Laserfiche WebLink
[6]SAMPLING TUBE INSTALLATION ing out of the duct,select a shorter tube using Table 1. Otherwise,trim <br /> [6.1]SAMPLING TUBE SELECTION the tube to leave approximately 1 to 2 inches extending outside the duct. <br /> The sampling tube must be purchased separately. Order the correct length, Plug the end with the end cap and tape closed any holes in the protrud- <br /> as specified in Table 1, for width of the duct where it will be installed. It is ing section of tube.Be sure to seal the duct where the tube protrudes. <br /> recommended that the sampling tube length extend at least 2/3 across the duct FIGURE 4. <br /> width for optimal performance. <br /> TABLE 1.SAMPLING TUBES RECOMMENDED FOR DIFFERENT 12- <br /> DUCT WIDTHS: <br /> Outside Duct Width Sampling Tube Recommended* <br /> Up to 1 ft. DST1 2- <br /> 1 to 2 ft. DST1.5 <br /> 2 to 4 ft. DST3 <br /> /4 DETECTOR <br /> 4 to 8 ft. DST5 HOLE <br /> 8 to 12 ft. DST10(2-piece) H0215-00 <br /> NOTE:Air currents inside the duct may cause excessive vibration,especially <br /> *Must extend a minimum of 2/3 the duct width. These sampling tubes can when the longer sampling tubes are used.In these cases,a 3 inch floor flange <br /> only be used with new InnovairFlex duct smoke detectors. (available at most plumbing supply stores) may be used to fasten the sam- <br /> The sampling tube is always installed with the air inlet holes facing into the pling tube to the other side of the duct. When using the flange/connector <br /> air flow.To assist proper installation,the tube's connector is marked with an mounting technique,drill a 1 to 1'/4 inch hole where the flange will be used. <br /> arrow.Make sure the sampling tube is mounted so that the arrow points into [6,3]MODIFICATIONS OF SAMPLING TUBES <br /> the airflow as shown in Figure 3.Mounting the detector housing in a vertical There may be applications where duct widths are not what is specified for the <br /> orientation is acceptable provided that the air flows directly into the sampling installation.In such cases,it is permissible to modify a sampling tube that is <br /> tube holes as indicated in Figure 3. The sampling tube and exhaust tube longer than necessary to span the duct width. <br /> can be mounted in either housing connection as long as the exhaust tube is <br /> mounted downstream from the sampling tube. Use a 0.193 inch diameter(u10)drill and add the appropriate number of holes <br /> so that the total number of holes exposed to the air flow in the duct is 10 to 12. <br /> FIGURE 3.AIR DUCT DETECTOR SAMPLING TUBE: Space the additional holes as evenly as possible over the length of the tube. <br /> SAMPLING TUBE ENDCAP NOTE:This procedure should only be used as a temporary fix and is not in- <br /> tended as a substitute for ordering the correct length tubes. <br /> ® ® ® [6.4]REMOTE SAMPLING TUBE INSTALLATION <br /> ® The detector arrangement can also incorporate remote mounting of the sam- <br /> pling tube and/or exhaust tube.In this case both the detector,sampling tube <br /> ® and exhaust tube (if included) should be rigidly mounted to withstand the <br /> pressure and vibrations caused by the air velocity.The location of the detec- <br /> ARROW MUST FACE AIR FLOW tor's sampling tube should be such that there is uniform airflow in the cross <br /> INTO AIR FLOW DIRECTION section area. <br /> H0551-00 The pressure differential across the sampling and exhaust ports in the detector <br /> CAUTION: The sampling tube end cap, included with the detector, is criti- housing shall be verified to be between 0.01 and 1.11 inches of water. Do so <br /> cal to proper operation of the duct smoke detector.The end cap is needed to by measuring the pressure difference between the inlet and outlet ports on the <br /> create the proper air flow to the sensor of the duct smoke detector.Once any detector housing using a manometer as described in Section 7.1. <br /> sampling tube length adjustments are made,plug the end of the sampling tube [7]MEASUREMENT TESTS <br /> with the provided end cap. <br /> [7.1]AIR FLOW <br /> A plastic exhaust tube is included with the unit to be installed if needed.In- The D4120 is designed to operate over an extended air speed range of 100 to <br /> stall into the housing connection that is downstream from the sampling tube 4000 FPM.To verify sufficient sampling of ducted air,turn the air handler on <br /> connection. The exhaust tube can be installed from the front or back of the and use a manometer to measure the differential pressure between the two <br /> detector.A longer 1 foot exhaust tube,model ETX,is available as an accessory sampling tubes.The differential pressure should measure at least 0.01 inches <br /> in cases where the molded exhaust tube does not extend at least 2 inches into of water and no more than 1.11 inches of water. Because most commercially <br /> the duct. available manometers cannot accurately measure very low pressure differen- <br /> [6.2]SAMPLING TUBE INSTALLATION tials,applications with less than 500 FPM of air speed may require one of the <br /> 1. For tubes shorter than the width of the duct, slide the sampling tube, following: 1)the use of a current-sourcing pressure transmitter(Dwyer Series <br /> with installed end cap,into the housing connection that meets the air- 607)per Section 7.2,or 2)the use of aerosol smoke per section 12.5.3. <br /> flow first.Position the tube so the arrow points into the airflow as shown [7.2]LOW FLOW AIR FLOW TEST USING DWYER SERIES 607 <br /> in Figure 3. Per NFPA sampling tubes over 3 feet long should be sup- DIFFERENTIAL PRESSURE TRANSMITTER <br /> ported at the end opposite the duct detector.In ducts wider than 8 feet, Verify the air speed of the duct using an anemometer. Air speed must be at <br /> work must be performed inside the duct to couple the other section of least 100 FPM.Wire the Dwyer transmitter as shown in Figure 5.Connect the <br /> the sampling tube to the section already installed using the'/2 inch con- leads of the meter to either side of the 1000Q resistor.Allow unit to warm up <br /> duit fitting. Make sure that the holes on both sections of the air inlet for 15 seconds.With both HIGH and LOW pressure ports open to ambient air, <br /> sampling tube are lined up and facing into the airflow. measure and record the voltage drop across the 100052 resistor(measurement <br /> 2. For tubes longer than the width of the duct,the tube should extend out 1),4.00 volts is typical.Using flexible tubing and rubber stoppers,connect the <br /> of the opposite side of the duct.Drill a 3/4 inch hole in the duct opposite HIGH side of the transmitter to the sampling tube of the duct smoke detec- <br /> the hole already cut for the sampling tube.Ensure that the sampling tube for housing, and the LOW side of the transmitter to the exhaust tube of the <br /> is angled downward from the duct smoke detector to allow for moisture duct smoke detector housing.Measure and record the voltage drop across the <br /> drainage away from the detector. The sampling tube should be angled 100052 resistor (measurement 2). Subtract the voltage recorded in measure- <br /> at least 1/4"downward for every 12"of duct width per Figure 4.There ment 1 from the voltage recorded in measurement 2.If the difference is greater <br /> should be 10 to 12 holes spaced as evenly as possible across the width of than 0.15 volts,there is enough air flow through the duct smoke detector for <br /> the duct.If there are more than 2 holes in the section of the tube extend- proper operation. <br /> 3 156-2967-008R <br /> 06-10 <br />