Laserfiche WebLink
FACP BATTERY CALCULATIONS <br /> COMPONENTS orv. CURRENT CURRENT REM POWER CABLE (SUPPLIED <br /> NETLINK (FACE) 1 0.15830A 0.30000A <br /> (DACT) 0.02400A 0.03700A 6 5 3 4 WITH PEM <br /> SLC DEVICES UPERVISORY ALARM <br /> CURRENT CURRENT <br /> DS-PS 2 0.00015A 0.00022A 0.00030A 0.00044A 1 <br /> DS-HFS 2 0.00015A 0.00022A 0.00030A 0.00044A <br /> DUCT 0 0.00040A 0.00044A 0.00080A 0.00088A <br /> 84-330002-001 4 0.00058A 0.00058A 0.00232A 0.00232A <br /> 70-407008-001 0 0.00024A 0.00024A 0.000OOA 0.000OOA <br /> 70-200200-001 0 0.00020A 0.00040A 0.000OOA O.000OOA <br /> 70-408004-001 0 0.00024A 0.00024A o.000OOA 000000A �3/4"C - 2#14THHN,1#14G Z B <br /> .STANDBY ALARM TG-PEM <br /> NED <br /> CURRENT CURRENT �K <br /> NAC CKT 1(AUX PWR) 0.018A 0.11000A 0.01800A 0.11000A <br /> NAC CKT 2 O.00A 0.28100A o.00000A 0.24200A FACP EVi-FA-45-239 TG-7 ES <br /> o.00A 0.0070A o.00000A o.00000A (BY FIRE ALARM VENDOR) CRN 1 1 4 7 <br /> SLC ALARM LED O.00A 0.03600A O.000OOA O.000OOA R <br /> TOTAL 0.20432A 0.69324A 3 <br /> TOTAL STANDBY CURRENT DRAW- 0.204 AMPS T <br /> X STANDBY TIME 48 HOURS <br /> STANDBY AMP HOUR TOTAL- 9.907 AH DG STC2 STGI TRIP BATT AG <br /> TOTAL ALARM CURRENT DRAW- 0.693 AMPS 1 2 1 2 3 4 5 6 1 2 3 1 2 G <br /> X ALARM TIME 0.167 HOURS BB <br /> ALARM AMP HOUR TOTAL= 0.116 AH <br /> STANDBY AH + ALARM AH = 9.923 AH RLK <br /> X DE-RATING FACTOR 1.20(201) RE0 EOL(q5 NEEDED) <br /> TOTAL Al REQUIRED= 11.91 AH <br /> MINIMUM BATTERY SIZE NEEDED: 12 AH <br /> 3/4"C (1) PHONE CABLE, <br /> BATTERY SIZE PROVIDED: 12 AH <br /> NOTE: 0.167 EQUALS 10 MINUTES OF ALARM TIME <br /> - <br /> (1) 2 CONDUCTOR FPL OR <br /> APPROVED EQUAL <br /> FACP VOLTAGE DROP CALCULATION CONSTRUCTION NOTES <br /> CIRCUIT SUPPLY ALARM OHMS NGT TOTAL LAST DEVICE VOLTAG <br /> NAME VOLTAGE CURRENT WIRE TYPE 1000 E. FEET RESISTANCE VOLTAGE DROP% � PROVIDE CELLULAR DIALER, AND MOUNT ADJACENT TO <br /> NAC1(AUX) 20.4 VDC 0.110 A #14AWG SOLID 3.07 10 0.0614 20.393 VDC 0.03% THE BUILDING FACP. CONFIGURE DIALER TO PROVIDE <br /> NAC2 20.4 VDC 0.242 A #14AWG SOLID 3.07 85 0.5219 20.27 VDC 0.62% SOLE PATH COMMUNICATION. DIALER SHALL BE <br /> N/A 20.4 VDC 0.000 A #14AWG SOLID 3.07 O 0 00.00 VDC 0% EIRE ALARM SYSTEM COMMUNICATIONS DETAIL COMPATIBLE WITH AT&T CELL SERVICE. <br /> N/A 20.4 VDC 0.000 A #14AWG SOLID 3.07 O 0 00.00 VDC 0% SCALE: NONE 7260 E506 <br /> PROVIDE (1) CONDUIT PENETRATION FOR PHONE AND <br /> FIRE ALARM CONNECTIONS. WIRE AS SHOWN. PROVIDE <br /> ADDRESSABLE MODULE AS NECESSARY TO PROVIDE <br /> STEP 1: VERIFY SIGNAL STRENGTH AT PROPOSED LOCATION FOR CELLULAR COMMUNICATOR PANEL INDICATED ON GENERAL TROUBLE ALARM FROM CELLULAR DIALER TO <br /> 4O, DRAWINGS. IF ACCEPTABLE *SIGNAL STRENGTH IS ACQUIRED, SKIP TO STEP 5. BUILDING FACP. <br /> STEP 2: IF ORIGINALLY PROPOSED LOCATION IS INADEQUATE, FIELD TEST *SIGNAL STRENGTH WITHIN A 20FT RADIUS PROVIDE (1) CONDUIT PENETRATION FOR 24/12VDC <br /> TO IDENTIFY LOCATION(S) SUITABLE FOR INSTALLATION OF REMOTE/EXTERNAL CELLULAR ANTENNA. POWER AND EARTH GROUND FROM THE BUILDING FACP <br /> COORDINATE THE FINAL ANTENNA LOCATION WITH BOEING AND SPACE USERS (IF IMPACTED) FOR POWER SUPPLY. PROVIDE POWER AND EXPANSION <br /> MONITORED BY TYCO AND APPROVAL PRIOR TO ROUGH-IN AND SKIP TO STEP 4. MODULE AND WIRE AS SHOWN. MAINTAIN <br /> F F S S <br /> k <br /> * MANUFACTURER'S REQUIRED 1/4" SEPARATION <br /> 04 1:03 L1:02 L1:01 ANALQG PHON� LINE SIGNAL SENT TO CENTRAL STEP 3: IF ACCEPTABLE SIGNAL STRENGTH IS NOT ACHIEVED WITHIN 20FT OF ORIGINAL PROPOSED LOCATION FOR BETWEEN POWER AND COMMUNICATION WIRING. <br /> (PRIMARY BOEING FIRE DEPARTMENT CELLULAR COMMUNICATOR PANEL, PROPOSE ALTERNATE LOCATION FOR CELLULAR PANEL. COORDINATE <br /> 45-239 FACEATE PATHWAYS FOR SIGNAL REQUIRED BY CODE, AS SHOWN. WITH BOEING AND SPACE USERS FOR POTENTIAL LOCATIONS, PREFERABLY NEAR ORIGINAL LOCATION. 4 PROVIDE PHENOLIC LABEL, WHITE LETTERING, RED <br /> NAC2 STEP 4: LOCATE AND PROVIDE EXTERNAL CELLULAR ANTENNA, EXTERIOR MOUNTING BRACKET AND COAXIAL CABLE BACKGROUND, THAT READS: <br /> 30CD 15CD 75CD FROM CELLULAR COMMUNICATOR TO THE ANTENNA. THE ANTENNA AND PANEL SHOULD BE LOCATED <br /> WITHIN 20FT OF EACH OTHER. "FIRE ALARM CELLULAR DIALER" <br /> S� ANALOG PHONE LINE STEP 5: PROVIDE 24VDC POWER, MONITORING CIRCUIT, AND TELEPHONE LINE TO CELLULAR COMMUNICATOR FROM <br /> 5 PROVIDE CELL ANTENNA AND EVALUATE FIELD SIGNAL <br /> QJ eJ ((SECONDARY) BUILDING FACE. <br /> P� STRENGTH IN ACCORDANCE WITH DETAIL 2. INSTALL <br /> EVF-FA-45-239 STEP 6: PROVIDE REQUIRED SET-UP, PROGRAMMING AND TESTING OF CELLULAR COMMUNICATOR EQUIPMENT PER CONDUIT AND EXTENDED ANTENNA CABLE AS <br /> THE MANUFACTURER'S INSTRUCTIONS. CELLULAR DIALER SHALL BE CONFIGURED AND INSTALLED AS A NECESSARY TO REMOTE MOUNT ANTENNA IF COVERAGE <br /> o c c c SOLE PATH FOR FIRE COMMUNICATIONS. IS NOT SUITABLE AT FACP LOCATION. UPDATE BOM <br /> WITH SELECTED CABLE LENGTH AND PROVIDE REDLINES <br /> FF L /12b" TO BOEING ENGINEER. <br /> L1:05 L107 U7 6 L1:08 <br /> *ACCEPTABLE SIGNAL STRENGTH SHALL BE DETERMINED BY MANUFACTURERS SPECIFICATIONS AND LOCAL AHJ <br /> ORDINANCES. © FOR REMOTE INSTALLATIONS PROVIDE PHENOLIC LABEL, <br /> WHITE LETTERING, RED BACKGROUND, THAT READS: <br /> BUILDING FIRE ALARM SYSTEM RISER "FIRE ALARM CELLULAR ANTENNA" <br /> SCALE: NONE E506 <br /> CELLULAR COMMUNICATOR INSTALLATION SEQUENCE INSIDE CELL ENCLOSURE POST COMMUNICATOR <br /> SETTINGS AND CELLUAR PHONE NUMBER. PROVIDE <br /> SCALE: NONE E260 E506 PRINTED LABEL, HANDWRITTEN INFORMATION IS NOT <br /> ACCEPTABLE. PROVIDE SETTINGS AND CELLULAR <br /> INFORMATION TO BOEING ENGINEER. <br /> 45-239 BUILDING SYSTEM FACP POINTS <br /> POINT NUMBER/ZONE BOEING DESCRIPTION FACP POINT - COMMENTS - GRID/SHEET LOC. <br /> L1:001 122 SMK OFFICE N FACP SMOKE DETECTOR - B3/E260 BILL OF MATERIALS <br /> L1:002 123 SMK OFFICE S OFFICE WEST SMOKE DETECTOR - 33/260 ITEM QTY. PART NO. MANUFACTURER DESCRIPTION <br /> u:oo3 124 MAN PULL DR S1 OFFICE CENTER SMOKE DETECTOR - A2/260 1 1 76-800100-001 KIDDE ARIES FIRE ALARM CONTROL PANEL <br /> _1:004 125 MAN PULL DR S2 OFFICE EAST SMOKE DETECTOR - Ai/260 2 1 76-800015-001 KIDDE ARIES DACT CARD <br /> L1:005 126 45-745 HEAT REST. W. IWOMENS R.R. HEAT DETECTOR - A4/260 3 4 DS-SB KIDDE DETECTOR BASE <br /> _1:006 127 45-745 HEAT REST. E. IMENS R.R. HEAT DETECTOR - A4/260 4 2 DS-PS KIDDE PHOTO DETECTOR <br /> L1:007 128 45-745 MAN PULL DR. W. INORTH EXIST MANUAL PULL - A4/260 5 2 DS-HFS KIDDE HEAT DETECTOR(135° FIXED) <br /> �ki u:ooa 129 45-745 MAN PULL DR. E. S.W. EXIST MANUAL PULL - A4/E260 6 4 84-330002-001 KIDDE DOUBLE ACTION PULL STATION <br /> BUILDING FACP POINTS LIST7 2 SLA1106 POWERPATROL 12VDC 12 AH BATTERIES <br /> 8 1 BK-P2RL SYSTEM SENSOR HORN/STROBES <br /> SCALE: NONE E106 9 2 BK-SRL SYSTEM SENSOR STROBES <br /> si'o'J 10 1 TG-7FS-A TELGUARD ATT CELLULAR DIALER <br /> 11 1 1 SSU00689 ISPACEAGE FIRE ALARM DOCUMENT CABINET <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE ACCEPTABILITY DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE <br /> NEW FIRE MONITORING PANEL REPLACEMENT 27851053 CSL MDK 09.15.22 <br /> HIS DESIGN AND/OR CHECKED FIRE ALARM SYSTEM DETAILS 27851053 <br /> SPECIFICATION IS APPROVED SHEET <br /> A SHOP DRAWINGS AGOW/JS 04.28.23 BOEzw" APPROVED er DEPT. DATE TITLE E506 <br /> CHECKED <br /> ete Linamen APPROVED BUILDING 45-239 JOB N0. COMP NO. _ <br /> xmsr�.re,vu�x::-., 3 <br /> APPROVED ELECTRICAL MASTER EVERETT, WA DWG NO. 45-239-E506 <br />