Laserfiche WebLink
4. Exhaust Fan- Exhaust fans and dampers shall not be required to be shut down on ❑ F] El <br /> system actuation as the systems have been tested under both zero-and high- <br /> velocity flow conditions. <br /> Functional/Discharge Test <br /> Part 1 —Manual Functional/Discharge Test: PASS FAIL N/A <br /> 1. Fire Alarm Tech-If the building is equipped with a fire alarm system,a fire alarm <br /> tech shall be present so that the test can be done at one time.Also ensure that the <br /> fire alarm monitoring company have been notified and the system is on test. <br /> 2. Nitrogen or Dry Air-The manual functional discharge test shall be performed on El F] El <br /> the piping network using nitrogen or dry air at a pressure not to exceed the <br /> normal operating pressure of the extinguishing system. <br /> 3. Balloons- Balloons shall be placed on all discharge nozzles to indicate that the El R R <br /> lines are clear, and air can move freely through the lines. <br /> 4. Activate Manual Actuator-Initiate the test by having a member of the kitchen El R El <br /> staff or the contractor pull the manual actuator(pull station)to the system. <br /> 5. Force& Movement of Actuator-Verify that the manual actuator has a force less El 0 <br /> than 40 Ib and a movement of less than 14 inches to secure operation. <br /> 6. Balloon Volumes-All of the balloons shall inflate but may inflate at different El FJ El <br /> volumes depending on the flow rates of the nozzles. <br /> 7. Fire Alarm Activation-If the building is equipped with a fire alarm system,did the El R R <br /> activation of the system activate local notification device/bell and activate an <br /> alarm signal(clearly illustrating the type and location of alarm) at the fire alarm <br /> panel? <br /> 8. Power& Fuel Shutdown-Did the activation of the system shut down power and El R El <br /> fuel supply to All equipment protected under the hood and the makeup air <br /> suppling the hood? Does it have to be manually reset after system activation? <br /> 9. Exhaust Fan-Did the activation of the system turn on or keep on the exhaust fan El El El <br /> and did they continue to operate during and after then system discharge? <br /> 10. Visual Indicator- Did the visual indicator on the control head illustrate that the El El El <br /> system has operated? <br /> Dire Marr;I I'r (riiico 1425.257.8100 1 everethva.go0he I INFORMATION HANDOUT C-10 14.29.2020 I Paye 6 <br />