Laserfiche WebLink
James Bronder <br /> From: James Bronder <br /> Sent: Tuesday,January 11, 2022 11:01 AM <br /> To: terry@nwgrd.com <br /> Subject: Correction Notice 1 - M2109-068 <br /> Hi Terry, <br /> Please address the following comments regarding the Mechanical permit application: <br /> 1. Please specify the proposed range to be installed in the proposed kitchen. Provide cut sheets as required to <br /> best describe the proposed installation that demonstrates compatibility between the range and the hood being <br /> installed. Also, please describe the type of cooking that is occurring. Please note that the Type of Hood is to be <br /> compatible with the proposed range and type of cooking. Please clarify and revised plans as required. IMC <br /> 507.1.2. <br /> 2. Please provide additional details on the proposed hood based on the usage provisions of IMC 507.1.2. Please <br /> identify the construction and dimensional requirements such as clearances. For Type I hoods, see IMC 507.2 <br /> and for Type II hoods see IMC 507.3. <br /> 3. Drawings are unclear as to where the exhaust is terminating. Please provide a small detail elevation <br /> dimensionally indicating the exhaust location. For Type I exhaust requirements IMC 506.3.13, for Type II, IMC <br /> 506.4.2. <br /> Thank you, <br /> — James Bronder, P.E., S.E. <br /> Associate Engineer—Plans Examiner I Permit Services <br /> 425.257.8810 13200 Cedar Street, 2nd Floor, Everett, WA 98201 <br /> EVERETT Phone Hours: M/W/Th: 8 a.m.—12 p.m & 1 p.m.—3 p.m. <br /> everettwa.gov/permits I Facebook I Twitter <br /> Note:Emails and attachments sent to and from the City of Everett are public records and may be subject to disclosure pursuant to the Public <br /> Records Act. <br /> 1 <br />