Laserfiche WebLink
Part 2 —Automatic Functional Test: PASS FAIL N/A <br />1. Reset System - The contractor shall reset the system and ensure that the ❑ ❑ ❑ <br />equipment under the hood is on and power/gas is being supplied. <br />2. Activate Fusible Link - Initiate the automatic functional test by having the ❑ ❑ ❑ <br />contractor activate the most remote fusible link or detector. <br />3. Fire Alarm Activation - If the building is equipped with a fire alarm system, did the <br />❑ ❑ ❑ <br />activation of the system activate local notification device/bell and activate an <br />alarm signal (clearly illustrating the type and location of alarm) at the fire alarm <br />panel? <br />4. Power & Fuel Shutdown - Did the activation of the system shut down power and <br />❑ ❑ ❑ <br />fuel supply to ALL equipment protected under the hood and the makeup air <br />suppling the hood? Does it have to be manually reset after system activation? <br />5. Exhaust Fan - Did the activation of the system turn on or keep on the exhaust fan <br />❑ ❑ ❑ <br />and did they continue to operate during and after then system discharge? <br />6. Visual Indicator - Did the visual indicator on the control head illustrate that the <br />❑ ❑ ❑ <br />system has operated? <br />Returning System to Operational Condition <br />PASS FAIL N/A <br />1. Operational Conditions - After completion of all functional testing, the following ❑ ❑ ❑ <br />shall be done to return the system to operational conditions: <br />• Each agent tank shall be reconnected. <br />• All power/gas has been restored. <br />• If the system is connected to an alarm, the alarm shall be taken off test. <br />• All cooking equipment shall be in its approved locations. <br />• All grease filters shall be installed. <br />• The contractor verifies that the system is fully operational. <br />2. NFPA 17 Report - Prior to final approval the installing contractor shall complete, ❑ ❑ ❑ <br />sign, and provide a copy of the NFPA 17A acceptance test report. <br />Fire Marshal's Office 425.257.8100 1 everettwa.gov/fire INFORMATION HANDOUT C-10 4.29.2020 1 Page 7 <br />