Laserfiche WebLink
4. Movable Equipment-Cooking equipment that are movable (casters or wheels)for El F] El <br /> the purpose of maintenance and cleaning shall be provided to ensure that it is <br /> properly returned and positioned for nozzle coverage. <br /> 5. Tethering Devices-Gas cooking equipment shall be provided with an approved <br /> tethering device.When casters are used,an approved heavy-duty, quick- <br /> disconnect,flexible gas lines must also be provided. <br /> 6. Equipment Spacing- Ensure that appliances spacing shall comply with the El El El <br /> following: <br /> • Cooking equipment must be spaced at least 6 inches apart from other <br /> cooking equipment. <br /> • Cooking equipment must be spaced at least 6 inches from walls. <br /> • The hood must overhang or extend a horizontal distance not less than 6- <br /> inches beyond the outer edges of the cooking surfaces. <br /> Piping <br /> PASS FAIL N/A <br /> 1. Specifications-Pipe,tubing, hose,fitting, hangers, and supports shall be in <br /> accordance with the manufacturer's design, installation, and maintenance manual. <br /> 2. Tightness-Piping shall be physically checked for tightness. 0 El El <br /> 3. Pipe Penetrations-All penetrations into and out of the ventilation hood and/or El El El <br /> duct is done with a listed seal off device that is liquid tight. <br /> Nozzles <br /> PASS FAIL N/A <br /> 1. As Per Plans- Ensure that all discharge nozzles are the type specified in the plans, El El <br /> permanently marked for identification, and listed for the intended use. <br /> 2. Distance-Inspect each type of nozzle and the required length from nozzle to heat D El El <br /> source. <br /> 3. Placement& Positioning-Verify that all discharge nozzles placement, position, El El El <br /> and orientation is per the specific installation manual and for the specific <br /> appliance. <br /> 4. Caps- Discharge nozzles shall be provided with caps or other suitable devices to El El El <br /> prevent the entrance of grease vapors, moisture,environmental contaminants,or <br /> other foreign materials into the piping.The caps or other devices shall blow off, <br /> blow open, or blow out upon agent discharge. <br /> 5. Obstructions-Address any obstructions such as shelves, hanging cooking El El El <br /> equipment,etc.that may impede the discharge and application of the system. <br /> Fire Marshal's Office 1425.257.8100 1 everetivra.yov/(ire I INFORMATION HANDOUT C-10 14.29.2020 I Paye 3 <br />