Laserfiche WebLink
Mr. Drew Martin <br /> 2713 Maple Street, LLC <br /> Plan Check Number: B2101-051, Second Building Review <br /> March 7th, 2022 <br /> The proposed party wall has been revised along drawings to show a simpler construction. See <br /> assembly 'W3' on Sheet A4 Sections. <br /> Section C/A4 shows the exterior wall on the east side of the building. The wall has a FSD=0 <br /> and is required to be a minimum one-hour rated wall per Table R302.1(1). The wall should be <br /> continuous from the foundation to the roof sheathing. Alternatively, solid blocking matching the <br /> out-to-out surfaces of the GWB may be provided at both the floor and roof framing. The rated <br /> construction should also be provided for the parapet extending above the roof. <br /> Section C/A4 north wall references the proposed 1-hour fire rated wall / assembly W4/ Sheet <br /> A4, detail WP 8136. <br /> 5/ The floor plans on Sheet A2 show exhaust fans located adjacent to or near the east fire-rated <br /> / exterior wall, including but not limited to the range exhaust fans. Openings into or through this <br /> wall are not allowed for air ducts for FSD<3 feet, including interior member penetrations into <br /> the wall cavity space. All ducts must be located outside the wall assembly. The proposed duct <br /> routes should be shown in the plans. Details should be provided where ducts will be located in <br /> chases; the chases should be shown in the plans. See Section R106.1.1 and Table R302.1(1). <br /> A note has been added to the proposed wall assembly W4/ Sheet A4 for penetrations not allowed. <br /> Proposed duct routes have been added to the Floor Plans and proposed duct chase in second level, <br /> bath area. <br /> Smoke and CO alarms should be provided per IRC Sections R314 and R315. The locations of all <br /> alarms should be shown on the plans. A note should be included requiring the alarms to be <br /> hardwired, interconnected, and provided with back-up battery power as required. Alarm <br /> clearances should comply with Section R314.3 Item 4 and Section R314.3.1. <br /> Smoke and CO alarms have been located on the plans; a note has been added to Sheet A2 Floor <br /> Plans for alarms. See note #19 Sheet A2. <br /> Section A/A4 shows a 6'-8"clearance for the stairs dimensioned to the tread surface. The <br /> clearance should be dimensioned to a line connecting the stair nosings. The clearance <br /> dimension should be revised. The floor framing above may need to be revised. See Section <br /> R311.7.2. <br /> The height clearance has been adjusted and reference to 6'-8" min height relocated to stair <br /> nosing. Second Level closet has been relocated to allow for the min. height clearance. <br /> /7. Sections C/A4 and D/A4 specify a sleeper floor system at the Main Level per Floor Type"F3". <br /> The following comments should be addressed: <br /> a. Sheet A4 does not include this floor type. It appears the Type"F2" may be intended. The <br /> design should be revised as needed. See Section R106.1.1. <br /> b. The floor will be raised above the exterior grade. The egress door and landing are required <br /> to comply with Section R311.3.1. A section through the egress door threshold should be <br /> included in the drawings. <br /> ( Page 3 of 8 <br />