Laserfiche WebLink
„�i rtest <br />Preliminary TAB Report <br />PROJECT: Angry Crab Shack <br />LOCATION: Everett, WA <br />PROJECT #: 230180 <br />DATE: <br />CONTACT: <br />10/5/2023 <br />Tyler Balazic <br />SYSTEM/UNIT: MAU-01 <br />Tested By: <br />Tyler Balazic <br />AREA: Rooftop <br />Date: <br />10/5/2023 <br />Unit ... <br />Motor <br />Data <br />Unit Location Roof <br />Motor Manufacturer <br />Dayton <br />Unit Serves Kitchen Hood <br />Motor HP <br />1 1/2 HP <br />Unit Manufacturer Captive -Aire <br />Motor RPM <br />1725 RPM <br />Model Number Not Legible <br />Motor Frame <br />56H <br />Serial Number Not Legible <br />Motor Rated Volts <br />208 - 220 / 440 Volts <br />Fan Type / Class FC / I <br />Motor Phase <br />3 <br />Motor Hertz <br />60 Hz <br />Ell'1. <br />Motor FL Amps <br />5.0 / 2.5 Amps <br />Fan RPM Actual 909 RPM <br />Motor Service Factor <br />1.2 <br />Motor RPM Actual 1703 RPM <br />Nominal Efficiency <br />78.5 Eff. <br />Electrical Test Data <br />Sheave <br />Data <br />Motor Amps 1 5.6 Amps <br />Motor Fan <br />Drive Type <br />Belt Belt <br />Sheave Model <br />2VP56 Not Legible <br />Bore Size <br />5/8” in. 3/4" in. <br />Number of Belts <br />2 <br />Belt Size <br />A49 <br />Centerline <br />15 in. <br />Air Test <br />Data <br />Design Actual <br />Total Fan CFM <br />4970 CFM 3110 CFM <br />Log: <br />MAU-01 10/5/2023 Tyler Balazic Mesh filters plugged, removed during balancing. <br />MAU-01 10/5/2023 Tyler Balazic Airflow is low of design. Attempted to remove <br />plugged mesh filters. Fan is at max service factor <br />amp draw. Unable to properly read voltage at this <br />time. <br />Airtest Co. LLC <br />