Laserfiche WebLink
„�i rtest <br />Preliminary TAB Report <br />PROJECT: Angry Crab Shack <br />LOCATION: Everett, WA <br />PROJECT #: 230180 <br />SYSTEM/UNIT: MAU-01/Duct-01 <br />DATE: 10/5/2023 <br />CONTACT: Tyler Balazic <br />Tested By: Tyler Balazic <br />Date: 10/5/2023 <br />Traverse Location <br />Inlet Duct <br />Sum of Readings 2488 FPM <br />Type of Traverse <br />Rectangular <br />Design Velocity <br />994 FPM <br />Test Instrument Used <br />Velgrid <br />Average Velocity <br />622 FPM <br />Inner Height <br />30 in. <br />Design Total Flow (CFM) <br />4970 CFM <br />Inner Width <br />24 in. <br />Actual Total Flow (CFM) <br />3110 CFM <br />Duct Area <br />5.000 sq. ft. <br />Fan RPM <br />909 RPM <br /># of Rows (T-B) <br />2 <br />Readings Per Row (L-R) <br />2 <br />Total Readings <br />4 <br />Row 1 <br />Row 2 <br />Traverse Data Points <br />661 636 <br />594 1`37 <br />0 <br />M <br />24 <br />Airtest Co. LLC <br />