feloa'ot <br /> BUILDING TECHNICAL SERVICES <br /> Deficiency Report <br /> PROJECT: Bezos Everett Transit Station DATE: 10/5/2022 <br /> LOCATION: Everett,WA CONTACT: Nicolas Hanson <br /> PROJECT#: 802031258 <br /> Issue ID: 0005 Status: Open Issue Priority: Low <br /> Equipment: AHU-EXISTING/VAV-01-17 Created Date: 05-Oct-22 <br /> Issue Description: <br /> 173% of design fan airflow at lowspeed <br /> Issue Type: Not Assigned Job Tag: Repair Estimate: <br /> Role Assignment: Company Administrator Cross Ref#: Replacement Cost: <br /> User Assignment: <br /> Issue ID: 0001 Status: Open Issue Priority: Medium <br /> Equipment: AHU-EXISTING/VAV-01-2A Created Date: 04-Oct-22 <br /> Issue Description: <br /> Bad transformer. No 24V. <br /> Issue Type: Not Assigned Job Tag: Repair Estimate: <br /> Role Assignment: Company Administrator Cross Ref#: Replacement Cost: <br /> User Assignment: <br /> Issue ID: 0003 Status: Open Issue Priority: Medium <br /> Equipment: AHU-EXISTING/VAV-01-4 Created Date: 05-Oct-22 <br /> Issue Description: <br /> Fan not running <br /> Issue Type: Not Assigned Job Tag: Repair Estimate: <br /> Role Assignment: Company Administrator Cross Ref#: Replacement Cost: <br /> User Assignment: <br /> Issue ID: 0006 Status: Open Issue Priority: Low <br /> Equipment: AHU-EXISTINGNAV-01-6 Created Date: 05-Oct-22 <br /> Issue Description: <br /> 141% of design fan airflow at lowspeed <br /> Issue Type: Not Assigned Job Tag: Repair Estimate: <br /> Role Assignment: Company Administrator Cross Ref#: Replacement Cost: <br /> User Assignment: <br /> Issue ID: 0007 Status: Open Issue Priority: High <br /> Equipment: EF-01 Created Date: 05-Oct-22 <br /> Issue Description: <br /> Outdoor louvers not installed, outlet blocked off with plywood. <br /> Issue Type: Not Assigned Job Tag: Repair Estimate: <br /> Role Assignment: Company Administrator Cross Ref#: Replacement Cost: <br /> User Assignment: <br /> Issue ID: 0008 Status: Open Issue Priority: High <br /> Equipment: EF-02 Created Date: 05-Oct-22 <br /> Issue Description: <br /> Outdoor louvers not installed, outlet blocked off with plywood. <br /> Issue Type: Not Assigned Job Tag: Repair Estimate: <br /> Role Assignment: Company Administrator Cross Ref#: Replacement Cost: <br /> User Assignment: <br /> Preliminary <br /> 10/05/2022 1 :04:54 PM Page 1 of 1 <br />