l <br /> Mr. Drew Martin <br /> 2713 Maple Street, LLC <br /> Plan Check Number: B2101-051, Second Building Review <br /> March 7th, 2022 <br /> Sheet A4 has been adjusted to show correct reference to Floor Type 'F2'. A detail has been <br /> added to Sheet A6 Details to show egress door threshold requirements, see Detail 9 / Sheet <br /> A6. <br /> ee The Main Floor Plan 1/A2 appears to show heat pump units under the egress windows on the <br /> exterior of the building. The heat pumps may prevent proper emergency egress and rescue <br /> activity, and should be relocated. The heat pump locations should also be shown in the Site <br /> Plan and elevations on Sheets Al and A3, respectively. See Sections R106.1.1 and R310. <br /> The heat pump location has been adjusted on Sheet A2 Floor Plans and added to Sheet A3 / <br /> Elevations and Al Site Plan. <br /> S Detail 1/A6 specifies a guard opening size of 4.375 inches. The guard should not allow passage <br /> of a 4-inch sphere, as indicated in the"Building Code Summary" on Sheet A0.0. In addition, <br /> the reference to"SRC"standards should be removed. See Section R312.1.3. <br /> The guard opening note has been updated on Sheet A6 Details, Detail 1. The reference to external <br /> codes has been removed. <br /> 19� Lx 6/dt4 <br /> ( . Sheet A6 provides an Energy Code Summary. The following comments should be addressed: <br /> a. The energy credit section includes a fuel normalization credit per the 2018 edition of the <br /> WSEC. If the project is intended to comply with this edition, the required number of energy <br /> credits is 6.0 per WSEC-18 Section R406.3. Note that the selected credits comply with the <br /> 2015 edition and require revision to the 2018 edition. Alternatively, the design should <br /> comply with the WSEC-15 provisions; the fuel normalization credit does not apply to this <br /> edition, and an additional 1.0 credit is required. See also General Comment 1. <br /> b. The selected credits include improved thermal performance values, including but not limited <br /> to UMAx=0.28 for vertical fenestrations. The typical values listed should be revised for <br /> consistency. <br /> c. The summary should specify UMAx=0.50 for skylights. <br /> d. The construction drawings and summary specify continuous R-10 under-slab insulation. <br /> This is not substantiated by the"Typical Wall Section" in "Sheet 4/6"on Sheet A1.2. The <br /> design should be revised. <br /> e. The construction drawings and summary specify R-49 roof insulation. This requires a <br /> minimum framing depth of 15.5 inches per WSEC Table A101.4. An additional minimum <br /> one inch is required for the venting baffles per Section C/A4. Note that the depth of the <br /> existing roof framing should be specified. <br /> f. The selected credits include efficient HVAC and water heating systems. The minimum <br /> performance requirements for these systems per WSEC Table 406.2 should be specified. <br /> The Energy Code Summary on Sheet A6 Details has been updated to show the 2015 Edition, credits <br /> have been updated accordingly. The Summary shows vertical fenestrations U-Factor and proposed <br /> skylights. <br /> IThe Floor Assembly'F2'on Sheet A4 Sections has been updated to show the existing R-10 under- <br /> slab perimeter and proposed R-10 rigid insul. with sleeper system. <br /> Page 4 of 8 9 <br />