Laserfiche WebLink
10. Smoke/Aerosol Tester- Smoke detectors will be tested in place using a Smoke ❑ ❑ ❑ <br />Detector Tester Aerosol Dispenser with Telescoping Pole to ensure smoke entry <br />into the sensing chamber and an alarm response. No magnets will be allowed. <br />11. <br />Laptop - Laptop with appropriate software to make program changes if necessary. <br />❑ <br />❑ <br />❑ <br />12. <br />Manufacturer's Testing - Any equipment required by the manufacturer's <br />❑ <br />❑ <br />❑ <br />published testing instructions. <br />Notification of Testing: <br />❑ <br />❑ <br />❑ <br />13. <br />Occupants - All building occupants shall be notified of the test. <br />❑ <br />❑ <br />❑ <br />14. <br />Monitoring Company - Monitoring Company shall place the systems(s) in "test". <br />❑ <br />❑ <br />❑ <br />15. <br />Verify Information - Verify that the monitoring company has a valid address, <br />❑ <br />❑ <br />❑ <br />proper business name, and the correct number for Snohomish County 911 (425- <br />407-3970). <br />Step 2: Signage and Markings PASS FAIL N/A <br />1. FACP Room - An approved sign shall be posted on the door to the room containing ❑ ❑ ❑ <br />the FACP. The sign shall be constructed of durable materials, permanently <br />installed, readily visible, and have a red background and white lettering that reads <br />"FIRE ALARM CONTROL PANEL INSIDE" or "FIRE ALARM ROOM" or "FACP ROOM" <br />or similar language. <br />2. Contact Information - An approved sign shall be posted at the control panel and ❑ ❑ ❑ <br />states the name of the monitoring company and the 24-hour phone number of the <br />Central Station. It shall also state that the Central Station shall be called before <br />doing any work or testing on any system being monitored. <br />3. Instructions - Reset instructions and reset code shall be clearly posted at the FACP ❑ ❑ ❑ <br />4. Floor Plan - A laminated floor plan (11"x17" minimum) for each building floor shall ❑ ❑ ❑ <br />be posted adjacent to the FACP in the Fire Control Room. It shall indicate the <br />location of all initiating devices, inspector's test valve, monitored valves and main <br />corridors, stairwells and elevators. <br />5. Dedicated Circuit -The fire alarm control panel shall be on its own dedicated <br />circuit that is labeled FACP, red in color, and locked in the ON position. <br />6. J-Boxes - It is required that all fire alarm J-boxes are painted red or labeled FIRE <br />ALARM. <br />❑ ❑ ❑ <br />❑ ❑ ❑ <br />Fire Marshal's Office 425.257.8100 1 everettwa.gov/fire I INFORMATION HANDOUT C-5 <br />4.13.2020 1 Page 2 <br />