• • <br /> Plan Check Number: B2208-005 <br /> A: Assembly aisles have been revised to comply with current code requirements. <br /> See A2.2 <br /> 9. The project requires accessibility improvements per IEBC Sections 305.6 and 305.7. <br /> Inaccessible areas including but are not limited to routes to the front entrance, rear exits at <br /> both levels, and the Main Floor bathrooms. <br /> A: Accessible routes have been revised to comply with current code for access aisle <br /> width behind unfixed seating between the bar and proposed stairs. Main floor <br /> restroom updated with signage for accessible use and grab bars to comply with <br /> current code requirements. See A2.2 <br /> 10.The Lower Level is required to comply with the accessibility requirements of Chapter 11 even <br /> though an accessible route is not required to the level. See Section 1101.2. <br /> A: Accessible routes have been revised to comply with current code for access aisle <br /> width behind unfixed seating between the bar and proposed stairs. See A2.2 <br /> 11. Both levels require two exits that must have accessible egress per IBC Section 1009.1. The <br /> routes to and landings for the stairs must be accessible, including exterior landings. <br /> A: All routes to egress exits have been verified and/or revised to comply with <br /> current IBC Section 1009.1 code. See A2.2 <br /> 12. Sheet A5.2 should specify that the grab bars include blocking capable of supporting a minimum <br /> 250 LB load. See IBC Section 1101.2 and ICC A117.1-09 Section 609.8. <br /> A: Notations have been added to grab bar detail on A5.2 <br /> Energy: <br /> 13.The basement level is required to comply with the insulation requirements for new construction <br /> per WSEC-18 Section C502.1. Details for insulating this level should be included. <br /> A: Basement Insulation information is provided on the building sections &wall type <br /> schedule. See A2.2 &A4.1 <br /> 14. Energy credits should the new conditioned space in the basement should be specified per <br /> WSEC-18 Section C406.1. The performance requirements should be specified in the drawings. <br /> A: See A2.2, A2.3 &A4.1 for Insulation & lighting energy information for basement <br /> expansion area. <br /> Miscellaneous: <br /> 15. Locks should be specified for all single-user restrooms per IBC Section 1209.3.1. <br /> A: Locks are specified in the Door schedule on A5.1 <br /> Structural <br /> 1. The project appears to include structural work, including but not limited to creating an opening <br /> in the main floor for a new stairway, and construction of a new stairway. Structural drawings <br /> should be prepared by a professional engineer licensed in the state of Washington. Framing <br /> plans and details should be provided per IBC Section 1603.1. Calculations substantiating the <br /> Page 3 of 4 <br />