Mr. Eric Evans <br />Shelter Holdings <br />Plan Check Number: B1912-032, First Structural Review <br />January 3, 2020 <br />Gravity System: <br />12. The structural calculations for the Level 2 post -tensioned concrete slab include a 150 psf <br />unreducible live load. Based on five floors of tributary load at 40 psf, the live load should be at <br />least 200 psf. It is not clear if the load has been reduced per IBC Section 1607.10. <br />Supplemental documentation substantiating the live load shall be submitted for review. See <br />IBC Section 1604.4. <br />13. The post -tensioned reinforcement for the Level 2 concrete slab is provided on Sheets 53.11B <br />and 53.12B. See IBC Sections 1603.1 and 1901.5 Item 3. The following comments shall be <br />addressed: <br />a. The extend of the distributed tendons between Grids 7 and 8 should be specified. <br />b. The floor at Grid D.3-E/7.5-8 does not appear to be provided with distributed tendons and <br />my be required to perform as a mildly -reinforced slab. The design should be clarified. <br />Calculations substantiating the slab design shall be submitted for review as needed. <br />c. The floor at Grid C-E/18.5-20 is effectively discontinuous at the pour strip and acts as a <br />cantilever from the column line at Grid 20. The plans specify a tendon depth of 2.75 inches <br />while the calculations are based on a depth of 6.5 inches. The design should be reviewed <br />and revised as needed. <br />d. The stair landing at Grid D-D.3/7-8 is located at the south end on Sheet 53.11B. The <br />structural calculations show the landing at the north end. The design should be reviewed <br />and revised as needed. <br />14. The mild reinforcement for the Level 2 concrete slab is provided on Sheets 53.21B and 53.22B. <br />The plans appear to be missing reinforcement, and should be reviewed and revised as needed. <br />See IBC Sections 1603.1 and 1901.5 Item 3. The following comments shall be addressed: <br />a. The plans appear to show column reinforcement at some but not all locations on Sheet <br />53.21B. The plans do not appear to identify any typical conditions. <br />b. The slab on Sheet 53.21B includes openings at Grids D-D.3/7-8 and E-G/7.5-8 without <br />perimeter reinforcement. See Sheet 53.22B providing reinforcement around the openings. <br />c. Sheet 53.21B includes multiple openings with perimeter reinforcement. The does not <br />appear to be completely specified. <br />d. The slab includes landings within the concrete walls at Grids D-D.3/7-8, G.7-H/19.2-20.5, <br />and N-0/20.7-21. In appears that at least some of the slabs are intended to be mildly - <br />reinforced only, but are generally not provided with reinforcement. <br />e. Continuing with the previous comment, Bar Type R9 is specified near the landing at Grid <br />G.7-H/19.2-20.5. The specified bar length is 9 feet, which only extends to the middle of the <br />landing. Note that the bars appear intended to reinforce the cantilever slab along the pour <br />joint rather than the stair landing. <br />15. The floor weight in the structural calculations is estimated to be 25 psf and does not appear to <br />include a component for the interior non -bearing walls. Similarly, the floor framing has been <br />designed for a dead load of 25 psf. Revised calculations should be submitted for review that <br />substantiate the floor framing design including additional weight for the non -bearing walls. <br />3200 <br />dar <br />0 Everett WAStreet98201 O 425.257.88577 fax O everett asgov/permitgov <br />s <br />Page 5 of 7 <br />