Laserfiche WebLink
• • <br /> b. The drawings should include penetration details for the walls separating the dwelling and <br /> the lobby. See IBC Section 714.4. <br /> c. Wall Type "W2" indicates an STC rating of 30 to 34. However, the listed assembly GA <br /> File No. WP3605 does not indicate this rating. The walls separating the dwelling and the <br /> lobby are required to have a minimum rating of 50. See IBC Section 1206.2. <br /> Response#4: <br /> See sheet A-1.1 for wall types specified on detail 2, as well as, revised wall type "W2" to <br /> indicated STC rating of 50 minimum. <br /> 5. Correction#5: <br /> The proposed construction will require repair to the horizontal assembly. The assembly <br /> requires a minimum one-hour construction. The required construction should be determined <br /> based on the configuration of the building, and a detail included in the construction drawings. <br /> See IBC Section 420.2 and Table 601. <br /> Response#5: <br /> See sheet A-1.1 for W1 and W2 1-hr wall types indicated on detail 2. <br /> 6. Correction#6: <br /> Proposed Plan 2/A-1.1 and the Door Schedule on Sheet A-2.1 specify a new 20-minute rated <br /> door between the stair shaft and the West Lobby. In addition,the door appears to be depicted <br /> as having a window per the plan. The stairway should be a shaft constructed as fire barriers <br /> with a minimum 2-hour rating per IBC Sections 713.2 and 713.4,respectively. The door should <br /> have a minimum 90-minute rating per Table 716.1(2). The door is not allowed to have a <br /> window unless it complies with the requirements and limits for a vision panel. <br /> Response#6: <br /> See sheet A-1.1 and A-2.1 for revised stairway scope to remain the same. <br /> Egress: <br /> 7. Correction#7: <br /> The Existing and Proposed Plans on Sheet A-1.1 includes installing a new door between the <br /> stairway and West Lobby. The door is located within one foot of the stairs and the north side of <br /> the stairs does not show a handrail. The building was originally permitted under the 2012 IBC <br /> and required a handrail on both sides;this requirement is still in effect even if the handrail was <br /> not installed during the original construction. The required handrail should be specified on the <br /> north side. Details for its construction should be specified. The door must comply with the <br /> minimum opening requirements or be eliminated. See IBC Sections 1005.3.2, 1010.1.1, <br /> 1011.11, 1014.2,and 1014.6. <br /> Response#7: <br /> See sheet A-1.1 and A-2.1 for revised stairway scope to remain the same. <br /> Accessibility <br /> 8. Correction#8: <br /> The project proposes converting the single bedroom unit to a studio unit. The original building <br /> design included Type A units as required by IBC Section 1107.6.2.2.1. The provided number <br /> and distribution of units may be impacted by the proposed design. An analysis should be <br /> performed to verify that the minimum number and distribution of units has been maintained. <br />