• <br /> • December 2008 Section 2 System Components Page 2—8 <br /> • Amerex Restaurant Fire Suppression System (EX 4658) <br /> • DETECTOR BRACKET ASSEMBLY(P/N 12508) 10" <br /> (25.4 cm) ,.--- <br /> • Each detector bracket in the Amerex Kitchen Fire I <br /> • Suppression System is comprised of three parts the <br /> detector bracket, detector linkage and two EMT fittings. i( / C \ i I <br /> • The fusible link is ordered separately. The bracket serves r a Q ,� <br /> • gi ma <br /> as support for the linkage and is attached to a rigid _fall ( � �� Limon <br /> • surface. The linkage supports the fusible link and a <br /> continuous cable run under tension. At a predetermined Fusible link not included with detector <br /> • temperature the fusible link will separate, relieving tension <br /> • on the cable and actuating the system. <br /> • This manual will refer to series and terminal detectors. There is no difference in part num s or dimensio <br /> between series and terminal detectors. A terminal detector is the last or only detector in the network and the <br /> • cable must be "terminated" there. A series detector is any detector located betwee erminal detector <br /> • and the mechanical release module in the detection network. Cable Terminal End <br /> 13110 \ tR , <br /> • TEST LINKS (P/N 12891) <br /> • Test links are available for conducting functional tests of the detection , ,l.• system. This device fits the detector linkage in the same manner as the l f97, <br /> fusible link, is normally placed on the terminal detector and can be cut, <br /> • simulating a fusible link separating under fire conditions. P/N 12891 <br /> • CORNER PULLEY(P/N 12309) 13/64"Dia. <br /> • Mounting <br /> • The Amerex Kitchen Fire Suppression System uses a"high temperature" � Holes <br /> corner pulley to change direction of the cable by 90°. This corner pulley ( z(j�) ' 2 <br /> (• may be used in environments with temperatures up to 700°F (371°C). <br /> • Mounting holes are provided for anchoring the corner pulley where �\ 3o9 /\ <br /> allowed by local codes.• P/N 12309 <br /> • CORNER PULLEY(P/N 16444) <br /> 111 <br /> • The Amerex Kitchen Fire Suppression System also use a "high temperature" �, <br /> compression corner pulley to change direction of the cable by 90°. (This ( ©�11 <br /> • �_ \ <br /> compression corner pulley [Brooks Model CP5] allows complete assembly of j �`\ � P/N 16444• <br /> � <br /> conduit and corner pulleys prior to installing the cable). <br /> • PULLEY TEE (P/N 12506) i„° '6 <br /> • I1 - <br /> A pulley tee is used to change the direction of two cables by 90°. This ( u I /P/N 12506 <br /> • device can be used with mechanical gas valves and manual pull stations j <br /> 411 but not fusible link detectors. It cannot be used where temperatures g•*c ,t5 ° <br /> l�h <br /> exceed the ran e of 32° 120°F (0°-49°C). , �J J <br /> • <br /> • CABLE (P/N 12553) <br /> • Cable is used to run from the MRM, MRM II or PRM, through conduit and corner pulleys to detectors, <br /> mechanical gas valves or manual pull stations. It is 1/16 inch diameter, stainless steel (7 x 7 —480#tensile <br /> • strength)—available in 500 foot(152 m)spools(P/N 12553). <br /> • <br /> EYEBOLT SUPPORT (P/N 17520) <br /> • <br /> • Eyebolt supplied with one Hex. Nut used to lock the eyebolt into finial t- . \ ^.. <br /> position. Eyebolt is used to support bare cable run in plenum of the ��/ <br /> • hood in a Linear Fusible Link Detection System. <br /> • <br />• <br />• <br />