ECU PSE Seattle Genetics 8/4/2023 <br /> ENGINEERING Everett,WA 98203 RVC <br /> Anchor Analysis: <br /> Anchor Properties <br /> Anchor Mfg. = Hilti <br /> Anchor= Kwik Bolt TZ2 <br /> ESR- 4266 Evaluation Service Report <br /> dia= 0.50 in. Anchor Diameter <br /> hnom= 3.7500 in. Nominal Embedment <br /> hef= 3.2500 in. Effective Embedment <br /> Sm;n= 2.00 in. Minimum Anchor Spacing <br /> f'c= 3000 psi Concrete Compressive Strength <br /> no= 2 Overstrength Factor <br /> p= 1.3 Redundancy factor <br /> SDC= D Seismic Design Category <br /> t seis= 0.75 Seismic Reduction Factor for SDC C,D,or E <br /> Pu= 3239 lbs. Ultimate Uplift per Anchor Group <br /> V„= 3008 lbs. Ultimate Shear per Anchor Group <br /> Check For Anchor Strength-Uplift <br /> N = 4 Number of Anchors in Group <br /> fya= 96.3 ksi Min.Specified Yield Strength(Neck) <br /> fun= 114.0 ksi Min. Specified Ultimate Tensile Strength (Neck) <br /> Ase,N= 0.099 in.2 Effective Tensile Stress Area (Neck) <br /> Nsa= 11240 lbs. Steel Strength in Tension <br /> = 0.75 Strength Reduction Factor <br /> (kNsa= 8430 lbs. Factored Capacity per Each Anchor <br /> Nua= 810 lbs. Ultimate Uplift per Anchor <br /> Nua/�Nn= 0.10 OK Utilization Such That 4Nsa>_ Nua <br /> Check For Anchor Pullout-Uplift <br /> N = 4 Number of Anchors in Group <br /> Np,cr= NA lbs. Pull Out Strength of a Single Anchor in Cracked Concrete <br /> Nu= NA lbs. Adjusted Pull Out Strength for Cracked Concrete <br /> tPc,p= 1 Modification Factor for Uncracked Concrete (ACI Sec. 17.4.3.6) <br /> = 0.65 Strength Reduction Factor <br /> kNp,eq= NA lbs. Factored Pull Out Strength per Anchor <br /> Nua= 810 lbs. Ultimate Uplift per One Anchor <br /> Nua/ckNn= NA NA Utilization Such That 4Np,eq>_ N„a <br /> 48/49 <br />