Laserfiche WebLink
Seatronics, Inc. <br />Acceptance Test Procedure #111137 <br />Boeing Everett Final Assembly VESDA Systems <br />6.0 ACCEPTANCE TESTS - TROUBLE CONDITIONS <br />6.1 DESCRIPTION OF EVENTS <br />Verify trouble responses specified in Tables 6-1 thru 6-5. For each trouble <br />condition listed, the appropriate system response should occur. <br />6.2 To verify control panel trouble conditions, perform the following: <br />6.2.1 Disconnect appropriate wire ' X' or perform instruction listed in <br />Table 2. <br />6.2.2 Verify indicated response(s) by placing check mark in the <br />appropriate box or space. <br />6.2.3 Press control panel trouble acknowledge switch to silence trouble <br />audible if sounding. <br />7.0 SECURE FROM TEST <br />7.1 Verify the 120VAC power source to the fire alarm control panel(s) has been <br />restored. <br />7.2 Verify that the control panel(s) is in normal supervisory condition. <br />7.3 Instruct the operating personnel in the proper operation of the system. <br />