Laserfiche WebLink
`Kidde Fire Systems <br />Consolidated Report <br />Parts Report <br />Total Agent Required: 271.5 lb <br />Cylinder Name: 80L 300 bar Nitrogen Cylinder (Part: 38-428031-100) <br />Number of Cylinders: 5 <br />Nozzle <br />Nozzle <br />Type <br />Diameter <br />Nozzle Area <br />Part Number <br />E1-N1 <br />180 <br />3/4 in <br />0.1902 in z <br />38-407600-125 <br />E2-N1 <br />180 <br />1/2 in <br />0.0247 in z <br />38-407500-045 <br />Pipe & <br />Fittings <br />Type <br />Diameter <br />Length Elbows (90) Elbows (45) Tees <br />Unions <br />40T <br />1/2 in <br />10.67 ft <br />0 0 0 <br />0 <br />40T <br />3/4 in <br />23.43 ft <br />3 0 1 <br />0 <br />40T <br />t in <br />5.13 ft <br />0 0 5 <br />0 <br />Other <br />Obiects <br />Name Quantity Part Number <br />3/4 in. Flex Hose, 16 in., 90/90 <br />5 38-400330-410 <br />End Cap <br />1 38-400020-101 <br />Prebuilt <br />Manifold: <br />1 38-351000-007 <br />System Acceptance Report <br />System Discharge Time: <br />113.5 seconds <br />Percent Agent In Pipe: <br />1.8% <br />Percent Agent Before First Tee: <br />1.6% <br />Enclosure Number: 1 <br />Enclosure Name: ROOM <br />Minimum Design Concentration: 46.90% <br />Adiusted Design Concentration: 50.55% <br />Calculation Date/Time: Monday, February 13, 2023, 1:26:29 PM <br />Copyright (c) JENSEN HUGHES, Inc. Licensed to: Kidde-Fenwal <br />KeyID:396621834 <br />Page: 3 of 11 <br />