Laserfiche WebLink
„�i rtest <br />Preliminary TAB Report <br />PROJECT: Angry Crab Shack <br />LOCATION: Everett, WA <br />PROJECT #: 230180 <br />DATE: <br />CONTACT: <br />10/5/2023 <br />Tyler Balazic <br />SYSTEM/UNIT: EF-01 <br />Tested By: <br />Tyler Balazic <br />AREA: Rooftop <br />Date: <br />10/5/2023 <br />Unit ... <br />Motor <br />Data <br />Unit Location Roof <br />Motor Manufacturer <br />A.O. Smith <br />Unit Serves Kitchen Hood <br />Motor HP <br />3 HP <br />Unit Manufacturer Captive -Aire <br />Motor RPM <br />1725 RPM <br />Model Number NCA24FA <br />Motor Rated Volts <br />208 - 230 / 460 Volts <br />Serial Number 867818 <br />Motor Phase <br />3 <br />Fan Type / Class BI / I <br />Motor Hertz <br />60 Hz <br />Motor FL Amps <br />9.4 / 4.7 Amps <br />Ell <br />Motor Service Factor <br />1.15 <br />Fan RPM Actual 942 RPM <br />Motor RPM Actual 1765 RPM <br />Sheave <br />Data <br />Motor Fan <br />Drive Type <br />Belt Belt <br />Sheave Model <br />2VP42 Not Legible <br />Bore Size <br />7/8” in. 1" in. <br />Number of Belts <br />2 <br />Belt Size <br />BX29 <br />Centerline <br />8 in. <br />Air Test <br />Data <br />Design Actual <br />Total Fan CFM <br />5775 CFM 6105 CFM <br />Log: <br />EF-01 10/5/2023 <br />Tyler Balazic No access to record running amps & volts. <br />Airtest Co. LLC <br />