Delayed Egress Locking System: <br />3. Activation - Verify that the delay electronics of the delayed egress locking system <br />deactivates upon actuation of the automatic sprinkler system or automatic fire <br />detection system, allowing immediate, free egress. <br />Smoke / Fire Protective Curtain Assemblies: <br />4. Qualified Personal - Testing of protective curtain assemblies shall be performed by <br />a qualified person with knowledge and understanding of the operating <br />components of the type of assembly being subject to testing. <br />5. Testing Twice Per Device - All smoke/fire protective curtains that are connected to <br />the fire alarm system shall be tested a minimum of twice per device. <br />6. Closing Without Power - All protective curtain assemblies shall be capable of <br />closing the curtain without power. <br />7. Delays - Protective curtain assemblies shall not have a delay in the initiation of <br />closing of more than 10 seconds. <br />8. Closing Speed - Protective curtain assemblies shall have an average closing speed <br />of not less than 6 in./sec or more than 24 in./sec. <br />Horizontal Sliding /Accordion / Folding Fire Doors: <br />9. Horizontal Sliding, Accordion or Folding Doors - All special-purpose horizontal <br />sliding, accordion or folding doors that are a component of a means or egress shall <br />comply with the following: <br />• Connected to the fire alarm system and close when in alarm. <br />• Shall be power operated and shall be capable of being operated manually <br />in the event of power failure. <br />• The door assembly shall have an integrated standby power supply. <br />• Exiting hardware shall accommodate for a person with disabilities, have <br />sharp contrast from the door's surface, and include both graphic images <br />and bold lettering. (Example: PUSH TO OPEN) <br />• The door shall open to the minimum required with within 10 seconds after <br />activation of the operating device. <br />PASS FAIL N/A <br />❑ ❑ ❑ <br />PASS FAIL N/A <br />❑ ❑ ❑ <br />❑ ❑ ❑ <br />❑ ❑ ❑ <br />❑ ❑ ❑ <br />❑ ❑ ❑ <br />PASS FAIL N/A <br />❑ ❑ ❑ <br />Fire Marshal's Office 1 425.257.8100 1 everettwa.gov/fire I INFORMATION HANDOUT C-5 <br />4.13.2020 I Page 9 <br />