SEQUENCE OF OPERATIONS: <br />EXISTING ALLERTON BACTALK DOC SYSTEM SHALL BE CONNECTED TO NEW BOILERS, BOILER PUMPS AND CIRCULATION PUMPS WITH FULL SYSTEM PEER TO PEER <br />BACNET INTEROPERABIDTY, DDC SYSTEM REVISIONS SHALL BE INSTALLED. BY ATS. CONTACT DAN ALBERT. <br />EXISTING ALLERTON IBEX SYSTEM CONTROLS THE TERMINAL UNITS. THREE WAY VALVES IN TERMINAL UNITS SHALL BE REPLACED WITH NEW 2-WAY VALVES; <br />PROVIDED BY ATE, INSTALLED BY MC. <br />MAIN CIRCULATION PUMPS P-1 AND P-2 PUMPS P-1 AND P-2 ARE REDUNDANT AND ARE MODULATED BY VFD'S. PUMPS P-1 AND P-2 SHALL BE STAGED AS <br />LEAD/STANDBY. THE LEAD PUMP DESIGNATION SHALL BE ROTATED WEEKLY BY THE DDC. <br />ON A CALL FOR HEAT, LEAD MAIN CIRCULATION PUMP (P-1 OR P-2) SHALL BE ENERGIZED. LEAD PUMP VFD SHALL MODULATE PUMP SPEED TO MAINTAIN A <br />DISCHARGE PRESSURE OF 13 PSI (ADJUSTABLE). <br />MAIN CIRCULATION PUMP FLOWS SHALL BE MONITORED BY DIFFERENTIAL PRESSURE ACROSS EACH PUMP. IF DIFFERENTIAL PRESSURE INDICATES LOSS OF FLOW, THE <br />LEAD PUMP SHALL BE DE -ENERGIZED AND THE STANDBY PUMP SHALL BE ENERGIZED AND DDC SHALL BE ALARMED. <br />UPON FAILURE OF THE LEAD PUMP VFD, THE LEAD PUMP SHALL BE DE -ENERGIZED AND THE STANDBY PUMP SHALL BE ENERGIZED. UPON FAILURE OF THE <br />STANDBY PUMP VFD, THE DDC SYSTEM SHALL SIGNAL SELECTED STANDBY PUMP TO OPERATE IN BYPASS MODE AND THE DDC SYSTEM SHALL SET AN ALARM <br />BOILERS B-1 AND B-2: <br />BOILERS ARE REDUNDANT AND STAGED AS LEAD/STANDBY. THE LEAD BOILER DESIGNATION SHALL BE ROTATED WEEKLY. (ADJUSTABLE) <br />ON A CALL FOR HEAT, LEAD BOILER AND DESIGNATED BOILER PUMP SHALL BE ENERGIZED. LEAD BOILER SHALL OPERATE AT FULL FIRING RATE UNTIL HEATING <br />LOOP TEMPERATURE MATCHES BOILER RESET SCHEDULE TEMPERATURE. IF LEAD BOILER CANNOT MEET BOILER RESET SCHEDULE, LEAD BOILER SHALL BE <br />DE -ENERGIZED AND STANDBY BOILER SHALL BE ENERGIZED. SELECTED BOILER SHALL MODULATE FIRING RATE AND FLOW RATE TO MAINTAIN RESET SCHEDULE <br />(ADJUSTABLE) <br />RESET SCHEDULE SHALL BE BASED ON OUTSIDE AIR TEMPERATURE: AT 60 DEGREES OAT (ADJUSTABLE) SUPPLY WATER TEMPERATURE SHALL BE 120 DEGREES <br />(ADJUSTABLE). BELOW 60 DEGREES OAT, THE SUPPLY WATER TEMPERATURE SHALL INCREASE WTH TEMPERATURE DECREASE. AT 40 DEGREES OAT (ADJUSTABLE), <br />THE SUPPLY WATER TEMPERATURE SHALL BE THE MAXIMUM TEMPERATURE OF 180 DEGREES (ADJUSTABLE). <br />SHUTDOWN: BOTH BOILERS SHALL AUTOMATICALLY SHUT OFF WHEN EITHER EMERGENCY POWER OFF (EPO) IS PRESSED OR THE CO DETECTOR IS IN ALARM. THE <br />DDC SHALL MONITOR AUXILIARY CONTACTS FOR PROVIDING STATUS. EPO SHALL BE WIRED DIRECTLY TO BOILER CONTROL PANEL, WITH MONITORING BY DDC. <br />BOILER PUMPS BP-1 AND BP-2: <br />BOILER PUMPS ARE EQUIPPED WITH INTEGRAL SPEED CONTROLS. EACH BOILER PUMP SHALL BE MODULATED BY ITS ASSOCIATED BOILER'S INTEGRAL CONTROLS, TO <br />MODULATE BASED ON BOILER FIRING RATE. BOILER PUMP FAILURE SHALL BE MONITORED AND ALARMED BY ASSOCIATED BOILER ON -BOARD CONTROL. EVERETT <br />PUBUC SCHOOLS OPERATIONS SHALL DETERMINE THE DATE THAT THE BOILER SYSTEM IS STARTED AND STOPPED FOR THE SEASON. <br />EXISTING SUMP PUMP: <br />EXISTING SUMP PUMP LOCATED IN THE SOUTH WEST CORNER OF THE BOILER ROOM SHALL BE MONITORED BY THE DDC SYSTEM. WHEN SUMP PUMP IS STARTED BY <br />EXISTING CONTROL PANEL, DDC SHALL BE SIGNALED THAT THE PUMP IS OPERATING, <br />PUMP RUN HISTORY SHALL BE LOGGED BY THE DEC SYSTEM. <br />IF A HIGH WATER ALARM IS INITIATED BY THE EXISTING PUMP CONTROL PANEL, THE DDC SYSTEM SHALL SET AN ALARM. END OF SEQUENCE OF OPERATIONS <br />EXISTING HYDRONIC EQUIPMENT <br />SCHEDULE <br />AIR <br />HEATING <br />HOT WATER COIL DATA <br />MARK <br />SUPPLY FAN <br />GEM <br />OUTSIDE AIR <br />MIN. GEM <br />HEATING <br />OUTPUT <br />(MEN) <br />GPM <br />DESIGN WATER <br />TEMP. DELTA <br />REMARKS <br />ECU-1 <br />1,375 <br />550 <br />60.5 <br />6.10 <br />20 <br />1 <br />BCU-2 <br />1375 <br />550 <br />60.5 <br />6.10 <br />20 <br />1 <br />BCU-3 <br />1100 <br />440 <br />48.4 <br />4,80 <br />20 <br />2 <br />BCU-4 <br />600 <br />240 <br />26.4 <br />2.60 <br />20 <br />1 <br />BCU-5 <br />500 <br />200 <br />22.0 <br />2.20 <br />20 <br />1 <br />UV-1 <br />750 <br />250 <br />33.0 <br />3.30 <br />20 <br />1 <br />UV-2 <br />1000 <br />250 <br />55.0 <br />5.50 <br />20 <br />1 <br />UV -3 <br />1000 <br />250 <br />55.0 <br />5.50 <br />20 <br />1 <br />UV-4 <br />1000 <br />250 <br />55.0 <br />5.50 <br />20 <br />1 <br />UV-5 <br />1000 <br />250 <br />55.0 <br />5.50 <br />20 <br />1 <br />UV-6 <br />1000 <br />250 <br />55.0 <br />5.50 <br />20 <br />1 <br />UV-7 <br />1250 <br />250 <br />65.0 <br />6.50 <br />20 <br />1 <br />UV-8 <br />1250 <br />250 <br />65.0 <br />6.50 <br />20 <br />1 <br />UH-1 <br />200 <br />N/A <br />5.0 <br />1 0.50 <br />20 <br />3 <br />UH-2 <br />200 <br />N/A <br />5.0 <br />0.50 <br />20 <br />4 <br />HVU-2 <br />1600 <br />250 <br />95.5 <br />9.50 <br />20 <br />1 <br />HVU-3 <br />1500 <br />250 <br />90.0 <br />9.00 <br />20 <br />1 <br />HVU-4 <br />1500 <br />250 <br />90.0 <br />9.00 <br />20 <br />1 <br />HVU-5 <br />1800 <br />250 <br />107.5 <br />10.75 <br />20 <br />1 <br />HVU-6 <br />1500 <br />250 <br />80.0 <br />8.00 <br />20 <br />1 <br />HVU-7 <br />1500 <br />250 <br />80.0 <br />8.00 <br />20 <br />4 <br />HVU-8 <br />1500 <br />250 <br />80.0 <br />8.00 <br />20 <br />1 <br />HVU-9 <br />2000 <br />250 <br />119.0 <br />11.90 <br />20 <br />2 <br />RAD-1 <br />N/A <br />N/A <br />14.5 <br />1.50 <br />20 <br />5 <br />RAD-2 <br />N/A <br />N/A <br />3.9 <br />0.40 <br />20 <br />5 <br />RAD-3 <br />N/A <br />N/A <br />1 6.6 <br />0.70 <br />20 <br />5 <br />RAD-4 <br />N/A <br />N/A <br />6.6 <br />0.70 <br />20 <br />5 <br />RAD-5 <br />N/A <br />N/A <br />6.6 <br />0.70 <br />20 <br />5 <br />RAD-6 <br />N/A <br />N/A <br />14.4 <br />1.40 <br />20 <br />5 <br />RAD-7 <br />N/A <br />N/A <br />7.0 <br />0.70 <br />20 <br />5 <br />RAD-8 <br />N/A <br />N/A <br />6.6 <br />0.70 <br />2 <br />1 5 <br />RAD-9 <br />N/A <br />N/A <br />6.6 <br />0.70 <br />20 <br />5 <br />BAD 10 <br />N/A <br />N/A <br />7.0 <br />0.70 <br />20 <br />5 <br />REMARKS: <br />1. REPLACE EXISTING THREE WAY VALVE WITH NEW TWO- WAY VALVE. <br />2. REPLACE EXISTING THREE WAY VALVE WITH NEW THREE- WAY VALVE <br />3. INSTALL NEW THREE WAY TWO POSSITION VALVE TO EXISTING WILD COIL <br />4. INSTALL NEW TWO WAY TWO POSSITION VALVE ON EXISTING WILD COIL <br />5. REPLACE EXISTING TWO WAY VALVE WITH NEW TWO WAY VALVE. <br />MISCELLANEOUS MECHANICAL <br />EQUIPMENT SCHEDULE <br />MARK <br />DESCRIPTION <br />SERVES <br />BASIS OF DESIGN <br />NOTES <br />AS-1 <br />AIR SEPARATOR <br />PRIMARY CIRC LOOP <br />B&G CRS-3F <br />1 <br />SF-i <br />SHOT FEEDER <br />PRIMARY CIRC LOOP <br />5 GAL <br />2 <br />MF-1 <br />BOILER MAGNETIC FILTER <br />PRIMARY CIRC LOOP <br />XT-3 <br />3 <br />RPBFP <br />REDUCED PRESSURE BACKFLOW PREVENTOR <br />SYSTEM MAKE-UP <br />WATTS 009-1" <br />4 <br />NOTES: <br />1. COALESCING <br />2. GTP - DB5. <br />3. BOILER MAG <br />4. PROVIDE 1/4 <br />AIR SEPARATOR WITH STRAINER AND BLOW DOWN. PROVIDE WITH HIGH CAPACITY AIR VENT. <br />XT BY ECLIPSE MAGNETICS. <br />TURN BALL VALVES ON INLET AND OUTLET. <br />MOTOR/INVERTOR SCHEDULE <br />MARK <br />SERVES <br />LOCATION <br />H.P. <br />VOLTS <br />PHASE <br />BASE OF DESIGN <br />NOTES <br />VFD-1 <br />PUMP P-1 <br />BOILER ROOM <br />5 <br />208 <br />3 <br />ABB <br />1 <br />VFD-2 <br />PUMP P-2 <br />BOILER ROOM <br />5 <br />208 <br />3 <br />ABB <br />1 <br />NOTES: <br />1. PROVIDE WITH <br />ELECTRONIC BYPASS. <br />MODEL ACH580-VDR-024A-2 <br />PUMP SCHEDULE <br />MARK <br />SERVES <br />PUMP TYPE <br />GPM <br />PUMP HEAD (FT ING) <br />MIN <br />EFF (7) <br />MOTOR DATA <br />SUCTION DIFF <br />(Y/N) <br />TRIPLE DUTY VALVE <br />SIZE(IN) <br />BASIS OF DESIGN <br />NOTES <br />HP <br />V/PH <br />FLA <br />RPM <br />P-1 <br />MAIN CIRC LOOP <br />END SUCT <br />125 <br />60 <br />50 <br />5.0 <br />208/3 <br />16.7 <br />1800 <br />YES <br />3" <br />B&G E-1510-2BD <br />1,2,3 <br />P-2 <br />MAIN CIRC LOOP <br />END SHOT <br />125 <br />60 <br />50 <br />5.0 <br />208/3 <br />16.7 <br />1800 <br />YES <br />3" <br />B&G E-1510-2BD <br />1,2,3 <br />BP-1 <br />BOILER PUMP <br />IN -LINE <br />96 <br />10 <br />55 <br />1 <br />208/1 <br />3.5 <br />VAR <br />NO <br />NO <br />B&G ECOCIRC XL-40-200 <br />4 <br />BP-2 <br />BOILER PUMP <br />IN -LINE <br />96 <br />10 <br />55 <br />1 <br />208/1 <br />3.5 <br />VAR <br />NO <br />NO <br />B&G ECOCIRC XL-40-200 <br />4 <br />NOTES: <br />1. INSTALL PUMP ON INERTIAL BASE. MASON BMK-6"-18"x42". PROVIDE WITH LBMC-6-B <br />2. CONNECT PUMP TO VFD. SEE INVERTER SCHEDULE. <br />3. PUMPS P-1 AND P-2 ARE REDUNDANT, AND SHALL OPERATED AS LEAD/STANDBY. <br />4. CONNECT TO INLET OF NEW BOILER IN BOILER ROOM. <br />CORNER BRACKETS AND (4) C-A-310 HOUSED SPRING <br />MOUNTS, 1" DEFLECTION <br />HOT WATER BOILER SCHEDULE <br />BOILER INPUT <br />WATER <br />FIRING RATE <br />PRESSURE <br />VENT CONN. <br />ELECTRICAL DATA <br />BASIS OF DESIGN <br />MARK <br />RATING <br />(MEN) <br />OUTPUT (MBH) <br />GPM (20'DIF) <br />L.W.T. DEG.F <br />GAS (CFH) <br />INLET PRESSURE <br />(PSIG) <br />DIA. INCHES <br />MCA <br />V. <br />PH. <br />MANUFACTURER/MODEL# <br />3-1 <br />1,250 <br />1,203 <br />120 <br />180 <br />1250 <br />12" WC <br />160 <br />8" <br />9.0 <br />120 <br />1 <br />LOCHINVAR CREST FBN-1251 <br />B-2 <br />1,250 <br />1,203 <br />120 <br />180 <br />1250 <br />12" WC <br />160 <br />8" <br />9.0 <br />120 <br />1 <br />LOCHINVAR CREST FBN-1251 <br />NOTES: <br />1. 10" DIRECT VENT COMBUSTION AIR. <br />2. 75 PSI RELIEF VALVE, 2". <br />3. BOILER VOLUME 157 GALLONS. <br />4. BOLT BOILERS TO EXISTING CONCRETE PAD. <br />5. PROVIDE WITH ALARM, EMS GATEWAY AND CONDENSATE NEUTRALIZER KIT. <br />EXISTING BLADDER COMPRESSION <br />TANK SCHEDULE <br />MARK <br />SYSTEM SERVED <br />SYSTEM VOLUME <br />(GAL.) <br />TEMP. RANGE <br />(DEG.F.) <br />PRESS. RANGE (PSIG) <br />BLADDER PRESS. <br />(PSIG) <br />TANK VOLUME <br />(GAL.) <br />ACCEPTANCE <br />VOLUME (GAL.) <br />BASIS. OF DESIGN <br />NOTES <br />MAX. <br />MIN. <br />MAX. <br />MIN. <br />(E)BT-1 <br />HTG LOOP <br />955 <br />185 <br />50 <br />50 <br />15 <br />15 <br />80 <br />80 <br />AMTROL EXTROL 300L <br />1 <br />NOTES: <br />1. EXISTING TO REMAIN. CONTRACTOR TO REPLACE <br />EXISTING BLADDER WITH NEW <br />BLADDER FROM ORIGINAL MANUFACTURER. <br />POINTS LIST SCHEDULE <br />SYSTEM DESCRIPTION <br />w <br />N <br />s <br />FMCS OUTPUT <br />EMCS <br />INPUT <br />EMCS ALARM <br />EMCS APPLICATION/ FUNCTION <br />REMARKS <br />DIGITAL <br />ANALOG <br />DIGITAL <br />ANALOG <br />DESCRIPTION <br />o~ <br />_ <br />- <br />e- <br />rn <br />o <br />0 <br />0 <br />oPOINT <br />0 <br />z <br />o <br />oQ <br />N <br />z <br />o <br />o <br />w <br />¢a <br />a <br />o <br />. <br />o <br />oIM <br />N wo <br />wo <br />Y <br />oN <br />mH <br />a¢o <br />¢ <br />¢ <br />- <br />z� <br />NEW EQUIPMENT <br />B-1,2 <br />GAS FIRED BOILERS <br />X <br />X <br />X <br />0 <br />X <br />X <br />X <br />X <br />X <br />X <br />EMCS ENABLES BOILERS <br />BURNER <br />0 <br />0 <br />0 <br />0 <br />INTERNAL CONTROL AND ALARM <br />FAN <br />0 <br />0 <br />0 <br />BP-1,2 <br />BOILER PUMPS <br />X <br />X <br />0 <br />X <br />0 <br />MODULATED BY BOILER <br />SPEED CONTROLLER <br />0 <br />X <br />0 <br />P-1,2 <br />MAIN CIRC PUMPS <br />X <br />X <br />X <br />X <br />VFD -1,2 <br />CIRC PUMP VFD <br />X <br />X <br />X <br />X <br />X <br />SUPPLY WATER TEMPERATURE <br />X <br />RETURN WATER TEMPERATURE <br />X <br />X <br />X <br />X <br />SUPPLY WATER PRESSURE <br />X <br />X <br />CO DETECTOR <br />CO ALARM <br />X <br />X <br />EPO <br />EMERGENCY SHUTOFF <br />X <br />X <br />EXIST. EQUIPMENT <br />SUMP PUMP <br />EXIST SUMP PUMP <br />X <br />X <br />X <br />X <br />RAD; UV; BCU; HVU <br />TERMINAL UNITS (IBEX CONTROL) <br />X <br />X <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) = EXISTING IBEX POINTS <br />NOTES: <br />0 INTERNAL CONTROL POINT <br />X DDC POINT <br />B GRHBNBUSCH GROUP, INC <br />do n xDE <br />(2moe) i ec� sdm swrt iosJ �a�'owis F�uc <br />Silver Lake Elementary <br />Boiler Replacement <br />address: <br />12815 Bothell -Everett Highway <br />Everett, WA 98208-6630 <br />design phase: <br />PERMIT <br />SET <br />revisions: <br />no. description date <br />design by: <br />R L / A V <br />drawn by: <br />J A / J Z <br />scale: <br />a s n o t e d <br />date: <br />11 / 15/2022 <br />job no.: <br />2022.125 <br />sheet title: <br />MECHANICAL <br />SCHEDULES <br />approvals: sheet number: <br />M0.3 <br />