Laserfiche WebLink
Chvac-Full Commercial HVAC Loads Calculation Program Elite Software Development,Inc. <br /> Pacific Air Control, Inc. Maritime Institute <br /> Bothell,WA 98021 Page 4 <br /> Air Handler#1 - RTU-1 - Summary Loads <br /> Rm Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A. <br /> No Room Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM <br /> Volume CFM/S ft CFM/S ft W.Exh Act.CFM Act.CFM <br /> 100 Lobby 224 2,797 4,691 600 5/P, 5/P, <br /> 1 006/ft2 0.06/ft2 <br /> 4pm July 3 123 300 0 . <br /> 2,016 0.55 1.34 0 28 28 <br /> 41 33 <br /> 101 Admin 150 1,665 3,720 400 5/P, 5/P, <br /> 2 006/ft2 0.06/ftZ <br /> Spm July 2 73 238 0 . <br /> 1,350 0.49 1.59 0 19 19 <br /> 25 26 <br /> 105 Break 175 2,068 3,122 400 5/P, 5/P, <br /> 6 006/ft2 0.06/ft2 <br /> Sam July 2 91 200 0 . <br /> 1,575 0.52 1.14 0 21 21 <br /> 31 22 <br /> 106 Hallway 460 1,232 5,399 1,000 5/PZ 5 /P2 <br /> 7 6pm July 5 54 345 0 0.06/ft 0.06/ft <br /> 4,140 0.12 0.75 0 53 53 <br /> 18 38 <br /> 109 Storage 160 2,445 3,260 400 5/P, 5/P, <br /> 8 006/ft2 0.06/ft2 <br /> 1 pm September 2 108 208 0 . <br /> 1,440 0.67 1.30 0 20 20 <br /> 36 23 <br /> 110 Open Office 720 4,868 11,246 1,600 5/PZ 5/P2 <br /> 9 1 pm September 8 215 719 0 0.06/ft 0.06/ft <br /> 6,480 0.30 1.00 0 83 83 <br /> 72 80 <br /> Room Peak Totals: 1,889 15,074 31,439 4,400 <br /> Total Rooms: 6 22 665 2,009 0 223 223 <br /> Unique Rooms: 6 17,001 0.35 1.06 0 223 223 <br /> S:\Engineering\Chvac 8 Projects\Maritime Institute.CH8 Monday, October 23,2023,01:54 PM <br />