Laserfiche WebLink
FACP BATTERY CALCULATIONS <br /> COMPONENTS orv. cuRRENT CURRENT REM POWER CABLE (SUPPLIED <br /> AFC-100(FACP) 1 0.13000A 0.22000A WITH PEM <br /> UD-2000(DACT) 1 0.01600A 0.02300A 6 5 3 4 <br /> SLC DEVICES SUPERVISORY ALARM <br /> CURRENT CURRENT <br /> PAD-PD 6 0.00030A 0.00030A 0.00180A 0.00180A 1 <br /> PAD-HD 0 0.00030A 0.00030A 0.000OOA O.000OCA <br /> PAD-DUCT 0 0.00030A 0.00030A 0.000OOA 0.000OOA <br /> PAD100-PSSA/PSDA 4 0.00020A 0.00020A 0.00080A 0.00080A <br /> PAD100-RM 0 0.00024A 0.00024A 0.000OOA O.000OOA <br /> PAD-MIM 10.00020A 0.00040A 0.00020A 0.00040A <br /> PAD100-DIM o 0.00024A 0.00o24A 0.00oo0A o.000OOA 3 3/4"C - 2#14THHN,1#14G 2 B <br /> STANDBY ALARM TG-PEM <br /> F 04 <br /> CURRENT CURRENT <br /> NAC CKT 1(AUX PWR) 0.018A 0.11000A 0.01800A 0.11 oo0A <br /> NAC CKT 2 O.00A 1.11700A o.000OOA IA1700A FACP EVT-FA-45-237 I I TG-7FS <br /> - o.00A o.000OOA o.000OOA 0.000oaA (BY FIRE ALARM VENDOR) GEN 1 1 4 7 <br /> SLC ALARM LED O.00A 0.036 CA O.000OOA 0.03600A R <br /> TOTAL 0.1668A L509A JG TOTAL STANDBY CURRENT DRAW= 0.1668 AMPSX STANDBY TIME 48 HOURST <br /> STANDBY AMP HOUR TOTAL= 8.006 AHDC STC2 STCITRIP BATT AC <br /> TOTAL ALARM CURRENT DRAW= 1.509 AMPSX ALARM TIME 0.167 HOURS 1 21 2 3 4 5 6 12 3 1 2 <br /> ALARM AMP HOUR TOTAL= 0.252 AH BB (D &Ga BB <br /> STANDBY AH + ALARM AH = 8.2584 AH eLK <br /> X DE PALING FACTOR 1.20(20%) xED EOL(q NEEDED) <br /> TOTAL AH REQUIRED= 9.9101 All <br /> MINIMUM BATTERY SIZE NEEDED: 10 AH <br /> BATTERY SIZE PROVIDED: 12 AH <br /> NOTE: 0.167 EQUALS 10 MINUTES OF ALARM TIME <br /> 3/4"C - (1) PHONE CABLE, <br /> (1) 2 CONDUCTOR FPL OR <br /> APPROVED EQUAL <br /> FACP VOLTAGE DROP CALCULATION CONSTRUCTION NOTES <br /> CIRCUIT SUPPLY ALARM OHMS NGT TOTAL LAST DEVICE ;DROP <br /> LTAG <br /> NAME VOLTAGE cuRRENT WIRE TYPE 000 F. FEET RESISTANCE VOLTAGE % [j�::, PROVIDE CELLULAR DIALER, AND MOUNT ADJACENT TO <br /> NAC1(AUX) 20.4 VDC 0.110 A #14AWG SOLID 3.07 10 0.0614 20.393 VDC 0.03% THE BUILDING FACP. CONFIGURE DIALER TO PROVIDE <br /> NAC2 20.4 VDC 1.117 A #14AWG SOLD 3.07 208 1.2771 18.97 VDC 6.99% SOLE PATH COMMUNICATION. DIALER SHALL BE <br /> N/A 20.4 VDD 0.000 A #14AWG SOLID 3.07 0 0 00.00 VDC 0% EIRE ALARM SYSTEM COMMUNICATIONS DETAIL COMPATIBLE WITH AT&T CELL SERVICE. <br /> N/A 20.4 VDC 0.000 A #14AWG SOLD 3.07 0 0 00.00 VDC 0% SCALE: NONE 7260 E506 <br /> PROVIDE (1) CONDUIT PENETRATION FOR PHONE AND <br /> FIRE ALARM CONNECTIONS. WIRE AS SHOWN. PROVIDE <br /> ADDRESSABLE MODULE AS NECESSARY TO PROVIDE <br /> F STEP 1: VERIFY SIGNAL STRENGTH AT PROPOSED LOCATION FOR CELLULAR COMMUNICATOR PANEL INDICATED ON GENERAL TROUBLE ALARM FROM CELLULAR DIALER TO <br /> �QJv� �QJv`� �� �� �QJv`� �� �� �� DRAWINGS. IF ACCEPTABLE *SIGNAL STRENGTH IS ACQUIRED, SKIP TO STEP 5. BUILDING FACP. <br /> STEP 2: IF ORIGINALLY PROPOSED LOCATION IS INADEQUATE, FIELD TEST *SIGNAL STRENGTH WITHIN A 20FT RADIUS <br /> TO IDENTIFY LOCATIONS SUITABLE FOR INSTALLATION OF REMOTE EXTERNAL CELLULAR ANTENNA. PROVIDE (1) CONDUIT PENETRATION FOR 2ILDING C <br /> ( ) / POWER AND EARTH GROUND FROM THE BUILDING FACP <br /> ��� ��� OQO& COORDINATE THE FINAL ANTENNA LOCATION WITH BOEING AND SPACE USERS (IF IMPACTED) FOR POWER SUPPLY. PROVIDE POWER AND EXPANSION <br /> MONITORED BY TYCO AND APPROVAL PRIOR TO ROUGH-IN AND SKIP TO STEP 4. MODULE AND WIRE AS SHOWN. MAINTAIN <br /> F F S S F S S F S S MIM C <br /> ELLULAR * MANUFACTURER'S REQUIRED 1/4" SEPARATION <br /> 1:10 1:09 L1:08 L1:07 1:06 L1:05 L1:04 1:03 L1:02 L1:01 1:11 ANALOG PHONELINE SIGNAL SENT TO CENTRAL STEP 3: IF ACCEPTABLE SIGNAL STRENGTH IS NOT ACHIEVED WITHIN 20FT OF ORIGINAL PROPOSED LOCATION FOR BETWEEN POWER AND COMMUNICATION WIRING. <br /> (PRIMA R YBOEING FIRE DEPARTMENT CELLULAR COMMUNICATOR PANEL, PROPOSE ALTERNATE LOCATION FOR CELLULAR PANEL. COORDINATE <br /> 45-237 FACP EPARATE PATHWAYS FOR WITH BOEING AND SPACE USERS FOR POTENTIAL LOCATIONS, PREFERABLY NEAR ORIGINAL LOCATION. ® PROVIDE PHENOLIC LABEL, WHITE LETTERING, RED <br /> WP WP WP REQUIRED BY CODE, AS STEP 4: LOCATE AND PROVIDE EXTERNAL CELLULAR ANTENNA, EXTERIOR MOUNTING BRACKET AND COAXIAL CABLE BACKGROUND, THAT READS: <br /> NAC2 . FROM CELLULAR COMMUNICATOR TO THE ANTENNA. THE ANTENNA AND PANEL SHOULD BE LOCATED <br /> 11CD 30CD 30CD 75CD 110CD 110CD 30CD WITHIN 20FT OF EACH OTHER. "FIRE ALARM CELLULAR DIALER" <br /> ANALOG PHONE LINE STEP 5: PROVIDE 24VDC POWER, MONITORING CIRCUIT, AND TELEPHONE LINE TO CELLULAR COMMUNICATOR FROM PROVIDE CELL ANTENNA AND EVALUATE FIELD SIGNAL <br /> (SECONDARY) BUILDING FACP. STRENGTH IN ACCORDANCE WITH DETAIL 2. INSTALL <br /> EVT-FA-45-237 STEP 6: PROVIDE REQUIRED SET-UP, PROGRAMMING AND TESTING OF CELLULAR COMMUNICATOR EQUIPMENT PER CONDUIT AND EXTENDED ANTENNA CABLE AS <br /> THE MANUFACTURER'S INSTRUCTIONS. CELLULAR DIALER SHALL BE CONFIGURED AND INSTALLED AS A NECESSARY TO REMOTE MOUNT ANTENNA IF COVERAGE <br /> SOLE PATH FOR FIRE COMMUNICATIONS. IS NOT SUITABLE AT FACP LOCATION. UPDATE BOM <br /> WITH SELECTED CABLE LENGTH AND PROVIDE REDLINES <br /> 13'111 c" TO BOEING ENGINEER. <br /> *ACCEPTABLE SIGNAL STRENGTH SHALL BE DETERMINED BY MANUFACTURERS SPECIFICATIONS AND LOCAL AHJ <br /> ORDINANCES. © FOR REMOTE INSTALLATIONS PROVIDE PHENOLIC LABEL, <br /> WHITE LETTERING, RED BACKGROUND, THAT READS: <br /> BUILDING FIRE ALARM SYSTEM RISER "FIRE ALARM CELLULAR ANTENNA" <br /> SCALE: NONE E506 <br /> CELLULAR COMMUNICATOR INSTALLATION SEQUENCE INSIDE CELL ENCLOSURE POST COMMUNICATOR <br /> SCALE: NONE E260 E506 PRINTEDS LABEL, HANDWRITTENHANDWR TTEELLUAR ON EINFORMATION PIS ROVIDE <br /> 45-237 BUILDING SYSTEM FACP POINTS ACCEPTABLE. PROVIDE SETTINGS AND CELLULAR <br /> INFORMATION TO BOEING ENGINEER. <br /> POINT NUMBER/ZONE BOEING DESCRIPTION FACP POINT - COMMENTS - GRID/SHEET LOC. <br /> L1:001 1 45-237 SMK OFFICE E BLDG. 237 EAST SMOKE DETECTOR <br /> _1:002 2 45-237 SMK OFFICE W BLDG. 237 WEST SMOKE DETECTOR <br /> BILL OF MATERIALS <br /> L1:003 3 45-237 MAN PULL DR W1 BLDG. 237 MANUAL PULL STATION <br /> ITEM QTY. PART NO. MANUFACTURER DESCRIPTION <br /> _1:004 4 45-208 SMK RM E BLDG. 208 EAST SMOKE DETECTOR <br /> 1 1 3992753 POTTER FIRE ALARM CONTROL PANEL <br /> _1:0055 45-208 SMK RM w BLDG. 208 w7sT SMOKE DETECTOR <br /> _1:006 6 45-208 MAN PULL BLDG. 208 MANUAL PULL STATION 2 1 3992769 POTTER UD-2000 DACT CARD <br /> _1:007 7 45-120 SMK E BLDG. 120 EAST SMOKE DETECTOR 3 6 3992732 POTTER PAD100 6" BASE <br /> u:0o8 8 45-120 SMK W BLDG. 120 WEST SMOKE DETECTOR 4 6 3992770 POTTER PAD200 PHOTO DETECTOR <br /> _1:009 9 45-120 MAN PULL E BLDG. 120 EAST PULL STATION 5 4 3992720 POTTER PAD100 PULL STATION <br /> u:o10 10 45-120 MAN PULL W BLDG. 120 WEST PULL STATION 6 1 3992700 POTTER PAD100 MICO INPUT MODULE <br /> L1:011 11 DIALER TROUBLE CELLULAR COMMUNICATOR TROUBLE 7 2 SLA1104 POWERPATROL 12VDC 12 AH BATTERIES <br /> a <br /> � 8 2 BK-P2RL SYSTEM SENSOR HORN/STROBES (WALL MOUNT) <br /> 1 <br /> BUILDING FACP POINTS LIST 9 2 BK-PC2RL SYSTEM SENSOR HORN/STROBES (CEILING MOUNT) <br /> 0 3 BK-P2RK SYSTEM SENSOR WEATHER PROOF HORN/STROBES <br /> SCALE: NONE E`506 11 1 TG-7FS-A TELGUARD ATT CELLULAR DIALER <br /> 12 1 SSU00689 SPACEAGE FIRE ALARM STORAGE CABINET <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATEDRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE <br /> A FACP REPLACEMENT W9063564 JS MDK 03.17.23 ACCEPTABILITY J. KLU N 11.13.23 <br /> THIS FIRE ALARM SYSTEM DETAILS <br /> DESIGN ANDIOR CHECKED 29592174 11.13.23 <br /> SPECIFICATION IS APPROVED K. MULLEN 11.14.23 SHEET <br /> B SHOP DRAWINGS 29592174 AGOW JS 11.13.23 BOEIrw" APPROVED er DEPT. DATE TITLE E506 <br /> CHECKED <br /> .tL: K. MULLEN 11.14.23 <br /> APPROVED BUILDING 45-237 JOB NG 29592174 COMP NO. <br /> Q ,,� APPROVED EVERETT, WA DWG NO. 45-237-E506 <br />