SHEET NOTES: V1 a <br /> 1. REFER TO FEEDER AND PANEL SCHEDULES FOR ADDITIONAL 3 <br /> INFORMATION. <br /> w z <br /> 2. ONE-LINE DIAGRAM CREATED USING EXISTING RECORD <br /> DOCUMENTS.FIELD VERIFY EQUIPMENT,FEEDER SIZES,FUSE AND ,$ <br /> BREAKER RATINGS AND NOTIFY ENGINEER IMMEDIATELY OF ANY <br /> DISCREPANCIES. N g <br /> 3. COORDINATE POWER SHUTDOWNS OF OCCUPIED SPACES WITH m <br /> LANDLORD/OWNER. <br /> 2 � g <br /> FLAG NOTES: <br /> EXISTING PANELBOARD'PTIN PORTABLE RESTROOM TO BE REMOVED. Zjy.HUI <br /> s� <br /> EXISTING FEEDER TO REMAIN FOR REUSE. 0 <br /> SPLICE AND EXTEND FEEDER AS NECESSARY TO MAKE CONNECTION TO <br /> REPLACEMENT PORTABLE RESTROOM PANELBOARD'PT'.MATCH EXISTING 47756 <br /> WIRE AND CONDUIT SIZES. <br /> -roNAL F' <br /> �G <br /> EQUIPMENT SHALL BE SERVICE ENTRANCE RATED. <br /> (E)PRIMARY CABLING GROUND PER NEC AND WAC STANDARDS. <br /> INSTALLATION TO TRANSFORMER. <br /> I �SERVICEI <br /> EUTILITY XFMR <br /> W SEC. <br /> OINT <br /> 1000N <br /> 47,164 <br /> (E)EUSERC& FEEDER SCHEDULE <br /> T/METERING SECTION q <br /> :FC <br /> I COPPER CONDUCTORS <br /> V <br /> QUANTITY RACEWAY CONDUCTORS <br /> �(E)MAINS SECTION TAG OF SETS SIZE PHASE NEUTRAL GND(NOTE 3) <br /> OWNER METER(TYP.) 125 1 2" 3#1/0 - 1#6 <br /> I I M1 <br /> 125N 1 2' 3#1/0 1#1/0 1#6(#6) <br /> I I <br /> EPM 200 1 2-1/2" 3#3/0 - 1#6 <br /> 20ON 1 2-1/2" 3#3/0 1#3/0 1#6(#4) <br /> LAIN SWBD."MSB" 400 2 2-1/2" 3#3/0 - 1#2 <br /> I 480Y/277V,30,4W <br /> I 1000AMPS 1000A13P 40ON 2 2-1/2" 3#3/0 1#3/0 1#2(#1/0) <br /> 1000 3 4" 3#400kcmil - 1#2/0 <br /> I PARTIAL ONE-LINE 1000N 3 4" 3#400kcmil 1#400k—il 1#2/0(#3/0) <br /> I DIAGRAM.DOES NOT <br /> SHOW ALL CIRCUIT NOTES: <br /> C 20OA13P BREAKERS <br /> I <br /> N 1.COPPER FEEDERS ARE BASED ON COPPER CONDUCTORS <br /> I G WITH THWN/THHN INSULATION.CONDUCTOR DERATING O <br /> ---------------------- -----------------� IS BASED ON THWN/THHN CONDUCTORS WITH 90 O <br /> DEGREES C RATING. Z <br /> 2.GROUND CONDUCTOR(BONDING JUMPER)SIZE SHALL BE LIJG <br /> 200 <br /> INCREASED FOR FEEDERS FROM THE SOURCE OFA r , <br /> SEPARATELY DERIVED SYSTEM TO THE FIRST DISCONNECTING v� u <br /> ,`UMEANS PER NEC 250.30(A).SIZE AS INDICATED IN <br /> PARENTHESES. Q <br /> PORTABLE N ^ <br /> POWER VAULT LL L.L <br /> W <br /> HORIZON ELEMENTARY tY <br /> z CD <br /> SCHOOL RESTROOM <br /> 2°° <br /> 5,62° PORTABLE REPLACEMENT W Z <br /> (E)DISC DEMAND CALCULATION: W N <br /> I I'DT DP' JN 00 <br /> I 31211 EXISTING SERVICE: ryM� LJ_ m <br /> (3)200AF 12-MONTH PEAK DEMAND=152.2 kW W W <br /> 152.2 kW @ 0.9 POWER FACTOR=169.1 kVA O Q <br /> 169.1 kVA X 125%=211.4 kVA Z 5 z <br /> REVISED SERVICE: O O �/1 <br /> 200 ADJUSTED DEMAND=211.4 kVA O Q <br /> ADDED DEMAND OF PORTABLE RESTROOM=10.62 kVA U 1� <br /> TOTAL DEMAND=ADJUSTED+ADDED=222.0 kVA � LLJ <br /> 222.0 kVA/(480V x SQRT(3))=267 A �J_ <br /> _ NEW CALCULATED DEMAND DOES NOT EXCEED THE I,J_ <br /> (E)XFMR AMPACITY OF THE FEEDERS OR BUS SUPPLYING O N W <br /> IPOWER TO THESE LOADS. <br /> TPDP" ui <br /> 1150kVA N W <br /> 40ON <br /> (E)DIST.BOARD"PDP" <br /> 208/120V,30,4W I REV. RELEASE DATE <br /> EPR SET 11/28/23 <br /> 400AMPS C 400A/2P I <br /> I I <br /> I I <br /> 125A/2P 125A/2P 125A/2P 100A/2P 100A/2P 200A/2P <br /> I I <br /> I I <br /> (E)(3)#1/0 AWG+ (E)(3)#1/0 AWG+ (E)(3)#1/0 AWG+ (E)(3)#1/0 AWG+ <br /> 125N #6 AWG G #6 AWG G #6 AWG G #6 AWG G 20ON <br /> a <br /> 2"C 2"C 2"C 2 2"C <br /> 3 <br /> Q <br /> =w <br /> 3 <br /> N N N N N N PROJECT NO. 23202 <br /> p� IN� I IoC I lo< lob I to lo< <br /> z w I� I I� I I� I I� I I� I I� I HARGIS PROJECT NO. 23202 <br /> o DRAWN BY AH <br /> N u u u u AWG u CHECKED BY MH <br /> o (E)PANEL (E)PANEL (E)PANEL (E)PANEL t (E)P7�L 4 PANEL (E)PANEL APPROVED BY MH <br /> N "P-5" "P-1" "P-2" "P-3" "PTPT" "P-6/P-7" <br /> 125A 100A 100A 100A 100A 100A A 200A SHEET TITLE <br /> �0 5 PARTIAL ELECTRICAL <br /> ONE-LINE DIAGRAM <br /> Ino PARTIAL ELECTRICAL ONE-LINE DIAGRAM <br /> a E9.01 SCALE:NONE SHEET NUMBER <br /> rw <br /> °w LL E9.01 <br /> 0 <br />