LEGEND: <br /> O JUNCTION BOX 4S UNLESS NOTED OTHERWISE <br /> �s IONIZATION SMOKE DETECTOR <br /> 110CD <br /> © F❑ MANUAL STATION, DOUBLE ACTING <br /> WP <br /> F F M STROBE ALARM <br /> 3 3 MJ AUDIBLE/VISUAL ALARM <br /> 45-120 MAN PULL W 45-120 MAN PULL E <br /> CEILING AUDIBLE/VISUAL ALARM <br /> ZONE #: 10, L1:10 ZONE #: 09, L1:09 � <br /> 8 FIRE ALARM PANEL <br /> ® TELEPHONE PANEL <br /> 0 ADT PANEL <br /> EAc CELLULAR COMMUNICATOR <br /> SMK W SMK E <br /> ZONE #: 08, L1:08 ZONE #: 07, L1:07 <br /> GENERAL NOTES: <br /> 30CD /\ /\ 30CD <br /> 45-237 IS MONITORED BY 45-208 BUILDING FACP. <br /> BUILDING <br /> 45-120 REFERENCE DRWAWINGS <br /> 45-237-1E60 POWER PLAN VIEW <br /> 2� 45-237—E506 FIRE ALARM DETAILS <br /> 110CD <br /> WID © 110CD <br /> WID © CONSTRUCTION NOTES: <br /> THIS FIRE ALARM DESIGN IS INTENDED TO BE A <br /> PRELIMINARY DESIGN TO DIRECT A NICET CERTIFIED <br /> Wi 3 DESIGNER TO COMPLETE FINAL FIRE ALARM DESIGN IN <br /> ACCORDANCE WITH ALL APPLICABLE LAWS AND CODES. <br /> F APPLICATION FOR FIRE ALARM PERMIT USING FINAL <br /> 75CD STAMPED DRAWINGS IS REQUIRED. <br /> 45-237 MAN PULL DR W1 5 <br /> ZONE #: 03, L1:03 BUILDING FACP <br /> REMOVE OLD FACP, FOCUS PANEL, AND ASSOCIATED <br /> SMK OFFICE W SMK OFFICE E SMK RM 208 W SMK RM 208E HARDWARE. PROVIDE AND INSTALL NEW DIGITAL <br /> ZONE #: 02, _1:02 ZONE #: 01, _1:01 ZONE 05, _1:05 ZONE 04, _1:04 ADDRESSABLE BUILDING FACP. PROVIDE PHENOLIC <br /> # # LABEL ON PANEL THAT READS: <br /> Is <br /> 3 2 21 1 3 3 JF <br /> ZONEO� M06N PULL "45 237 06 EVi—FA-45-237 ARM CONTROL PANEL <br /> 120VAC FED FROM PANEL 'A'/20b" <br /> 30CPROVIDE CELLULAR COMMUNICATOR AND WIRE TO <br /> BUILDING FACP. SEE SHEET E506 FOR INSTALLATION <br /> BUILDING DETAILS. <br /> W2 BUILDING 45-208 <br /> 3 REPLACE EXISTING FIRE ALARM DEVICE WITH NEW <br /> COMPATIBLE DEVICE. REUSE CONDUIT AND WIRE WHERE <br /> POSSIBLE. (TYP. 6 SMOKES, 5 MANUAL PULL <br /> STATIONS, 7 HORN/STROBES) <br /> 4. FILL OUT AND RETURN ATTACHED BUILDING FACP <br /> POINTLIST TO ENGINEER A MINIMUM OF 3 WEEKS <br /> PRIOR TO FINAL ACCEPTANCE TESTING. <br /> PROVIDE NEW HORN/STROBE. NICET DESIGNER TO <br /> DETERMINE FINAL LOCATION AND QUAINTLY AS <br /> p REQUIRED BY CODE. <br /> FLOOR PLAN — EIRE ALARM © PROVIDE NEW OUTDOOR RATED HORN/STROBE, NICET <br /> SCALE: 1/4"=1'-0" N DESIGNER TO DETERMINE FINAL LOCATION AND <br /> QUAINTLY AS REQUIRED BY CODE. <br /> 4' 2' 0 2' 4' 8' <br /> SCALE: 1/4"=1'-0" <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATEDRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE <br /> A FACP REPLACEMENT W9063564 JC MDK 03.17.23 ACCEPTABILITY J. KLU N 11.13.23 FIRE ALARM POWER PLAN <br /> 29592174 11.13.23 <br /> SPTHIS <br /> ECIFICDESIGN AND/OR CHECKED ATION ISAPPROVED K. MULLEN 11.14.23 SHEET <br /> B SHOP DRAWINGS 29592174 AGOW JS 11.13.23 BOE/w" m naPRovEo BY DEPT. DATE TITLE <br /> K. MULLEN 11.14.2 <br /> 1 E260 <br /> 3 <br /> CHECKED <br /> �t Li amen 29592174 <br /> APPROVED BUILDING 45-237 JOB N0. COMP NO. <br /> .w.u...�.. � <br /> APPROVED EVERETT, WA DWG NO. 45-237-1E260 <br />