Laserfiche WebLink
STRING CALCULATIONS SYSTEM OCPD CALCULATIONS <br /> HOYMILES :HM-120ON(240V),HM-60ON(240V) STRING#1 STRING#2 STRING#3 STRING#4 STRING#5 INVERTER MODEL(S): HOYMILES HM-120ON(240V) HOYMILES HM-60ON(240V) <br /> MAX OUTPUT CURRENT 18.75A 18.75A 18.75A 18.75A 15.63A #OF INVERTER(S): 13 1 <br /> INVERTER IN SERIES: (3)HM-120ON (3)HM-120ON (3)HM-120ON (3)HM-120ON (1)HM-1200N,(1)HM-60ON MAX OUTPUT CURRENT: 5.00A 2.50A <br /> NOMINAL VOLTAGE/RANGE 211V-264V 211V-264V 211V-264V 211V-264V 211V-264V (#OF INVERTERS)X(MAX OUTPUT CURRENT) 65A 2.50A <br /> ARRAY OPERATING CURRENT: 360OW 360OW 360OW 360OW 180OW (#OF INVERTERS)X(MAX OUTPUT CURRENT)X 125%<=OCPD RATING <br /> ARRAY DC POWER: 2120OW (67.5A X 1.25)=84.38A<=90A,OK 5 L A R <br /> TOTAL MAX AC CURRENT: 67.5A PV LOAD CALCULATIONS:SUPPLY SIDE TIE-IN <br /> Revolution Energy Systems Inc. <br /> NUMBER OF CURRENT CARRYING CONDUCTORS PERCENT OF VALUES FEEDER WIRE RATING: 200A <br /> 4-6 .80 ALLOWABLE SOLAR CALCULATION 9981 West 190th St <br /> 7-9 .70 (FEEDER RATING=1.25) 160.00OOA(FEEDER WIRES ALLOWABLE SOLAR) Unit K Mokena IL 60448 <br /> 10-20 .50 160.000OA(AVAILABLE FOR PV) T: 708-995-1643 <br /> Conduit&Conductor Schedule <br /> TAG QTY WIRE GAUGE DESCRIPTION CONDUIT SIZE CONDUCTOR RATING CONDUCTOR TEMP.RATE AMBIENTTEMP TEMP.DERATE #OF CONDUCTORS CONDUCTOR RATING CONDUIT FILL <br /> DERATE W/DERATES <br /> 1 (2) 12 AWG AC-CABLE,COPPER(L1,L2) N/A-FREE AIR 30A 90°C 26°C 1.00 N/A-FREE AIR 30.OA N/A-FREE AIR <br /> (1) 12 AWG THWN-2COPPER-(GROUND) SITE INFORMATION <br /> (2) 10 AWG THHN/THWN-2,COPPER-(L1,L2) EDUARDO BOTELLO <br /> 3/4"PVC 40A 90°C 26°C 1.00 1.0 40.OA 12.03% <br /> 2 <br /> (1) 10 AWG THWN-2 COPPER-(GROUND) <br /> 706 LEGION DRIVE <br /> (10) 10 AWG THHN/THWN-2,COPPER-(L1,L2) <br /> 3 1"PVC 40A 90°C 26°C 1.00 0.8 32.OA 26.93% EVERETT,WA 98201 <br /> (1) 10 AWG THWN-2 COPPER-(GROUND) <br /> (3) 4 AWG THHN/THWN-2,COPPER-(L1,L2,NEUTRAL) AC System Size:16.20 kW AC/16.20 kVA <br /> 4 1-1/4"PVC 95A 90°C 26°C 1.00 1.0 95A 21.87% <br /> (11 6 AWG THWN-2 COPPER-(GROUND) DC System Size:21.20 kW DC <br /> 5 (3) 3 AWG THHN/THWN-2,COPPER-(Ll,L2,NEUTRAL) 1-1/4"PVC 100A 75°C 26°C 1.00 1.0 100A 25.89% Lat,48.0088921 <br /> (1) 6 AWG THWN-2 COPPER-(GROUND) Long,-122.1953944 <br /> (53)VSUN400-108BMH 400 <br /> PV Modules <br /> (13) HOYMILES HM-120ON(240V) <br /> (1) HOYMILES HM-60ON(240V) <br /> Inverter(s) <br /> SNOHOMISH PUD <br /> GROUNDING&GENERAL NOTES: INTERCONNECTION NOTES: <br /> 1. PV INVERTER IS UNGROUNDED,TRANSFORMER-LESS TYPE. 1. INTERCONNECTION SIZING, LIMITATIONS AND COMPLIANCE DETERMINED IN ACCORDANCE WITH [NEC <br /> 2. DC GEC AND AC EGC TO BE SPLICED TO EXISTING ELECTRODE 705.12],AND[NEC 690.64]. <br /> 2. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9], [NEC 230.95]AND[NEC 690.5] <br /> 3.ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS FOUND TO 3.ALL EQUIPMENT TO BE RATED FOR BACKFEEDING. <br /> BE INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION. 4. PV BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE BUSBAR RELATIVE TO THE MAIN BREAKER. <br /> 4.JUNCTION BOX QUANTITIES,AND PLACEMENT SUBJECT TO CHANGE IN THE FIELD- <br /> JUNCTION BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE DISCONNECT NOTES <br /> TRANSITIONS. 1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS <br /> 5.AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER REMAINING LIVE ARE CONNECTED TO THE TERMINALS MARKED"LINE SIDE"(TYPICALLY THE UPPER TERMINALS) DRAWN BY:V. MIRAFLOR <br /> AC DISCONNECTING MEANS IS LOCATED WITHIN 10'OF SERVICE DISCONNECT. 2.AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE,AND BE A DATE: <br /> VISIBLE-BREAK SWITCH 12/7/2023 <br /> ELECTRICAL CALCS- PV06 <br />