Laserfiche WebLink
Fusible Links/Detectors <br /> PASS FAIL N/A <br /> 1. Specifications-All fusible links shall be positioned in brackets per manufacturer's ❑ n ❑ <br /> specifications. <br /> 2. Placement-Verify that a fusible links or heat detectors are provided above each D El <br /> protected cooking appliance and at or within 12 inches of duct opening in <br /> accordance with the extinguishing system manufacturer's design, installation,and <br /> maintenance manual. (A single listed detection device shall be permitted for more <br /> than one appliance when installed in accordance with the system's listing.) <br /> 3. Temperature- Ensure that the appropriate temperature fusible links that is <br /> indicated on the plans are installed in the system. <br /> 4. Markings-The year of manufacture shall be stamped on all fusible links,and also <br /> marked on the system inspection tag. <br /> Agent Tanks & Mechanical Control Heads <br /> PASS FAIL N/A <br /> 1. Agent Tanks-Verify that all Agent Tanks comply with all of the following: ❑ El ❑ <br /> • Tanks provided on site are the same model as indicated on approved <br /> plans. <br /> • Quantity of tanks match approved plans. <br /> • Tanks are labeled UL3OO. <br /> • Tanks are filled to correct volume. <br /> • Tanks are fastened securely to their mounting brackets. <br /> 2. Control Heads-Verify Control Heads comply with the following: ❑ ❑ ❑ <br /> • Listed devices <br /> • Located in a safe location free from damage, high temperatures,and <br /> accessible. <br /> • Provided with a visual indicator to show that the system is in a ready <br /> condition or is in need of recharging. <br /> riri Wrr,lril f;(Afiice 1425.257.£3100 1 everelhva.gov/iire I INFORMATION IIANf)OUI (:-10 14.29.2020 I Page 4 <br />