Laserfiche WebLink
INTEGRATION OF DETECTORS COMPATIBLE CONTROL UNITS <br /> KS-PS detectors can be mixed in any order with SmartOne Fire Alarm Current Legacy <br /> legacy detectors on a Kidde Fire Systems intelligent control unit Control Unit <br /> running SmartOne protocol. (FACU)Type Product Product <br /> Single Loop ARIES®-SLX ARIES <br /> FenwaINETT'6000 <br /> MICRO SLX <br /> PEGAsys"* <br /> FenwaINET 2000* <br /> Multiple Loop ARIES®-MLX ARIES NETLink <br /> FenwaINET 8000-ML <br /> MICRO MLX <br /> PEGAsys* <br /> FenwaINET 2000* <br /> * FACUs running software revision 82.4 are compatibility-tested but <br /> not agency listed with the device(s)in this data sheet. <br /> - - - - - - - - - - - - - - - - - - - - <br /> OKS-PS or <br /> TO SMARTONE DS SERIES <br /> CONTROL UNIT CPD-7052,PSD-7152 DETECTOR TO <br /> OR or THD-7252 DETECTOR ® NEXT <br /> ANOTHER DETECTOR <br /> DETECTOR <br /> (Not Polarity <br /> Sensitive) O <br /> - - - - - - - - - - - - - - - - - - - - - - - - <br /> Figure 1: Combining Legacy Detectorswith KS Series Detectors <br /> (Class B Wiring Style Shown) <br /> NOTES: <br /> 1. Detectors are not polarity sensitive.Terminals 3 and 7 <br /> (SmartOne legacy detectors)or Terminals 2 and 4 (KS <br /> or DS Series detectors)can be reversed. <br /> 2. Detectors can be installed in any order. <br /> 3. SLC loop is not sensitive to the location of the control unit <br /> (can be left or right end of loop). <br /> 4. Four-wire loops will be wired as shown, bringing loose end <br /> of loop back to the control unit. <br /> K-71-101 3 or <br /> Kidde <br /> Effective:October 2020 <br /> Fire Systems <br />