Laserfiche WebLink
L Kidde Fire Systems Consolidated Report <br />Maximum Design Concentration: 52.00% <br />Minimum Predicted Concentration: 50.92% (At 70 F) <br />Maximum Predicted Concentration: 50.92% (At 70 F) <br />Maximum Allowed Enclosure Pressure: 5.0 lb / ft 2 <br />Estimated Free Vent Area Required: 0.8 ft2 <br />Installed Vent Area: 0.0 ft2 <br />Predicted Enclosure Pressure: N/A <br />Maximum Enclosure Flow Rate: 2.7 INS <br />Oxygen Concentration (Total Discharge): 10.3% <br />Minimum <br />Agent Adjusted Agent <br />Nozzle Required Required <br />Predicted <br />Agent <br />Delivered <br />Nozzle <br />Pressure <br />(Average) <br />E1-N1 214.7 lb 238.8 lb 241.3 lb 397 prig <br />Enclosure Number: 2 <br />Enclosure Name: SUB -FLOOR <br />Minimum Design Concentration: 46.90% <br />Adiusted Design Concentration: 50.59% <br />Maximum Design Concentration: 52.00% <br />Minimum Predicted Concentration: 47.81% (At 70 F) <br />Maximum Predicted Concentration: 47.81% (At 70 F) <br />Maximum Allowed Enclosure Pressure: 5.0 lb / ft Z <br />Estimated Free Vent Area Required: 0.1 ft2 <br />Installed Vent Area: 0.0 ft2 <br />Predicted Enclosure Pressure: N/A <br />Maximum Enclosure Flow Rate: 0.3 Ib/s <br />Oxygen Concentration (Total Discharge): 10.9% <br />Calculation Date/Time: Monday, February 13, 2023, 1:26:29 PM <br />Copyright (c) JENSEN HUGHES, Inc. Licensed to: Kidde-Fenwal <br />KeyID:396621834 <br />Page: 4 of 11 <br />