Laserfiche WebLink
Honeywell <br /> C o Analog and Networking Systems <br /> GWF-7075 <br /> Intelligent Fire Alarm Control Panel <br /> General <br /> The Gamewell-FCI®,GWF-7075 is an Addressable Fire Alarm Control Panel(FACP). <br /> The GWF-7075 has a signaling line circuit(SLC)loop that is used to connect the f - <br /> addressable detectors.The SLC loop is capable of supporting up to 75 detectors and <br /> 75 modules using the System Sensor®Velociti®Protocol,and it also offers the built-in <br /> support for the SWIFT'wireless fire alarm devices. <br /> The GWF-7075 is equipped with two configurable Notification Appliance Circuits <br /> (NACs)that support a maximum output of 2.5A.This panel communicates with the <br /> built-in,dual-line digital and IP communicator including an optional cellular <br /> communication module. <br /> The GWF-7075 fire alarm control panel offers the following powerful features: <br /> • detector sensitivity • pre-trouble maintenance alert <br /> • day/night thresholds • calibration trouble alert GWF-7075 <br /> • drift compensation <br /> The GWF-7075 panel supports a variety of devices,including the following <br /> accessories: <br /> • RA-1000 Remote Annunciator <br /> • 5880-LED I/O Module <br /> • GFPS-6S Intelligent Remote Power Supply <br /> • 5824 SeriaVParallel Printer Interface Module(for printing system reports) <br /> FEATURES & BENEFITS <br /> • Built-in support for up • GWF-7075 can be • Uses a JumpStart Auto • Firmware can be • Offers a built-in <br /> to 75 detectors and 75 surface or flush Programming''feature upgraded in the field synchronization for <br /> modules operating in mounted for easy programming appliances from <br /> Velociti" or CLIP mode • Supports up to four AMSECO'",Centex'. <br /> • Contains a built-in USB • System programmable SWIFT'"'wireless System Sensor',and <br /> • Offers a four line LCD interface used for from the front panel gateways.Each Wheelock'" <br /> display with 40 programming gateway may include <br /> characters per tine • Provides a built-in dual up to 49 wireless • Reports events to the <br /> • Includes the • phone line,digital devices Central Station by <br /> • Available in a red or a programmable date alarm communicator/ point or by zone <br /> black cabinet setting for Daylight transmitter(DACT).IP • Supports Class B(Style <br /> Saving Time or optional cellular 4)and Class A(Style 6 <br /> technologies or Style 7 configuration <br /> for SLC,and SBUS <br />