separation or a fire sprinkler system to be installed. It is unclear from the plans where this <br /> required separation construction (wall, floor construction, and opening protectives for doors <br /> and windows), or a fire sprinkler system is shown. Please clarify and revise plans as required. <br /> IBC 509, IBC Table 716.2, 716.3. <br /> 6. Please provide drawings for the ADA compliant bathroom shown in the proposed Sheet 2 as it <br /> appears to be missing from the plans. Drawings locating ADA hardware and appurtenances <br /> appear to be missing from the plans. IBC 107.2.1. <br /> 7. On Sheet 2,the proposed second floor appears to indicate portions of the "bar" area to where <br /> the refrigerators are located to have limited ceiling height. Please verify that that the ceiling <br /> height is maintaining a minimum of 7'-0" as it appears to be a kitchen space in these areas. <br /> Please clarify and revise plans as required. IBC 1207.2. <br /> 8. On Sheet 2,the proposed "bar" area would appear to require that these areas are accessible. The <br /> current configuration does not appear to meet the clearance requirements for a U-shaped <br /> kitchen. Please revise configuration as required. IBC 1109.4, ICC A117.1-2009 804. <br /> 9. Please clarify if the revised bathrooms are gender neutral as it appears that the previous <br /> configuration were single use occupancy restroom configurations from the existing conditions. <br /> IBC 2902.2.2. <br /> RESUBMITTAL REQUIREMENTS <br /> In order for the processing of your application to continue, it will be necessary to provide the Building <br /> Division with the following items: <br /> ❑ (2) New,complete sets of revised construction documents reflecting the corrections as <br /> required. <br /> ❑ (1) Response letter detailing how the corrections were resolved. <br /> All codes cited refer to the 2018 International Building Code (IBC), 2018 International Existing Building <br /> Code (IEBC),the 2018 International Fire Code (IFC),the 2018 International Mechanical Code (IMC), <br /> and/or the 2018 Washington State Energy Code (WSEC), as amended by the State of Washington and <br /> adopted by the City of Everett. The current IBC referenced standard for accessible design is the 2009 <br /> "Accessible and Usable Buildings and Facilities" (ICC/ANSI A117.1). Federal ADA regulations and <br /> standards may be more restrictive. <br /> These comments address building issues only.Additional revisions or additions may be required by <br /> other departments (such as Utilities,Traffic, Planning or Fire). All required submittals must be of <br /> sufficient detail and information to ensure that the proposed structure will be constructed in <br /> compliance with all adopted codes. <br /> Sincerely, <br /> James Bronder, PE, SE <br /> Associate Engineer <br /> Plans Examiner <br /> E Page 2 of 2 <br />