Laserfiche WebLink
It <br /> • <br /> Plan Check Number: B2208-005 <br /> for additional discussion and the definition of"occupant load"in IBC Section 202. <br /> a. Minimum clear width of 44" (3'-8") revised. See A2.2 <br /> b. Continuing with the previous comments, modifications to the stair width will impact the <br /> required aisle clearances addressed in other comments. <br /> .a, Minimum aisle clearances have been reviewed and dimensioned. See A2.2 <br /> c. The rear corridor in the Lower Floor Plan on Sheet A2.2 should specify a minimum width of <br /> 44 inches per IBC Table 1020.2. <br /> a. Dimension added to rear Corridor to verify minimum width. See A2.2 <br /> d. The Kitchen Door leading to the Main Level rear corridor swings into the corridor and <br /> obstructs the width. The door swing should be reversed. Note that reversing the swing will <br /> have conflicts with accessibility requirements per ICC A117.1-09 Figure 404.2.3.2. See IBC <br /> Sections 1005.7, 1020.3, and 1101.2. <br /> a. Kitchen door leading to the rear corridor has been relocated and revised. <br /> See A2.2 Main Floor Plan <br /> e. This comment is provided for the designer's consideration. The corridor leading to the rear <br /> exit stairway is less than the minimum required width of 44 inches for new construction per <br /> IBC Table 1020.2. While this is an existing condition, the occupant load using the exit route <br /> may increase due to the proposed modifications. <br /> a. N/A <br /> 4. The main dining area at Lower Floor should be provided with maximum occupant load sign per <br /> IBC Section 1004.9. The location of the signs should be specified in the floor plans. <br /> a. In addition to the existing occupancy plan notes that states the location <br /> for the occupancy signage and notation on the plan has been added in this <br /> location. <br /> 5. The following comments should be addressed for the exit signs: <br /> a. The Main Floor signs at the front exit and the rear corridor should be relocated for visibility. <br /> a. Signs are existing and are visible. <br /> b. An additional sign should be provided at the Lower Floor at the entrance to the rear corridor <br /> from the Seating Area. <br /> a. An additional sign has been shown. See A2.0, A2.2 &A2.3 lower floor <br /> c. Exit signs should be consistently shown in the Occupancy Plans on Sheet A2.0 with the Floor <br /> Plans on Sheet A2.2. <br /> a. Drawings have been revised to show signs consistently. See A2.0 &A2.2 <br /> 6. The following comments should be addressed for the emergency means-of-egress illumination: <br /> a. The lighting shall specify a minimum 90-minute uninterrupted supply power per IBC Section <br /> 1008.3.4. <br /> a. A notation is provide on the Reflected ceiling plan specifying min. 90- <br /> Minute uninterrupted supply power. The notation has also been add to the <br /> Occupancy and floor plans. See A2.0,A2.2 <br /> b. Exterior lights should be shown at all exits per IBC Section 1008.3.2(5). An additional light <br /> at the main entrance of the Main Floor should be provided. <br /> a. Exterior light shown and added to the floor plans. See A2.0, A2.2 &A2.3 <br /> c. Egress lighting should be consistently shown in the Occupancy Plans on Sheet A2.0 with the <br /> Floor Plans on Sheet A2.2. <br /> a. Egress lighting revised to show consistently. See a2.0, A2.2 &A2.3 <br /> Page 2 of 4 <br />