Anchor Fastening Technical Guide, Edition 21
<br /> DESIGN DATA IN CONCRETE PER ACI 318
<br /> ACI 318 Chapter 17 Design
<br /> The design tables in Tables 2 to 4 are Hilti Simplified Design Tables. The load values were developed using the design
<br /> parameters and variables of ICC Evaluation Services ESR-4236 and the equations within ACI 318 Chapter 17 as amended by
<br /> ICC-ES AC193. The strength design capacities calculated from the tables below are to be compared to the factored loads
<br /> determined from strength design load combinations. For a detailed explanation of the Hilti Simplified Design Tables, refer to
<br /> Section 3.1.8. Data tables from ESR-4236 are not contained in this section, but can be found at www.hilti.com or
<br /> www.icc-es.org.
<br /> Table 2 - Hilti HDI-P TZ design strength based on concrete failure modes in uncracked concrete
<br /> per ACI 318 14 Ch. 17 1'2'3'4'5
<br /> Nominal Nominal Tension(lesser of concrete breakout/pullout)-cpN Shear(lesser of concrete breakout or pryout)-rpVn
<br /> anchor embed. f',=2500 psi f',=3000 psi f',=4000 psi f',=6000 psi F0=2500 psi f',=3000 psi f',=4000 psi f',=6000 psi
<br /> diameter in.(mm)
<br /> in. (17.2 MPa) (20.7 MPa) (27.6 MPa) (41.4 MPa) (17.2 MPa) (20.7 MPa) (27.6 MPa) (41.4 MPa)
<br /> lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN)
<br /> 3/8 3/4(19) 310(1.4) 340(1.5) 395(1.8) 485(2.1) 350(1.6) 385(1.7) 445(2.0) 545(2.4)
<br /> Table 3 - Hilti HDI-P TZ design strength based on concrete failure modes in cracked concrete
<br /> per ACI 318 14 Ch. 17 1'2.3'4'5'6'7
<br /> Nominal Nominal Tension(lesser of concrete breakout/pullout)-cpN0 Shear(lesser of concrete breakout or pryout)-cpVn
<br /> anchor embed. f',=2500 psi f',=3000 psi f',=4000 psi f',=6000 psi f',=2500 psi f',=3000 psi f',=4000 psi f',=6000 psi
<br /> diameter in.(mm) (17.2 MPa) (20.7 MPa) (27.6 MPa) (41.4 MPa) (17.2 MPa) (20.7 MPa) (27.6 MPa) (41.4 MPa)
<br /> in. lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN)
<br /> 3/8 3/4(19) 190(0.8) 200(0.9) 220(1.0) 255(1.1) 250(1.1) 270(1.2) 315(1.4) 385(1.7)
<br /> The following footnotes apply to both Table 2 and 3:
<br /> 1 See Section 3.1.8.6 of the Anchor Tech Guide Ed.17 to convert design strength value to ASD value.
<br /> 2 Linear interpolation between concrete compressive strengths is not permitted.
<br /> 3 Tabular values are for a single anchor with a minimum edge distance of 6-1/2-in(166mm)and a minimum spacing of 8-in(204mm). For a 6-in(153mm)edge distance multiply
<br /> uncracked concrete tension and shear values by 0.92. No reduction needed for cracked concrete.
<br /> 4 Compare to the steel values in Table 4. The lesser of the values is to be used for the design.
<br /> 5 Tabular values are for normal weight concrete only. For lightweight concrete multiply design strength by A,as follows:For sand-lightweight,A,=0.68. For all-lightweight,A,=0.60.
<br /> 6 Tabular values are for static loads only. For seismic tension loads,multiply cracked concrete tabular values in tension by aN,,,,=0.74.
<br /> 7 No additional reduction needed for seismic shear for concrete breakout or pryout failure. See Section 3.1.8.7 of the Anchor Tech Guide Ed.17 for additional information on seismic
<br /> applications.
<br /> Table 4 - Hilti HD1-P TZ design strength based on steel failure per ACt 318 Ch. 17 1,2,3
<br /> Steel strength of HDI-P TZ anchor Steel strength of ASTM A36 threaded rod
<br /> Nominal anchor
<br /> diameter Tensile' Shears Seismic Shear" Tensile' Shear' Seismic Shear"
<br /> in. WNsa TV. WVsa iPNsa.md NVsa.,d NVsa,rod.aa
<br /> lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN)
<br /> 3/8 4,065(18.1) 585(2.6) 585(2.6) 3,370(15.0) 1,885(8.4) 1,320(5.9)
<br /> 1 See Section 3.1.8.6 of the Anchor Tech Guide Ed.17 to convert design strength value to ASD value.
<br /> 2 Steel strength in tension and shear determined from the lesser of the HDI-P TZ or the inserted threaded rod.
<br /> 3 Hilti HDI-P TZ anchors are considered a brittle steel element. ASTkA A36 threaded rod is considered a ductile steel element.
<br /> 4 Tensile cpN„=cpA,,,^,f,,,,as noted in ACI 318 Ch.17.
<br /> 5 Shear values for HDI-P TZ determined by static shear tests with cpV„s N 0.60 A,,,v f,,,as noted in ACI 318 Ch.17.
<br /> 6 Seismic shear values for HDI-P TZ determined by seismic shear tests with cpV„<cp 0.60 A„.„f,,,,as noted in ACI 318 Ch.17.
<br /> 7 Shear values for threaded rod determined by WV..,,,=cp 0.60 A,,,,,f,„,as noted in ACI 318 Ch.17.
<br /> 8 Seismic shear values for threaded rod determined by iPV , =cp 0.70
<br /> 9 See Section 3.1.8.7 of the Anchor Tech Guide Ed.17 for additional information on seismic applications
<br /> Anchor Fastening Technical Guide Edition 21 13.0 ANCHORING SYSTEMS 13.3.13 HDI-P TZ FLUSH ANCHOR 431