Laserfiche WebLink
Post Indicator Valve fli ft <br />PASS FAIL N/A <br />23. Accessible -Both Remote Post Indicator Valves and Wall Post Indicator Valves ❑ ❑ <br />shall be easily accessible, and the Open/Closed indicator shall be visible at all <br />times. <br />24. <br />Cutable Lock - The PIV shall be provided with a cutable padlock. <br />❑ <br />❑ <br />25. <br />Clear Space- A clear working space not less than 36 inches in width, 36 Inches in <br />❑ <br />❑ <br />depth and 28 inches in height shall be provided. <br />System In Full Operation; <br />PASS <br />FAIL N/A <br />26. <br />Systems Normal- Ensure all systems are normal <br />❑ <br />❑ ❑ <br />22. <br />Alarm Off Test- Ensure the Fire Alarm is off of test with the monitoring company. <br />❑ <br />❑ ❑ <br />28. <br />NFPA 13 Report- The installer shall complete and sign the NFPA 13 Contractor's <br />❑ <br />❑ ❑ <br />Material and Test Certificate for Aboveground Piping prior to final approval of the <br />system. Ilf the building is also equipped with a standpipe system the installer shall <br />also complete and sign the NFPA 14 Contractor's Material and Test Certificate for <br />Aboveground Piping prior to final approval of the system.) <br />29. Keys for Knox Box -Keys for the Fire Sprinkler Room and Pill shall be provided ❑ ❑ ❑ <br />so they may be placed into the Knox Box. <br />Fire Marshal's Office 142525761 DO I everettwa.govlfire I INFORMATION HANDOUT C-6 14.13.2020 1 Page 11 <br />