My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
1318 75TH ST SE 2024-03-01
>
Address Records
>
75TH ST SE
>
1318
>
1318 75TH ST SE 2024-03-01
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
3/1/2024 3:57:39 PM
Creation date
2/13/2024 11:03:33 AM
Metadata
Fields
Template:
Address Document
Street Name
75TH ST SE
Street Number
1318
Imported From Microfiche
No
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
312
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Soniya <br />Blue Moon Realty LLC <br />Plan Check Number: B2201-048, 2nd Building Review <br />June 16, 2022 <br />Architectural <br />1. Safety glazing should be specified for the window located at the bottom of the stairs adjacent to <br />the front entry door. R308.4.7 <br />2. It appears that the garage stair landing is 30 inches above the adjacent floor. A guardrail <br />should be specified. Guard details should be included in the construction drawings. The guards <br />should comply with IRC Section R312.1. The guards, connections to the supporting framing, <br />and the supporting framing should be designed to resist a minimum 200-pound load per Table <br />R301.5. <br />3. A landing should be specified and shown on the drawings located at the bottom of the exterior <br />stairs. R311.7.6 <br />4. See energy credits on Sheet All. To qualify to claim credit 2.1, the building permit drawings <br />should specify the option being selected, the maximum tested building air leakage, and should <br />show the qualifying ventilation system and its control sequence of operation. WSEC Table <br />R406.3 <br />5. See energy credits on Sheet All. To qualify to claim credit 3.6, the building permit drawings <br />shall specify the option being selected, the heating equipment type(s), the minimum equipment <br />efficiency, and total installed heat capacity (by equipment type). WSEC Table R406.3 <br />6. See energy credits on Sheet All. To qualify to claim this credit, the building permit drawings <br />should specify the option being selected and should specify the water heater equipment type <br />and the minimum equipment efficiency. WSEC Table R406.3 <br />7. The roof details should comply with the ventilation requirements of IRC Section R806 and WSEC <br />Section R402.2.3. Include a calculation for the minimum required ventilation area in the <br />drawings. The vents should be equally distributed between the roof eaves and ridge, and <br />around the building perimeter. <br />Structural <br />1. The plans appear to show basement retaining walls supporting more than 48 inches of <br />unbalanced backfill. Retaining wall details should be included in the drawings and calculations <br />substantiating the design should be submitted for review. See IRC Section R404.1.1. Note that <br />retaining walls supporting more than 6 feet of backfill height measured to the bottom of the <br />footing should include an additional seismic lateral earth pressure. IBC 1807.2.2 <br />2. Continuing with the previous comment, the referenced detail 12/S3.0 appears to not apply. <br />The basement specifies a concrete slab and sections on Sheet A9 show a basement retaining <br />wall. Detail should be updated to reflect the sections on Sheet A9. R106.1.1 <br />3. It appears that the structural calculations on Page 28 specify a 4-foot square footing (F1), but <br />the drawings do not show the F1 footing. R106.1.1 <br />3200 Cedar Street © 425.257.8810 O everetteps@everettwa.gov <br />Everett, WA 98201 425.257.8857 fax everettwa.gov/permits <br />Page 2 of 3 <br />
The URL can be used to link to this page
Your browser does not support the video tag.