIONAL <br /> AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC.3(COMBINER BOX TO POI) S 8 Cu. 0.19 240.19 0.08% MAIN PV OCPD(15) MAX.CURRENT(RATED AMPS X1.25)= 30.25 A AC Scott Gurney <br /> NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 1.86 241.86 0.77% CONDUCTOR(THWN-2,COPPER(75'C TERM.))= 8 AWG #PV-011719-015866 <br /> NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 50 A CONTRACTOR: <br /> MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690.54) CONDUIT FILL DERATE= 1 BRS FIELD OPS <br /> MAXIMUM AC CURRENT 1.0 A AC AC OUTPUT CURRENT 24.2 A AC AMB.TEMP.AMP.CORRECTION= 1 800-377-4480 <br /> MAXIMUM OCPD RATING FOR AC MODULE 20 A AC NOMINAL AC VOLTAGE 240 V AC ADJUSTED AMP. = 50 <br /> GROUNDING NOTES WIRING &CONDUIT NOTES Z Q <br /> 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.47]AND[NEC 250.50-60]SHALL BE 1.ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE _0 <br /> M <br /> PROVIDED. PER[NEC 690.47],THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. O <br /> USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR(USE (V <br /> INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE 00 <br /> POLARIS BLOCK OR NEUTRAL BAR). CC a0 <br /> USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE G 0) L0 [` <br /> 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED <br /> THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER) IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF O 0 0 W W <br /> PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. LL > N N <br /> SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE Z - <br /> 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. C) .� <br /> COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR CABLE LISTED AND <br /> 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 250.122],AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS W W W <br /> PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.461. REQUIRED. LUCLU Lu <br /> 5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE <br /> 6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. O __'ie <br /> MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE W LL <br /> 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE U) X Ln i <br /> INSTALLATION <br /> 8.ENC OSURES SHALLALL BE PROPER Y PREP RED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9.EXPOSED AROOF PV DC CON(DU(CT]ORS SHALL BE USE-2,90-C RATED,WET AND UV RESISTANT,AND UL = N OCV > V V <br /> GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP V Q 06 W Q In <br /> 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES. <br /> EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90°C RATED, <br /> 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V DRAWING BY: <br /> EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND <br /> 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. Tia Bradley <br /> MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION FON <br /> WAS/, <br /> ff j 2023 *01 <br /> DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS �`` <br /> 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC � RDATEGREEN IF 4 AWG OR LARGER). POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY(OR MARKED GREY) 0 '� 1' a n U a r 18, 2023 <br /> 13.ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE 15.POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: J Y <br /> GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) ��' 0 <br /> 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.661, DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR L1-BLACK,PHASE B OR L2-RED, 'L NUMBER: <br /> ACCORDING TO[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY T <br /> 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND 'USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE <br /> CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] "USE-2 IS AVAILABLE AS UV WHITE 8 15 :37 :08686917 <br /> REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES. <br /> 18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, 54072 SHEET NAME: <br /> MEANS SHALL COMPLY WITH[NEC 690.3]]AND[NEC R MC CABLE IF DC CURRENT COMPLYING WITH [NEC690.31], [NEC 250.118(10)]. DISCONNECTING �J �FC;7S rF>it� `�1 _ E L E C CALL S <br /> 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH[NEC ss`�nN,11 FN�� O O O <br /> 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)]. <br /> REVISION: PAGE NUMBER: <br /> 0 PV6 <br />