Laserfiche WebLink
(E) POTTER AFC-1 00 <br /> The Symbol of Protection Fire Alarm Control Panel <br /> SLC Loop Accessories <br /> The control panel may be connected with up to 100 addressable devices or modules in any combination.The SLC is not restricted by any special wire <br /> requirements and may be wired with any wire that complies with the NEC. <br /> SLC Loop Devices <br /> Device Description <br /> PAD100-PD Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 to 3.83 percent per foot. <br /> PAD 100-PHD Combination Analog Photo Electric Smoke/Heat Detector—a smoke detector with a listed obscuration of 1.02 to 3.83 percent <br /> obscuration and a fixed temperature 135°Fahrenheit heat detector. <br /> PAD100-HD Analog Fixed(135d-185dF)or Rate-of-Rise Heat Detector(software selectable) <br /> PAD 100-DUCTR Addressable Duct Smoke Detector with Form C Relay.Addressable Duct Smoke Detector with Form C relay rated at 10a @ <br /> 250/120VAC or 8amps at 30VDC. <br /> PAD100-DUCT Addressable Duct Smoke Detector. <br /> PAD 100-6B 6"round base that is mounted to an electrical box and wired for connection of one of the above sensors. <br /> PAD 100-4B 4"round base that may be mounted to an electrical box and wired for connection to the above sensors. <br /> PAD 100-IB Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop. <br /> PAD100-RB Addressable Relay Base that contains one relay controlled by the SLC.Relay is rated at rated at 2 amps at 30 VDC or 0.5A at 125VAC. <br /> PAD100-SB Addressable Sounder Base that contains an addressable sounder module that may be configured for local,group and all call. <br /> PAD100-CD Addressable CO gas detector. <br /> PAD 100-DD Addressable photo electric smoke detector for use in DUCT/DUCTR enclosure. <br /> PAD100-LFSB Addressable Low Frequency Sounder Base that contains an addressable sounder module that may be configured for local,group and all <br /> call. The LFSB complies with the Low Frequency Signal Requirements(520 Hz) <br /> PAD100-SPKB Speaker base is a wall or ceiling mount speaker capable of 25 or 70.7 VRMS and is field selectable from 1/8W to 4W. <br /> Modules <br /> Device Description <br /> PAD 100-MIM Micro Input Module provides a small foot print contact module for mounting inside an enclosure. <br /> PAD100-PSSA Single Action Addressable Pull Station. <br /> PAD100-PSDA Dual Action Addressable Pull Station. <br /> PAD100-SIM Single Input Module is a standard contact module with an LED that mounts into a 4"square electrical box. <br /> PAD 100-DIM Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode. <br /> PAD100-TRTI Two Relay Two Input module provides two form C relays that are individually controlled by the control panel.Each relay is rated for 2 <br /> amps at 30VDC or 0.5 amps at 125VAC.Also provides two contact inputs. <br /> PAD 100-NAC Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel. <br /> PAD 100-ZM Zone Module is used to connect conventional 2-wire smoke detectors to the system. <br /> PAD100-IM Isolater Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop. <br /> PAD100-RM Relay Module that provides one form C relay controlled by the control panel.Relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC. <br /> PAD 100-LED Module provides a single addressable LED that is controlled by the control panel. <br /> PAD 100-SM Speaker Module provides switching for two audio channels. <br /> PAD 100-LEDK Addressable LED and key switch that mounts in a single gang box. <br /> PAD 100-DRTS DUCTR Remote Test Switch that mounts in a single gang box and optionally supervised.For use with the PAD 100-DUCTR only. <br /> PAD100-OR0I One Relay One Input Module provides one form C relay and one input.The relay is rated at 2 amps at 30VDC or 0.5 amps at 125VAC. <br /> Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com <br /> 8830134-REVD 3/19 PAGE 2 OF 4 <br />