Laserfiche WebLink
CONTRACTUAL RESPONSIBLE PARTIES <br /> Fire Protection, Inc. : Monitoring, Design, Permits, Rough-in, Trim & <br /> System testing. <br /> SEQUENCE OF OPERATIONS <br /> All Alarm and Trouble conditions shall enunciate at FACP as well as <br /> remote notify UL listed Central Station. Zones of alarm shall cause <br /> for all notification circuits to activate, send alarm zone to CS, <br /> re-dispatch to Fire and dispatch FPI runner service. Trouble and <br /> supervisory signals shall transmit to CS which will dispatch FPI <br /> runner service to site, (no notification circuits shall activate. ) On <br /> site emergency contact personnel shall be notified. Wet Waterflow <br /> ALARMS shall be retarded by a period of not more than 45 seconds. Low <br /> air shall activate at 251bs, causing for a supervisory signal. An <br /> activation signal on FACP smoke, Waterflow Switches, (wet and dry) <br /> and pull station shall cause alarm. An activation signal on PIV, <br /> tamper and Hi-low air zones shall cause a Supervisory condition. <br /> Opens, shorts, and ground faults on any zones shall cause for a <br /> trouble signal. <br /> Should you have any further questions, please feel free to contact me <br /> directly. <br /> DAVID MOW, SET <br /> NICET IV #120904 <br /> VP of Operations / Designer of Record <br />