MODULE SPECIFICATIONS SIL-410 HC+ DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS
<br /> RATED POWER(STC) 410 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MICROINVERTER TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 10.9 A AC
<br /> MODULE VOC 45.59 V DC STATE Washington JUNCTION BOX(1) MAX.CURRENT(ISC X1.25)= 13.6 A AC
<br /> MODULE VMP 38.99 V DC CITY Everett CONDUCTOR(TC-ER,COPPER(90°C))= 12 AWG BLUE RAVE N
<br /> MODULE IMP 10.52 A DC WEATHER STATION SNOHOMISH CO CONDUCTOR RATING= 30 A
<br /> MODULE ISC 11.15 A DC ASHRAE EXTREME LOW TEMP(°C) -5 AMB.TEMP.AMP.CORRECTION= 1
<br /> VOC CORRECTION -0.28%/°C ASHRAE 2%AVG. HIGH TEMP(°C) 26 ADJUSTED AMP.= 30 > 13.6 1403 N. Research Way
<br /> VMP CORRECTION -0.36%/°C JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 10.9 A AC Orem, UT 84097
<br /> SERIES FUSE RATING 20 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR S CIR 6 JUNCTION BOX(2) MAX.CURRENT(ISC X1.25)= 13.6 A AC 800.377.4480
<br /> W W W.BLUERAVENSOLAR.COM
<br /> ADJ,MODULE VOC @ ASHRAE LOW TEMP 49.4 V DC NUMBER OF MODULES PER MPPT 9 CONDUCTOR(UF-B,COPPER(60°C))= 10 AWG
<br /> CONFIDENTIAL-THE INFORMATION
<br /> ADJ.MODULE VMP @ ASHRAE 2%AVG.HIGH TEMP 34.4 V DC DC POWER RATING PER CIRCUIT(STC) 3690 CONDUCTOR RATING= 30 A HEREIN CONTAINED SHALL NOT BE
<br /> TOTAL MODULE NUMBER 9 CONDUIT FILL DEBATE= 1 USED FOR THE BENEFIT OF ANYONE
<br /> EXCEPT BLUE RAVEN SOLAR NOR
<br /> MICROINVERTER SPECIFICATIONS Enphase IQ8+Microinverters STC RATING OF ARRAY 3690 AMB.TEMP.AMP.CORRECTION= 1 SHALL IT BE DISCLOSED IN WHOLE OR
<br /> IN PART TO OTHERS OUTSIDE
<br /> POWER POINTTRACKING(MPPT)MIN/MAX 30 - 58 V DC AC CURRENT @ MAX POWER POINT(IMP 10.9 ADJUSTED AMP.= 30 > 13.6 RECIPIENTS ORGANIZATION,EXCEPT
<br /> MAXIMUM INPUT VOLTAGE 60 V DC MAX.CURRENT(IMP X 1.25) 13.6125 JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 10.9 A AC IN CONNECTION WITH THE SALE AND
<br /> USE OF THE RESPECTIVE EQUIPMENT,
<br /> MAXIMUM DC SHORT CIRCUIT CURRENT 15 A DC OCPD CURRENT RATING PER CIRCUIT 20 COMBINER BOX(3) MAX.CURRENT(ISC X1.25)= 13.6 A AC WITHOUT THE WRITTEN PERMISSION
<br /> MAXIMUM USABLE DC INPUT POWER 440 W MAX.COMB_ARRAY AC CURRENT(IMP) 10.9 CONDUCTOR(UF-B,COPPER(60°C))= 10 AWG OF BLUE RAVEN SOLAR LLC.
<br /> MAXIMUM OUTPUT CURRENT 1.21 A AC MAX.ARRAY AC POWER 261OW AC CONDUCTOR RATING= 30 A
<br /> AC OVERCURRENT PROTECTION 20 A CONDUIT FILL DERATE= 1 NABCE P
<br /> MAXIMUM OUTPUT POWER 290W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. fRISE(V) VEND(V) %VRISE AMB.TEMP.AMP.CORRECTION= 1 CERTIFIED
<br /> CEC WEIGHTED EFFICIENCY 97 % VRISE SEC_1(MICRO TO JBOX) 32.4 12 CU- 1.18 241.18 0.49% ADJUSTED AMP_= 30 > 13.6
<br /> VRISE SEC.2(1BOX TO COMBINER BOX) 5o 10 Cu. 1.38 241.38 0.58% COMBINER BOX TO INVERTER RATED AMPS= 10.9 A AC PV INSTALLATION
<br /> AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC.3(COMBINER BOX TO POI) 5 10 Cu. 0.14 240.14 0.06% MAIN PV OCPD(15) MAX.CURRENT(RATED AMPS X1.25)= 13.61 A AC PROFESSIONAL
<br /> NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 2.70 242.70 1.12% CONDUCTOR(THWN-2,COPPER(75°C TERM.))= 10 AWG Scott Gumey
<br /> #PV-011719-015866
<br /> NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 35 A
<br /> MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690.54) CONDUIT FILLDERATE= 1 CONTRACTOR:
<br /> MAXIMUM AC CURRENT 1.0 A AC [NOMINAL
<br /> PUT CURRENT 10.9 A AC AMB.TEMP.AMP.CORRECTION= 1 BRS FIELD OPS
<br /> MAXIMUM OCPD RATING FOR AC MODULE 20 A AC AC VOLTAGE 240 V AC ADJUSTED AMP.= 35 > 13.6 1 800-377-4480
<br /> U U
<br /> GROUNDING NOTES WIRING & CONDUIT NOTES Z Q 0
<br /> 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.471 AND[NEC 250.50-601 SHALL BE 1.ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE O
<br /> PROVIDED. PER [NEC 690.47],THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. ,,``�G H 0 U co Scf co _�e
<br /> USED AND BE BONDED AT THE INADEQUATE,OR IS ONLY METALLIC WATER ENTRANCE. IF EXISTING SYSTEM IS PIPING,,A SUPPLEMENTAL GROUNDING ELECTRODE BWILL BE POBOLTED LARIS BLOCK OR NEOUTRALBAR)REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR(USE SOV OE a,1 sy�l�p� CQC -0 04
<br /> USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE M M CV M
<br /> 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED >
<br /> THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER)IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF Q O W W
<br /> PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. -`� ` LL 4- N N
<br /> SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE .O + Z �O 0) N N
<br /> 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS.
<br /> COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6.ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2, AND SINGLE-CONDUCTOR CABLE LISTED AND
<br /> 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.211,[NEC TABLE 250.1221,AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS
<br /> PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.461. REQUIRED. J V W M to W W
<br /> 5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE LU
<br /> �'`� 2 > >> �
<br /> 6.THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. O m (1)
<br /> MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE m
<br /> 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE N (.0 L_
<br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS. 310.15(B)(3)(A)],&[NEC 310.15(13)(3)(C)]. Q tv
<br /> 8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9.EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90°C RATED,WET AND UV RESISTANT,AND UL = C� CV > V V
<br /> GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP U G 00 W Q
<br /> 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES.
<br /> EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90°C RATED,
<br /> 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V DRAWING BY:
<br /> EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND
<br /> 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. Brendan Fillmore
<br /> MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION
<br /> DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS PLOT DATE:
<br /> 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC
<br /> GREEN
<br /> 3.ALL CONDUIT
<br /> IF
<br /> BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE POSITIVE-R LARGER). PIOSITIVE GROUN ED SYSTEMS DC COND CTORS COOLOR CODED:R MARKED GREY) February 1 , 2024
<br /> GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK)
<br /> 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.471, [NEC TABLE 250.661, DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR L1-BLACK,PHASE B OR L2-RED, PROJECT NUMBER:
<br /> ACCORDING TO[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY
<br /> 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE 908916
<br /> CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] **USE-2 IS AVAILABLE AS UV WHITE
<br /> REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES.
<br /> 18.IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, SHEET NAME:
<br /> FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.311, [NEC 250.118(10)1. DISCONNECTING /�
<br /> MEANS SHALL COMPLY WITH[NEC 690.131 AND[NEC 690.151. E LEC CALLS
<br /> 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH[NEC
<br /> 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)]. REVISION: PAGE NUMBER:
<br /> 0 PV6