Laserfiche WebLink
MODULE SPECIFICATIONS QCells Q.PEAK DUO BLK ML-G10+ /t 400 <br />RATED POWER (STC) <br />400 W <br />MODULE VOC <br />45.55 V DC <br />MODULE VMP <br />3&09 V DC <br />MODULE IMP <br />10.5 A DC <br />MODULE ISC <br />11.07 A DC <br />VOC CORRECTION <br />-0.27 %/-C <br />VMP CORRECTION <br />-0.34 %/'C <br />SERIES FUSE RATING <br />20 A DC <br />ADJ, MODULE VOC @ ASHRAE LOW TEMP <br />49.2 V DC <br />ADJ. MODULE VMP @ ASHRAE 2% AVG. HIGH TEMP <br />33.3 V DC <br />MICRUINVtKILKSPLUI`ILA IIUNS <br />LnphaselQ8+Mcroinverters <br />POWER POINT TRACKING (MPPT) MIN/MAX <br />30 - 58 V DC <br />MAXIMUM INPUT VOLTAGE <br />60 V DC <br />MAXIMUM DC SHORT CIRCUIT CURRENT <br />15 A DC <br />MAXIMUM USABLE DC INPUT POWER <br />440 W <br />MAXIMUM OUTPUT CURRENT <br />1,21 A AC <br />AC OVERCURRENT PROTECTION <br />20 A <br />MAXIMUM OUTPUT POWER <br />290 W <br />CEC WEIGHTED EFFICIENCY <br />97 % <br />AC PHOTOVOLAAIC MODULE MARKING (NEC <br />NOMINAL OPERATING AC VOLTAGE <br />NOMINAL OPERATING AC FREQUENCY <br />MAXIMUM AC POWER <br />MAXIMUM AC CURRENT <br />MAXIMUM OCPD RATING FOR AC MODULE <br />GROUNDING NOTES <br />240 V AC <br />47 - 68 HZ AC <br />240 VA AC <br />1.0 A AC <br />20 A AC <br />DESIGN LOCATION AND TEMPERATURES <br />TEMPERATURE DATA SOURCE ASHRAE 2% AVG. HIGH TEMP <br />STATE Washington <br />CITY Everett) <br />WEATHER STATION SNOHOMISH CO <br />ASHRAE EXTREME LOW TEMP (-C) -5 <br />ASHRAE 2% AVG. HIGH TEMP (-C) 30 <br />WUFM FI FCTRICAI SPFCIFICATIONS CIR 1 CIR 2 CIR 1 CIR 4 CIR S CIR 6 <br />NUMBER OF MODULES PER MPPT <br />8 <br />DC POWER RATING PER CIRCUIT (STC) <br />3200 <br />8 <br />TOTAL MODULE NUMBER <br />320D <br />STC RATING OF ARRAY <br />AC CURRENT @ MAX POWER POINT (IMP <br />9.7 <br />MAX. CURRENT (IMP X 1.25) <br />12.1 <br />OCPD CURRENT RATING PER CIRCUIT <br />20 <br />9.7 <br />MAX. COMB. ARRAY AC CURRENT (IMP) <br />232OW AC <br />MAX. ARRAY AC POWER <br />AC VOLTAGE RISE CALCULATIONS <br />DIST (FT) <br />COND. <br />JRISE(V) VEND(V) %VRISE <br />VRISE SEC. 1(MICRO TO JBOX) <br />28.8 <br />12 Cu. <br />0.93 <br />240.93 <br />0.39% <br />VRISE SEC. 2 (JBOX TO COMBINER BOX) <br />45 <br />10 Cu. <br />1.11 <br />241.11 <br />0.46% <br />VRISE SEC. 3 (COMBINER BOX TO POI) <br />5 <br />10 Cu. <br />0.12 <br />240L12 <br />0.05% <br />TOTAL VRISE <br />2.16 <br />242.16 <br />0.90% <br />PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL (NEC 690. <br />AC OUTPUT CURRENT <br />NOMINAL AC VOLTAGE <br />1. A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH [NEC 690.471 AND [NEC 250.50-601 SHALL BE <br />PROVIDED. PER [NEC 690.471, THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE <br />USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR <br />INADEQUATE, OR IS ONLY METALLIC WATER PIPING, A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE <br />USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. <br />2. THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN <br />THE GROUNDING ELECTRODE AND THE PANEL (OR INVERTER) IF SMALLER THAN #6 AWG COPPER WIRE <br />PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR <br />SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER [NEC 250.64(C)]. <br />3. GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG <br />COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. <br />4. PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO [NEC 250.211, [NEC TABLE 250.1221, AND ALL METAL <br />PARTS OR MODULE FRAMES ACCORDING TO [NEC 690.461. <br />5. MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO NEC 690.42]. <br />6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A <br />MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. <br />7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE <br />MANUFACTURER'S INSTALLATION INSTRUCTIONS. <br />8. ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN <br />GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. <br />9. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVISES <br />EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. <br />10. GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER, SOLID OR STRANDED, AND BARE WHEN <br />EXPOSED. <br />11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A <br />MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO <br />DAMAGE). <br />12. GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLOR CODED GREEN (OR MARKED <br />GREEN IF 4 AWG OR LARGER). <br />13. ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE <br />GROUNDED BUSHINGS AT BOTH ENDS. <br />14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.471, [NEC TABLE 250.661, DC SYSTEM GEC SIZED <br />ACCORDING TO [NEC 250.1661, MINIMUM 8 AWG WHEN INSULATED, 6 AWG WHEN EXPOSED TO DAMAGE. <br />15. EXPOSED NON -CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND <br />CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH [NEC 250.1341 OR [NEC 250.136(A)] <br />REGARDLESS OF VOLTAGE. <br />WIRING & CONDUIT NOTES <br />9.7 A AC <br />240 V AC <br />CONDUCTOR SIZE CALCULATIONS <br />MICROINVERTER TO <br />MAX. SHORT CIRCUIT CURRRENT (ISC) = <br />JUNCTION BOX (1) <br />MAX. CURRENT (ISC X1.25) = <br />CONDUCTOR (TC-ER, COPPER (90°C)) = <br />CONDUCTOR RATING = <br />AMB. TEMP. AMP. CORRECTION = <br />ADJUSTED AMP. = <br />JUNCTION BOX TO <br />MAX. SHORT CIRCUITCURRRENT (ISC) = <br />JUNCTION BOX (2) <br />MAX. CURRENT (ISC X1.25) = <br />CONDUCTOR (UF-B, COPPER (60°C)) = <br />CONDUCTOR RATING = <br />CONDUIT FILL DERATE = <br />AMB. TEMP. AMP. CORRECTION = <br />ADJUSTED AMP. = <br />JUNCTION BOX TO <br />MAX. SHORT Cl RCUI T CURRRENT (ISC) = <br />COMBINER BOX (3) <br />MAX. CURRENT (ISC X1.25) = <br />CONDUCTOR (UF-B, COPPER (60-C)) = <br />CONDUCTOR RATING = <br />CONDUIT FILL DERATE <br />AMB. TEMP. AMP. CORRECTION = <br />ADJUSTED AMP. = <br />COMBINER BOX TO <br />INVERTER RATED AMPS = <br />MAIN PV OCPD (15) <br />MAX. CURRENT (RATED AMPS X1.25) = <br />CONDUCTOR (THWN-2, COPPER (75-C TERM.)) = <br />CONDUCTOR RATING = <br />CONDUIT FILL DERATE = <br />AMB. TEMP, AMP. CORRECTION = <br />ADJUSTED AMP. = <br />1. ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE <br />APPLICATIONS. <br />2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR (USE <br />POLARIS BLOCK OR NEUTRAL BAR). <br />3. ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT. REDUCING WASHERS DISALLOWED ABOVE <br />LIVE PARTS, MEYERS HUBS RECOMMENDED <br />4. UV RESISTANT CABLE TIES (NOT ZIP TIES) USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF <br />SURFACE IN ACCORDANCE WITH [NEC 110.2,110.3(A-B)]. <br />5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE <br />MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. <br />6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2, AND SINGLE -CONDUCTOR CABLE LISTED AND <br />IDENTIFIED AS PV WIRE, TYPE TC-ER, OR EQUIVALENT; ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS <br />REQUIRED. <br />7. ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO [NEC 690.8] FOR MULTIPLE <br />CONDUCTORS. <br />8. ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/81, ABOVE <br />THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE <br />310.15(B)(3)(A)],& [NEC 310.15(13)(3)(C)]. <br />9. EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2, 90-C RATED, WET AND UV RESISTANT, AND UL <br />LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP <br />EDGES. <br />10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90°C RATED, <br />WET AND UV RESISTANT, RATED FOR 600V <br />11.4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND <br />MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. <br />12. ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION <br />13. VOLTAGE DROP LIMITED TO 2% FOR DC CIRCUITS AND 3% FOR AC CIRCUITS <br />14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC <br />POSITIVE- RED (OR MARKED RED), DC NEGATIVE- GREY (OR MARKED GREY) <br />15. POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: <br />DC POSITIVE- GREY (OR MARKED GREY), DC NEGATIVE- BLACK (OR MARKED BLACK) <br />16. AC CONDUCTORS >4AWG COLOR CODED OR MARKED: PHASE A OR L1- BLACK, PHASE B OR L2- RED, <br />PHASE C OR L3- BLUE, NEUTRAL- WHITE/GRAY <br />USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE <br />" USE-2 IS AVAILABLE AS UV WHITE <br />17. RIGID CONDUIT, IF INSTALLED, (AND/OR NIPPLES) MUST HAVE A PULL BUSHING TO PROTECT WIRES. <br />18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, <br />FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.311, [NEC 250.118(10)1. DISCONNECTING <br />MEANS SHALL COMPLY WITH [NEC 690.131 AND [NEC 690.151. <br />19. CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18" BELOW ROOF SURFACE COMPLYING WITH [NEC <br />230.6(4)] AND SECURED NO GREATER THAN 6' APART PER [NEC 330.30(B)]. <br />9.7 AAC <br />12.1 A AC <br />12 AWG <br />30 A <br />1 <br />30 > <br />9.7 A AC <br />12.1 AAC <br />10 AWG <br />30 A <br />I <br />1 <br />30 > <br />9.7 A AC <br />12.1 A AC <br />10 AWG <br />30 A <br />1 <br />1 <br />30 > <br />9.7 A AC <br />12.1 AAC <br />10 AWG <br />35 A <br />1 <br />1 <br />35 > <br />BLUE RAVEN <br />12.1 <br />1403 N. Research Way <br />Orem, UT 84097 <br />800.377.4480 <br />W W W. BLU ERAVENSOLAR.COM <br />CONFIDENTIAL -THE INFORMATION <br />HEREIN CONTAINED SHALL NOT BE <br />USED FOR THE BENEFIT OF ANYONE <br />EXCEPT BLUE RAVEN SOLAR NOR <br />SHALL IT BE DISCLOSED IN WHOLE OR <br />12.1 <br />IN PART TO OTHERS OUTSIDE <br />RECIPIENTS ORGANIZATION, EXCEPT <br />IN CONNECTION WITH THE SALE AND <br />USE OF THE RESPECTIVE EQUIPMENT, <br />WITHOUT THE WRITTEN PERMISSION <br />OF BLUE RAVEN SOLAR LLC. <br />NABCEP <br />12.1 <br />CERTIFIED <br />PV INSTALLATION <br />PROFESSIONAL <br />Scott Gurney <br />#PV-011719-015866 <br />CONTRACTOR: <br />BRS FIELD OPS <br />12.1 <br />800-377-4480 <br />Z <br />0 0 <br />CQ 04 <br />G QD <br />0 0 <br />LL }' <br />Z j <br />M -0 <br />W -0 (6 <br />0 <br />L a <br />O <br />0 Lu I__ Lu <br />DRAWING BY: <br />Q Q <br />N Y <br />Vr) 04 <br />04 CO <br />N N <br />Cn U) <br />LU Lu <br />Cn y <br />Q 0 <br />Brendan Fillmore <br />DATE: <br />June 9, 2023 <br />PROJECT NUMBER: I <br />750417 <br />ELEC CALCS <br />REVISION: I PAGE NUMBER: <br />M <br />