Laserfiche WebLink
LEGEND: <br /> �J JUNCTION BOX 4S UNLESS NOTED OTHERWISE <br /> OS IONIZATION SMOKE DETECTOR <br /> HEAT DETECTOR FIXED 135° <br /> Q MANUAL STATION, DOUBLE ACTING <br /> ® STROBE ALARM <br /> ®Q AUDIBLE/VISUAL ALARM <br /> B FIRE ALARM PANEL <br /> O ADT PANEL <br /> FAC CELLULAR COMMUNICATOR <br /> GENERAL NOTES <br /> 1. CONDUIT: 1/2" MINIMUM, 3/4" MINIMUM FOR ALL <br /> HOMERUNS UNLESS NOTED OTHERWISE. 3/4" FLEX <br /> WITH GROUND WIRE. <br /> 2. CONDUCTORS SHOWN: #12 AWG, STRANDED COPPER, <br /> INSULATION TYPE THHN/THWN, UNLESS OTHERWISE <br /> NOTED. <br /> 3. COLOR CODE CONDUCTORS: IDENTIFY CONDUCTOR <br /> WHICH DO NOT HAVE APPROPRIATELY COLORED <br /> INSULATION WITH COLOR TAPE WHEREVER CONDUCTORS <br /> ARE ACCESSIBLE. IDENTIFY INSULATED GROUND <br /> CONDUCTORS IN ACCORDANCE WITH THE LATEST NEC <br /> (USING TAPE). COLOR CODE AS FOLLOWS: <br /> 208Y 120V 480Y/277 <br /> A0 (LEFT BUS IN PNL) BLACK BROWN <br /> B0 (CENTER BUS IN PNL) RED ORANGE <br /> CO (RIGHT BUS IN PNL) BLUE YELLOW <br /> NEUTRAL WHITE GRAY <br /> 45-296 SMK W 45-296 SMK E A EQUIPMENT GROUND GREEN GREEN <br /> ISOLATED GROUND GRN/YEL* GRN/YEL* <br /> ZONE 11, 1-1:11 ZONE #: 10, 1-1:10 *GREEN WITH YELLOW TRACER <br /> 4. DYMO LABEL EACH RECEPTACLE, JUNCTION/OUTLET BOX <br /> 1 TO FIRE ALARM PANEL LOCATED 1 AND SWITCH WITH CIRCUIT IDENTIFICATION. <br /> IN BLDG 45-203, 3/4"C - 4#12 <br /> 5. POST NEW OR REVISED PANEL SCHEDULES UPON <br /> COMPLETION OF JOB. <br /> 6. UPON COMPLETION OF JOB RETURN REDLINES TO <br /> ENGINEERING. <br /> 7. THE AREA CLASSIFICATION FOR THIS AREA IS CLASS I, <br /> DIVISION 2 UP TO 18" ABOVE FINISHED GRADE WITHIN <br /> 50'-0" OF AIRCRAFT. FOR THE PURPOSE OF THIS <br /> PROJECT, ALL WORK AREAS SHALL BE CONSIDERED <br /> CLASS I, DIVISION 2 UP TO 18" ABOVE FINISHED <br /> GRADE. ALL ELECTRICAL EQUIPMENT AND WIRING SHALL <br /> BE INSTALLED IN ACCORDANCE WITH NEC ARTICLE 501. <br /> FIRE ALARM PLAN,@ CONSTRUCTION NOTES <br /> SCALE: 1/8" = 1'-0" <br /> 1�ADD NEW SMOKE DETECTORS (QTY. 2) WITH <br /> ADDRESSABLE SMOKE DETECTORS COMPATIBLE <br /> WITH THE 45-203 BUILDING FACE. INSTALL <br /> A CONDUIT AND WIRE AS REQUIRED. <br /> 00, <br /> 8' 4' 0 4' 8' 16' <br /> SCALE: 1/8"=1'-0" <br /> �, <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATEDRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE <br /> ACCEPTABILITY BDH 06.10.13 FIRE ALARM PLAN 27851053 <br /> NEW FIRE ALARM PANEL REPLACEMENT 27851053 CSL MDK 08.05.22 SPTHIS DESIGN AND/OR CHECKED ECIFICATION IS APPROVED TT 06.10.13 SHEET <br /> A SHOP DRAWINGS AGOW JS 04.28.23 BOE//VG® m APPROVED BY DEPT. DATE TITLE 1 E60 <br /> BDH 06.10.13 <br /> CHECKED 4 <br /> .t.1- name° BUILDING 45-296 <br /> APPROVED JOB N0. COMP N0. <br /> „,�.uNw,„„m,,, 45-296-1 E60 � <br /> APPROVED ELECTRICAL MASTER EVERETT, WA DWG NO. 45-296-1E60 <br />