AC <br /> w�^ <br /> TESTING ANO Ca A~Ry <br /> SERVICES <br /> • EVERGREEN MANOR <br /> • • EVERETT,WA <br /> • • 2220161 <br /> • <br /> BRUCE HURLBUT <br /> ERV-1 <br /> • S WING LVL 2 UNITS <br /> AREA SERVED NO. CODE SIZE AK DESIGN INITIAL %OF OF <br /> FPM CFM FPM CFM DESIGN FPM CFM DESIGN <br /> RS/STAFF 9 CD-2 6X6 F. H. 15 63 420% - 15 1000/0 <br /> MED 10 CD-2 6X6 F. H. 10 10 1000/0 - 10 1000/0 <br /> PHONE 11 CD-2 6X6 F. H. 10 it 1100/0 15 1500/0 <br /> PG TOTAL 35 84 240% 40 114% <br /> TOTAL SUPPLY 300 399 133% 331 1100/0 <br /> RR UNIT 18 El EG-2 6X6 F. H. 30 25 83% 30 1000/0 <br /> RR UNIT 17 E2 EG-2 6X6 F. H. 30 32 107% 32 107% <br /> RR UNIT 16 E3 EG-2 6X6 F. H. 30 32 107% 31 103% <br /> RR UNIT 15 E4 EG-2 6X6 F. H. 30 35 117% 33 110% <br /> RR UNIT 14 E5 EG-2 6X6 F. H. 30 38 127% 33 1100/0 <br /> RR UNIT 13 E6 EG-2 6X6 F. H. 30 68 227% 32 107% <br /> RR UNIT 12 E7 EG-2 6X6 F. H. 30 32 107% 32 107% <br /> CORRIDOR E8 RG-2 8X8 F. H. 55 65 1180/0 54 98% <br /> RS/STAFF E9 RG-2 6X6 F. H. 25 24 96% 25 1000/0 <br /> PHONE E10 RG-2 6X6 F. H. 10 16 160% 16 160% <br /> EXHAUST 300 367 122% 318 106% <br /> EXHAUST REGISTER#E10 HAS ITS BALANCING DAMPER IN A FULL CLOSED POSITION. NO OBJECTIONABLE NOISE OR DRAFT NOTED. <br /> FORM ID:LOW VELOCITY TEST SHEET <br /> 10/24/2023 <br /> Page 27 of 56 <br />