Installation Application <br /> SIGA-CR and SIGA-CRR:modules mount to North American The operation of Signature Series control relays is determined by <br /> 2�h inch(64 mm)deep 1-gang boxes and 1 t/2 inch(38 mm)deep their sub-type code or"Personality Code." <br /> 4 inch square boxes with 1-gang covers and SIGA-MP mounting Personality Code 8:CONTROL RELAY(SIGA-CR/MCR) <br /> plates.The terminals are suited for#12 to#18 AWG(2.5 mm2 to <br /> 0.75 mm2)wire size. -Dry Contact Output.This setting configures the module to <br /> provide one Form"C" DRY RELAY CONTACT to control Door <br /> lc_ <br /> Closers, Fans, Dampers, etc. Contact rating is 2.0 amp @ <br /> Compatible electrical box 24 Vdc;0.5 amp @ 120 Vac(or 0.25A C�?220 Vac for non-UL <br /> applications). Personality Code 8 is assigned at the factory. No <br /> user configuration is required. <br /> P:11111 Personality Cade 8: POLARITY REVERSAL RELAY MODULE <br /> � (SIGA-CRRfMCRR).Thi€ oE!cfhe <br /> setting configures the Wlplatwhite reverse the olarit of its <br /> �' factory. No user configuration is required. <br /> I_'�J�.. o Compatibility <br /> 00•,• These modules are part of EDWARDS's Signature Series intelligent <br /> Status LEDs processing and control platform.They are compatible with EST3, <br /> LED viewing ports EST3X and i0 Series control panels. <br /> o, <br /> ` Warnings & Cautions <br /> This module will not operate without electrical power.As fires <br /> SIGA-MCR and SIGA-MCRR:mount the UIO motherboard frequently cause power interruption,we suggest you discuss <br /> inside a suitable EDWARDS enclosure with screws and washers further safeguards with your local fire protection specialist. <br /> provided. Plug the module into any available position on the <br /> motherboard and secure the module to the motherboard with the <br /> captive screws.Wiring connections are made to the terminals on Testing & Maintenance <br /> the motherboard (see wiring diagram). UIO motherboard terminals g <br /> are suited for#12 to#18 AWG(2.5 mm2 to 0.75 mm2)wire size. The module's automatic self-diagnosis identifies when it is <br /> defective and causes a trouble message.The user-friendly <br /> maintenance program shows the current state of each module <br /> UIO Motherboard and other pertinent messages. Single modules may be turned <br /> off(deactivated)temporarily,from the control panel.Availability of <br /> — — — maintenance features is dependent on the fire alarm system used. <br /> - - -f--- Scheduled maintenance(Regular or Selected)for proper system <br /> I Plug-in(UIO) operation should be planned to meet the requirements of the <br /> I Module Authority Having Jurisdiction(AHJ). Refer to current NFPA 72 and <br /> - ' {1--`1 ULC CAN/ULC 536 standards.-- <br /> - —1 <br /> Cabinet or electrical enclosure <br /> — <br /> Electronic Addressing-The loop controller electronically <br /> addresses each module, saving valuable time during system <br /> commissioning. Setting complicated switches or dials is not <br /> required. Each module has its own unique serial number stored <br /> in its on-board memory.The loop controller identifies each device <br /> on the loop and assigns a"soft"address to each serial number. <br /> If desired,the modules can be addressed using the SIGA-PRO <br /> Signature Program/Service Tool. <br /> EDWARDS recommends that this module be installed according <br /> to latest recognized edition of national and local fire alarm codes. <br /> Page 2 of 6 E85001-0239 <br /> Issue 1.1 <br />