FACP BATTERY CALCULATIONS <br /> COMPONENTS QTY. CURRRENT CURRENT PEM POWER CABLE (SUPPLIED <br /> AFC-100(FACP) 1 0.13000A 0.22000A WITH PEM) <br /> UD-2000(DACT) 1 0.01600A 0.02300A 6 5 3 4 <br /> SLC DEVICES SUPERVISORY ALARM <br /> CURRENT CURRENT <br /> PAD-PD 6 0.00030A 0.00030A 0.00180A 0.00180A 1 <br /> PAD-HD 2 0.00030A 0.00030A 0.00060A 0.00060A <br /> PAD-DUCT 0 0.00030A 0.00030A O.o000OA O.Oo000A <br /> PAD100-PSSA/PSDA 3 0.00020A 0.00020A 0.00060A 0.00060A <br /> PAD100-RM 0 0.00024A 0.00024A O.o000OA 0.000OOA ^ <br /> PAD-MIM 0 0.00020A 0.00040A O.00000A 0.000OOA �3/4 C - 2#14THHN,1#14G <br /> 0O <br /> PAD100-DIM 0 0.00024A 0.00024A O.o0000A O.00OA L, TG-PEM <br /> STANDBYALARM <br /> CURRENT CURRENT <br /> NAC CKT z <br /> NAC CKT 1(AUX PWR) 0.018A 0.11000A 0.01800A 0.11000A FACP EVi-FA-45-203 TG-TES <br /> o.oaA o.z8looA o.000aoA 0.28100A (BY FIRE ALARM VENDOR) °flN 1 1 4 7 <br /> O.OGA O.o0000A O.00000A O.Oo000A <br /> SLC ALARM LED O.00A 0.03600A O.00o00A 0.03600A R <br /> TOTAL 0.15700A 0.67300A 3 <br /> TOTAL STANDBY CURRENT DRAW= 0.157 AMPS T <br /> X STANDBY TIME 48 HOURS <br /> STANDBY AMP HOUR TOTAL= 7.536 AH DC STC2 STCI TRIP BATT AC <br /> TOTAL ALARM CURRENT DRAW= 0.673 AMPS 1 2 1 2 3 4 5 6 1 2 3 1 2 G <br /> X ALARM TIME 0.167 HOURS BB 0 GOO BB <br /> ALARM AMP HOUR TOTAL= 0.112 AH <br /> STANDBY AH + ALARM AH = 7.65 AH <br /> X DE-RATING FACTOR 1.20(20%) am EDL(u NEEDED) <br /> TOTAL AH REQUIRED= 9.18 AH <br /> MINIMUM BATTERY SIZE NEEDED: 10 AH <br /> BATTERY SIZE PROVIDED: 12 AH <br /> NOTE: 0.167 EQUALS 10 MINUTES OF ALARM TIME <br /> 3/4"C - (1) PHONE CABLE, <br /> (1) 2 CONDUCTOR FPL OR <br /> APPROVED EQUAL <br /> FACP VOLTAGE DROP CALCULATION v <br /> CONSTRUCTION NOTES <br /> CIRCUIT SUPPLY ALARM OHMS NGT TOTAL LAST DEVICE ;DROP <br /> TAG <br /> NAME VOLTAGE CURRENT WIRE TYPE 1000 FEET RESISTANCE VOLTAGE % PROVIDE CELLULAR DIALER, AND MOUNT ADJACENT TO <br /> NAC1(AUX) 20.4 VDC 0.110 A #14AWG SOLID 3.07 10 0.0614 20.393 VDC 0.03% THE BUILDING FACP. CONFIGURE DIALER TO PROVIDE <br /> NAC2 20.4 VDC 0.281 A #14AWG SOLID 3.07 145 0.8903 2015 VDC 1.23% SOLE PATH COMMUNICATION. DIALER SHALL BE <br /> N/A 20.4 VDC 0.000 A #14AWG SOLID 3.07 G O 00.00 VDC O% FIRE ALARM SYSTEM COMMUNICATIONS DETAIE COMPATIBLE WITH AT&T CELL SERVICE. <br /> N/A 20.4 VDC 0.000 A #14AWG SOLID 3.07 0 0 00.00 VDC o% SCALE: NONE E260 E506 <br /> PROVIDE (1) CONDUIT PENETRATION FOR PHONE AND <br /> FIRE ALARM CONNECTIONS. WIRE AS SHOWN. PROVIDE <br /> ADDRESSABLE MODULE AS NECESSARY TO PROVIDE <br /> DOS STEP 1: VERIFY SIGNAL STRENGTH AT PROPOSED LOCATION FOR CELLULAR COMMUNICATOR PANEL INDICATED ON GENERAL TROUBLE ALARM FROM CELLULAR DIALER TO <br /> O�c� X000 5 5ti � DRAWINGS. IF ACCEPTABLE *SIGNAL STRENGTH IS ACQUIRED, SKIP TO STEP 5. BUILDING FACP. <br /> TO <br /> ��F 00 L� X00 c0 cOv PDQ STEP 2: IF ORIGINALLY PROPOSED LOCATION IS INADEQUATE, FIELD TEST *SIGNAL STRENGTH WITHIN A 20FT RADIUS 3 PROVIDE (1) CONDUIT PENETRATION FOR 24/12VDC <br /> IDENTIFY LOC <br /> ON <br /> LULA <br /> �P eJ� �� eJ �� �� <br /> COORDINATE THEAFIINNALSANTENNALLOCATIONSWITH BIOEINGFAND SSP CERUSE SL(IFLIMPACTED) FOR POWER SUPPLY. PROVIDPOWER AND EARTH GROUNPOWER ANDFROMEEXPANSION FACP <br /> F F S F S S S CELLULAR MONITORED BY TYCO AND APPROVAL PRIOR TO ROUGH-IN AND SKIP TO STEP 4. MODULE AND WIRE AS SHOWN. MAINTAIN <br /> 1:07 L1:05 _1:06 1:08 _1:02 1:09 _1:04 _1:03 L1:01 ANALOG PHON� LINE DIALER SIGNAL SENT TO CENTRAL STEP 3: IF ACCEPTABLE *SIGNAL STRENGTH IS NOT ACHIEVED WITHIN 20FT OF ORIGINAL PROPOSED LOCATION FOR MANUFACTURER'S REQUIRED 1/4" SEPARATION <br /> (PRIMARY TG-7FS-A BOEING FIRE DEPARTMENT CELLULAR COMMUNICATOR PANEL, PROPOSE ALTERNATE LOCATION FOR CELLULAR PANEL. COORDINATE BETWEEN POWER AND COMMUNICATION WIRING. <br /> 45-203 FACP *TWO SEPARATE PATHWAYS FOR SIGNAL REQUIRED BY CODE, AS SHOWN. WITH BOEING AND SPACE USERS FOR POTENTIAL LOCATIONS, PREFERABLY NEAR ORIGINAL LOCATION. ® PROVIDE PHENOLIC LABEL, WHITE LETTERING, RED <br /> NAC2 STEP 4: LOCATE AND PROVIDE EXTERNAL CELLULAR ANTENNA, EXTERIOR MOUNTING BRACKET AND COAXIAL CABLE BACKGROUND, THAT READS: <br /> 15CD 15CD 30CD 75CD FROM CELLULAR COMMUNICATOR TO THE ANTENNA. THE ANTENNA AND PANEL SHOULD BE LOCATED <br /> WITHIN 20FT OF EACH OTHER. "FIRE ALARM CELLULAR DIALER" <br /> G0°6 G0°� <br /> ANALOG PHONE LINE STEP 5: PROVIDE 24VDC POWER, MONITORING CIRCUIT, AND TELEPHONE LINE TO CELLULAR COMMUNICATOR FROM PROVIDE CELL ANTENNA AND EVALUATE FIELD SIGNAL <br /> O� O� (SECONDARY) BUILDING FACP. STRENGTH IN ACCORDANCE WITH DETAIL 2. INSTALL <br /> eS eS EVT-FA-45-203 STEP 6: PROVIDE REQUIRED SET-UP, PROGRAMMING AND TESTING OF CELLULAR COMMUNICATOR EQUIPMENT PER CONDUIT AND EXTENDED ANTENNA CABLE AS <br /> THE MANUFACTURER'S INSTRUCTIONS. CELLULAR DIALER SHALL BE CONFIGURED AND INSTALLED AS A NECESSARY TO REMOTE MOUNT ANTENNA IF COVERAGE <br /> 01SOLEPATH FOR FIRE COMMUNICATIONS. IS NOT SUITABLE AT FACP LOCATION. UPDATE BOM <br /> S S B'/11c" WO BOEING LEND CABLE LENGTH AND PROVIDE REDLINES <br /> L1:11 L1:10 <br /> SLC 3/4"C - 4#12 *ACCEPTABLE SIGNAL STRENGTH SHALL BE DETERMINED BY MANUFACTURERS SPECIFICATIONS AND LOCAL AHJ 6 FOR REMOTE INSTALLATIONS PROVIDE PHENOLIC LABEL, <br /> ORDINANCES. <br /> WHITE LETTERING, RED BACKGROUND, THAT READS: <br /> BUILDING FIRE ALARM SYSTEM RISER "FIRE ALARM CELLULAR ANTENNA" <br /> SCALE: NONE E506 <br /> CELLULAR COMMUNICATOR INSTALLATION SEQUENCE [Z::_-�:- INSIDE CELL ENCLOSURE POST COMMUNICATOR <br /> SETTINGS AND CELLUAR PHONE NUMBER. PROVIDE <br /> 4520 BUILDING SYSTEM FACP POINTS SCALE: NONE E260 E506 PRINTED LABEL, HANDWRITTEN INFORMATION IS NOT <br /> ACCEPTABLE. PROVIDE SETTINGS AND CELLULAR <br /> INFORMATION TO BOEING ENGINEER. <br /> POINT NUMBER/ZONE BOEING DESCRIPTION FACP POINT - COMMENTS - GRID/SHEET LOC. <br /> _1:001 1 SMK @ FACP FACP SMOKE DETECTOR - B3/E260 <br /> L1:002 XX 2 SMK OFFICE WEST OFFICE WEST SMOKE DETECTOR - 33/260 <br /> _1:003 3 SMK OFFICE CENTER OFFICE CENTER SMOKE DETECTOR - A2/260 <br /> _1:004 XX 4 SMK OFFICE EAST OFFICE EAST SMOKE DETECTOR - A1/260 <br /> _1:005 5 HEAT WOMEN RESTROOM WOMENS R.R. HEAT DETECTOR - A4/260 BILL �F MATERIALS <br /> _1:006 6 HEAT MEN RESTROOM MENS R.R. HEAT DETECTOR - A4/260 ITEM QTY. PART N0. MANUFACTURER DESCRIPTION <br /> L1:007 7 MAN PULL DR N1 NORTH EXIT MANUAL PULL - A4/260 1 1 3992753 POTTER FIRE ALARM CONTROL PANEL <br /> _1:008 8 MAN PULL DR S1 S.W. EXIT MANUAL PULL - A4/E260 2 1 3992769 POTTER UD-2000 DACT CARD <br /> L1:009 9 MAN PULL DR S2 S.E. EXIT MANUAL PULL - A2-E260 3 8 3992732 POTTER PAD100 6" BASE <br /> L1:010 10 45-296 SMK EAST BLDG. 296 EAST SMOKE DETECTOR - Al 4 6 3992770 POTTER PAD200 PHOTO DETECTOR <br /> _1:011 11 45-296 SMK WEST BLDG. 296 WEST SMOKE DETECTOR - A3 5 2 3992735 POTTER PAD100 HEAT DETECTOR(1350 FIXED) <br /> Lk <br /> 6 3 3992720 POTTER PAD100 PULL STATION <br /> 7 2 SLA1104 POWERPATROL 12VDC 12 AH BATTERIES <br /> BUILDING FACP POINTS LIST 8 2 BK-P2RL SYSTEM SENSOR HORN/STROBES <br /> SCALE: NONE E506 9 2 BK-SRL SYSTEM SENSOR STROBES <br /> 10 1 TG-7FS-A TELGUARD ATT CELLULAR DIALER <br /> 11 1 SSU00689 SPACEAGE FIRE ALARM STORAGE CABINET <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE ACCEPTABILITY DRAWN UAIE SUBTITLE CURRENT REVISION SYMBOL DATE N <br /> HIS DESIGN AND/OR CHECKED FIRE ALARM SYSTEM DETAILS 27851053 A 04.28.23 <br /> NEW FIRE MONITORING PANEL REPLACEMENT 27851053 CSL MDK 09.15.22 SPECIFICATION IS APPROVED SHEET <br /> BOE//VG® ENGINEER E E 506 <br /> A SHOP DRAWINGS AGOW/JS 4.28.23 APPROVED BY DEPT. DATE <br /> CHECKED LL <br /> Ar <br /> APPROVED BUILDING 45-203 DB ND GDMP ND. <br /> APPROVED ELECTRICAL MASTER EVERETT, WA DWG NO. 45-203-E506 <br />