Laserfiche WebLink
,A.i <br />Preliminary TAB Report <br />PROJECT: Angry Crab Shack <br />LOCATION: Everett, WA <br />PROJECT #: 230180 <br />SYSTEM/UNIT: EF-01/Kitchen Hood-01 <br />Unit Data <br />Hood Manufacturer CaptiveAire <br />Hood Model Number 5424 R <br />Design Exhaust Airflow <br />5775 CFM <br />Calculated Exhaust Airflow <br />6260 CFM <br />Total Filters Height <br />16.00 in. <br />Total Filters Width <br />280.00 in. <br />Total Filter Area <br />31.11 Sq Ft <br />Filter Factor <br />0.78 <br />Total Readings - Exhaust <br />14 <br />Sum of Readings - Exhaust <br />3611 FPM <br />Ava Velocitv - Exhaust <br />258 FPM <br />EA-Reading001 <br />219 <br />FPM <br />EA-Reading002 <br />237 <br />FPM <br />EA-Reading003 <br />291 <br />FPM <br />EA-Reading004 <br />248 <br />FPM <br />EA-Reading005 <br />304 <br />FPM <br />EA-Reading006 <br />290 <br />FPM <br />EA-Reading007 <br />247 <br />FPM <br />EA-Reading008 <br />251 <br />FPM <br />EA-Reading009 <br />250 <br />FPM <br />EA-Reading010 <br />202 <br />FPM <br />EA-Reading011 <br />274 <br />FPM <br />EA-Reading012 <br />269 <br />FPM <br />EA-Reading013 <br />253 <br />FPM <br />EA-Readina014 <br />276 <br />FPM <br />DATE: 10/5/2023 <br />CONTACT: Tyler Balazic <br />Tested By: Tyler Balazic <br />Date: 10/5/2023 <br />Filter <br />Data <br />Filter Manufacturer <br />Captivaire <br />Filter Model Number <br />Captrate <br />Filter Type <br />Baffle <br />Filter Quantity <br />14 <br />Filter Size <br />16 x 20 <br />Log: EF-01/Kitchen Hood-01 10/5/2023 Tyler Balazic Nominal area 31.11 sqft x manufacturer provided <br />filter factor 0.78 = corrected area of 24.27 <br />Airtest Co. LLC <br />