Laserfiche WebLink
POINT NUMBER/ZONE BOEING DESCRIPTION FACP POINT- COMMENTS - GRID/SHEET LOC. <br /> 1:03:11 SV24-1 WF PRESSURE WATERFLOW PRESSURE SWITCH WITH DELAY K/1.5 - lE270 FIRE ALARM ABBREVIATIONS LEGEND <br /> 1:03:12 SV24-1 WF ISO TAMPER WATERFLOW ISOLATION TAMPER SWITCH K/1.5 - lE270 ALT SECONDARY OR ALTERNATE ELEVATOR RECALL <br /> 1:16:11 SV24-1 TAMPER OS&Y SPRINKLER VALVE L/1.5 TUNNEL - 40-025-TNE260 BEAM DET BEAM DEFECTOR SEE SHEET EOA FOR SYMBOLS AND ABBREVIATIONS. <br /> 1:03:13 SV24-3 WF PRESSURE WATERFLOW PRESSURE SWITCH WITH DELAY K/1.7 - lE270 CDR COMPUTER/NETWORK/DATA/IDF ROOM <br /> 1:03:14 SV24-3 WF ISO TAMPER WATERFLOW ISOLATION TAMPER SWITCH K/1.7 - lE270 COL COLUMN <br /> 1:16:12 SV24-3 TAMPER OS&Y SPRINKLER VALVE L/1.5 TUNNEL - 40-025-TNE260 COMM FAIL COMMUNICATION FAILURE <br /> 1:04:11 SV24-5 WF PRESSURE WATERFLOW PRESSURE SWITCH WITH DELAY K/2.7 - 1E270 CTRL CONTROLCW CATWALK <br /> 1:04:12 SV24-5 WF ISO TAMPER WATERFLOW ISOLATION TAMPER SWITCH K/2.7 - 1E270 DMPR DAMPER <br /> 1:17:11 SV24-5 TAMPER OS&Y SPRINKLER VALVE L/2.7 TUNNEL - 40-025-TNE260 DO DUCT SMOKE DETECTOR <br /> 1:05:11 SV24-7 WF PRESSURE WATERFLOW PRESSURE SWITCH WITH DELAY K/4.8 - 1E271 DIESEL DIESEL <br /> FP FIRE PUMP <br /> 1:05:12 SV24-7 WF ISO TAMPER WATERFLOW ISOLATION TAMPER SWITCH K/4.8 - 1E271 ELEC ELECTRICAL; ELECTRICAL ROOM <br /> 1:17:12 SV24-7 TAMPER OS&Y SPRINKLER VALVE L/3.8 TUNNEL - 40-025-TNE261 ELEVELEVATOR <br /> 1:05:13 SV24-9 WF PRESSURE WATERFLOW PRESSURE SWITCH WITH DELAY K/4.8 - 1E271 EPP EXCESS PRESSURE PUMP <br /> 1:05:14 SV24-9 WF ISO TAMPER WATERFLOW ISOLATION TAMPER SWITCH K/4.8 - 1E271 FACP FIRE ALARM CONTROL PANEL <br /> 1:17:13 SV24-9 TAMPER OS&Y SPRINKLER VALVE L/3.8 TUNNEL - 40-025-TNE261 ELEV FF HAT LIGHT FIRE FIGHTER HAT LIGHT IN A ELEVATORFLR FLOOR <br /> 1:06:11 SV24-11 WF PRESSURE WATERFLOW PRESSURE SWITCH WITH DELAY K/6.6 - 1E272 FM FIRE MAIN VALVE <br /> 1:06:12 SV24-11 WF ISO TAMPER WATERFLOW ISOLATION TAMPER SWITCH K/6.6 - 1E272 HEAT HEAT DETECTOR GENERAL NOTES <br /> 1:18:11 SV24-11 TAMPER OS&Y SPRINKLER VALVE L/6.6 TUNNEL - 40-025-TNE262 INTDEV INTERFACE DEVICE, MONITORING OR CONTROL <br /> 1:06:13 SV24-13 WF PRESSURE WATERFLOW PRESSURE SWITCH WITH DELAY K/6.6 - 1E272 ISO ISOLATION VALVEKITCHEN KITCHEN <br /> 1:06:14 SV24-13 WF ISO TAMPER WATERFLOW ISOLATION TAMPER SWITCH K/6.6 - 1E272 L BATT LOW BATTERY <br /> 1:18:12 SV24-13 TAMPER OS&Y SPRINKLER VALVE L/6.6 TUNNEL - 40-025-TNE262 L FUEL LOW FUEL (FIRE PUMP DIESEL TANK IS BELOW 50% FILLED) <br /> 1:07:11 SV24-15 WF PRESSURE WATERFLOW PRESSURE SWITCH WITH DELAY K/8 - 1E273 LBY LOBBY <br /> LRD LOW RATE DISCHARGE <br /> 1:07:12 SV24-15 WF ISO TAMPER WATERFLOW ISOLATION TAMPER SWITCH K/8 - 1E273 MAN PULL MANUAL PULL STATION <br /> 1:19:11 SV24-15 TAMPER OS&Y SPRINKLER VALVE L/8 TUNNEL - 40-025-TNE263 MECH MECHANICAL ROOM <br /> 1:07:13 SV24-17 WF PRESSURE WATERFLOW PRESSURE SWITCH WITH DELAY K/8 - 1 E273 NAC NOTIFICATION APPLIANCE CIRCUIT OR POWER SUPPLY <br /> 1:07:14 SV24-17 WF ISO TAMPER WATERFLOW ISOLATION TAMPER SWITCH K/8 - 1E273 OS&Y OUTSIDE SCREW AND YOKE VAVLE <br /> PD PUMP DISCHARGE VALVE <br /> 1:19:12 SV24-17 TAMPER OS&Y SPRINKLER VALVE L 8 TUNNEL - 40-025-TNE263 PH PENTHOUSE <br /> 1:08:11 SV24-19 WF PRESSURE WATERFLOW PRESSURE SWITCH WITH DELAY K/9 - 1E273 PIV POST INDICATOR VALVE <br /> 1:08:12 SV24-19 WF ISO TAMPER WATERFLOW ISOLATION TAMPER SWITCH K/9 - 1E273 POWER FAIL FACP POWER FAILURE <br /> 1:20:11 SV24-19 TAMPER OS&Y SPRINKLER VALVE L/9.6 TUNNEL - 40-025-TNE264 PRPRI PRIMARY N PRSYSTEM <br /> MARY <br /> 1:09:11 SV24-21 WF PRESSURE WATERFLOW PRESSURE SWITCH WITH DELAY K/10.5 - 1E274 PS PUMP SUPPLY VALVE <br /> 1:09:12 SV24-21 WF ISO TAMPER WATERFLOW ISOLATION TAMPER SWITCH K/10.5 - 1E274 PWR POWER REFERENCE DRAWINGS <br /> 1:20:12 SV24-21 TAMPER OS&Y SPRINKLER VALVE L/10.5 TUNNEL - 40-025-TNE264 RF ROOF <br /> RLY RELAY <br /> 1:10:11 SV24-23 WF PRESSURE WATERFLOW PRESSURE SWITCH WITH DELAY K/11 - 1E274 SEC SECTION VALVE <br /> 1:10:12 SV24-23 WF ISO TAMPER WATERFLOW ISOLATION TAMPER SWITCH K/11 - 1E274 SHUNT SHUNT TRIP <br /> 1:21:11 SV24-23 TAMPER OS&Y SPRINKLER VALVE L/10.9 TUNNEL - 40-025-TNE264 SMK SMOKE DETECTOR <br /> 1:01 SMK P FACP J.5/8.7 - 1E273 STL STALL <br /> STROBE STROBE, HORN OR ANY NOTIFICATION DEVICE <br /> 1:02 MAN PULL ® FACP J.5/8.7 - 1 E273 SUPPR SUPPRESSION <br /> 1:11:11 ELEV 11 FA J.2/10 - 1E274 SUPV SUPERVISORY <br /> 1:11:12 ELEV 11 TRBL J-2/10 - 1E274 <br /> SV SPRINKLER VALVE <br /> TAMPER TAMPER SWITCH <br /> 1:11:13 ELEV 11 SUPV J.2/10 - 1E274 TL300 TL300 TYCO COMMUNICATION DEVICE <br /> 1:12:11 ELEV 20 FA J.5/8.8 - lE270 TRBL TROUBLE <br /> 1:12:12 ELEV 20 TRBL J.5/8.8 - 1E270 UV UNIT VALVE <br /> 1:12:13 ELEV 20 SUPV J.5/8.8 - 1E270 VLV VALVE <br /> WF WATERFLOW SWITCH <br /> 1:13:11 ELEV 21 FA J.5/7.7 - 1E273 ZN ZONE <br /> 1:13:12 ELEV 21 TRBL J.5/7.7 - 1E273 <br /> 1:13:13 ELEV 21 SUPV J.5/7.7 - 1E273 <br /> 1:14:11 CDR RM 302K8 PNL FA J.2/8.6 - 3E273 <br /> 1:14:12 CDR RM 302K8 PNL TRBL J-2/8.6 - 3E273 <br /> 1:15:11 40-24 MAIN VESDA FA 40-24 MAIN VESDA PANEL J/1.2 - 1E270 CONSTRUCTION NOTES <br /> 1:15:12 40-24 MAIN VESDA TRBL 40-24 MAIN VESDA PANEL J/1.2 - 1E270 <br /> POINT NUMBER NOMENCLATURE <br /> 1 : 01 : 11 <br /> MONITORING INPUT NUMBER: <br /> 11 - INPUT 1 <br /> 12 - INPUT 2 <br /> 13 - INPUT 3 <br /> 14 - INPUT 4 <br /> ADDRESSABLE DEVICE NUMBER <br /> SIGNALING LINE CIRCUIT NUMBER <br /> 40-24 BUILDING FACP POINTS LIST 41 -75) / Po BOX <br /> 1138 <br /> SCALE: NONE E506SEATRONICS X253-"'Bas--6D600" <br /> SYM <br /> FIRE PROTECTION SUVICES,pB N).11065 ONG N0.11106-E506 <br /> 1 <br /> REVISION BY APPROVED DATE SYM REVISION BY APPROVm DATE ACCEPTABILITY DRAWN SUBTITLE CURRENT REVISION SYMBOL DATE <br /> S <br /> - EVEREIT FIRE PANEL REPLACEMENT SEA 5.13.19 THIS DESIGN AND/OR RG D s.t3.ts FIRE ALARM SYSTEM DETAILS 111065-0 - 5.13.19 <br /> c SPECIFICATION IAPPROVED SHEE <br /> BDE���® APPROVED BY DEPT. DATE LNQINUR N TREE EVERETT FIRE PANEL REPLACEMENT E506 <br /> AP BUILDING 40-024 JOB NO. 111065 COMP N0. <br /> APPR VED ELECTRICAL MASTER EVERETT, WA. ow0 NO. 40_024-E506 <br />